SPEC 81132

15kV AL 133% EPR (EAM) One-Third Neutral LLDPE

Single Conductor, 220 Mils Ethylene Propylene Rubber (EPR) / Ethylene Alkene Copolymer (EAM), 133% Insulation Level, One-third Concentric Neutral, Linear Low Density Polyethylene (LLDPE) Jacket. Silicone Free

...

Construction:

  1. Conductor:Moisture blocked class B compressed Aluminum ASTM B231 1350 ¾ hard H16/H26 ( Non Moisture Blocked Optional )
  2. Conductor Shield:Conventional Semi-conducting cross-linked copolymer; A conductor tape is used for cable size larger than or equal to 1500 Kcmil
  3. Insulation:220 Mils Ethylene Propylene Rubber (EPR) / Ethylene Alkene Copolymer (EAM) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Neutral:Helically applied soft drawn bare copper one-third concentric neutral
  6. Overall Jacket:Linear Low Density Polyethylene (LLDPE) Jacket, black with red extruded stripes; PowerGlide® LLDPE jacket optional

Applications and Features:

Southwire's 15kV cables are suited for use in wet and dry areas, conduits, ducts, direct burial, sunlight, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation. 140°C for emergency overload, and 250°C for short circuit conditions. Jacket types available that can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications:

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Rural Utility Standard RUS 1728F-U1 or 1728.204 (Electric standards and specifications for materials and construction)
  • UL 1072 Listed as MV 90 When Specified
  • Optional CSA 68.5: -40ºC and MV 90ºC optional marking available upon request
  • Sample Print Legend:

    SOUTHWIRE HI-DRI(R) [CONDUCTOR SIZE] [AWG or KCMIL] AL 15000 VOLTS EPR INSULATION 220 MILS -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    TBA2 (Solid)0.2570.7352200.8256x140.438501.0534908.4398
    6295602 (7)0.2820.7532200.8436x140.438501.0715338.6398
    TBA1 (Solid)0.2890.7672200.8576x140.438501.0855258.7502
    TBA1 (19)0.3220.8002200.8906x140.438501.1185438.9502
    6043991/0 (Solid)0.3240.7952200.8856x140.438501.1135888.9633
    6178751/0 (19)0.3510.8222200.9126x140.438501.1406139.1633
    6295622/0 (19)0.3950.8652200.9557x140.375501.1837589.5798
    TBA3/0 (19)0.4430.9212201.0119x140.292501.2397299.91006
    6161354/0 (19)0.4980.9682201.05811x140.239501.28686710.31269
    604040#4/0 (19)0.4980.9682201.05811x140.239501.28686810.31269
    6603154/0 (19)0.5120.9682201.0680.3501.28686791269
    TBA250 (37)0.5581.0442201.15413x140.202501.38295211.11500
    629565350 (37)0.6611.1472201.25718x140.146501.485122511.92100
    616186500 (37)0.7891.2692201.37916x120.103751.640158013.13000
    617104750 (61)0.9681.4582201.56824x120.069751.883216815.14500
    660002750 (61)0.9681.4582201.56815x100.069751.925221615.44500
    6168371000 (61)1.1171.6072201.74720x100.052752.104278916.86000
    6251811500 (91)1.3701.8702202.01030x100.034752.367380618.99000
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    # Hi-Dri-Plus® water blocking powder under jacket
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence ImpedancePositive Sequence ImpedanceShort Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (Solid)0.1620.2040.0470.0540.18213.60.257 + j1.2770.204 + j0.5732092120150
    2 (7)0.2660.3360.0440.0520.19414.40.389 + j1.2200.336 + j0.5162092120150
    1 (Solid)0.1290.1620.0440.0520.19414.40.215 + j1.2070.162 + j0.5042092140175
    1 (19)0.2110.2660.0410.0500.20715.40.319 + j1.1480.266 + j0.4472092140175
    1/0 (Solid)0.1020.1280.0400.0500.21115.70.181 + j1.1440.128 + j0.4432092155195
    1/0 (19)0.1670.2110.0380.0490.22216.50.264 + j1.1040.211 + j0.4052092155195
    2/0 (19)0.1330.1670.0360.0470.23617.60.221 + j1.0530.167 + j0.3552441180220
    3/0 (19)0.1050.1320.0330.0450.25519.00.186 + j1.0080.132 + j0.3113138200250
    4/0 (19)0.0840.1050.0300.0440.28020.90.159 + j0.9670.105 + j0.2713836235285
    4/0 (19)0.0840.1050.0300.0440.28020.90.159 + j0.9670.105 + j0.2713836235285
    4/0 (19)0.0840.1150.0380.0270.232.010.221+j0.3370.117+j0.0483839235285
    250 (37)0.0710.0900.0280.0430.30322.60.144 + j0.9290.090 + j0.2384533256309
    350 (37)0.0500.0650.0250.0400.34325.50.119 + j0.8810.065 + j0.1946277310370
    500 (37)0.0350.0460.0210.0390.39629.50.100 + j0.8360.046 + j0.1568865370445
    750 (61)0.0240.0330.0180.0370.46934.90.087 + j0.7920.033 + j0.12113298460525
    750 (61)0.0240.0330.0180.0380.46934.90.087 + j0.7900.033 + j0.12213211460525
    1000 (61)0.0180.0260.0160.0360.52739.30.080 + j0.7640.026 + j0.10117615520575
    1500 (91)0.0120.0210.0130.0340.61846.00.075 + j0.7320.021 + j0.07726423
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    TBA2 (Solid)6.5318.675.5920.966x141.441.2726.75729213.361771
    6295602 (7)7.1619.135.5921.416x141.441.2727.20793218.441771
    TBA1 (Solid)7.3419.485.5921.776x141.441.2727.56781220.982234
    TBA1 (19)8.1820.325.5922.616x141.441.2728.40808226.062234
    6043991/0 (Solid)8.2320.195.5922.486x141.441.2728.27875226.062817
    6178751/0 (19)8.9220.885.5923.166x141.441.2728.96912231.142817
    6295622/0 (19)10.0321.975.5924.267x141.231.2730.051128241.303551
    TBA3/0 (19)11.2523.395.5925.689x140.961.2731.471085251.464477
    6161354/0 (19)12.6524.595.5926.8711x140.781.2732.661290261.625647
    604040#4/0 (19)12.6524.595.5926.8711x140.781.2732.661292261.625647
    6603154/0 (19)13.0024.595.5927.130.981.2732.661290228.605647
    TBA250 (37)14.1726.525.5929.3113x140.661.2735.101417281.946675
    629565350 (37)16.7929.135.5931.9318x140.481.2737.721823302.269345
    616186500 (37)20.0432.235.5935.0316x120.341.9141.662351332.7413350
    617104750 (61)24.5937.035.5939.8324x120.231.9147.833226383.5420025
    660002750 (61)24.5937.035.5939.8315x100.231.9148.893298391.1620025
    6168371000 (61)28.3740.825.5944.3720x100.171.9153.444150426.7226700
    6251811500 (91)34.8047.505.5951.0530x100.111.9160.125664480.0640050
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    # Hi-Dri-Plus® water blocking powder under jacket
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2 (Solid)0.53150.670.01430.17720.59744.61940.257 + j1.2770.204 + j0.5732092120150
    2 (7)0.87271.100.01340.17060.63647.24410.389 + j1.2200.336 + j0.5162092120150
    1 (Solid)0.42320.530.01340.17060.63647.24410.215 + j1.2070.162 + j0.5042092140175
    1 (19)0.69230.870.01250.16400.67950.52490.319 + j1.1480.266 + j0.4472092140175
    1/0 (Solid)0.33460.420.01220.16400.69251.50920.181 + j1.1440.128 + j0.4432092155195
    1/0 (19)0.54790.690.01160.16080.72854.13390.264 + j1.1040.211 + j0.4052092155195
    2/0 (19)0.43640.550.01100.15420.77457.74280.221 + j1.0530.167 + j0.3552441180220
    3/0 (19)0.34450.430.01010.14760.83762.33600.186 + j1.0080.132 + j0.3113138200250
    4/0 (19)0.27560.340.00910.14440.91968.56960.159 + j0.9670.105 + j0.2713836235285
    4/0 (19)0.27560.340.00910.14440.91968.56960.159 + j0.9670.105 + j0.2713836235285
    4/0 (19)0.27560.380.01160.08860.7556.59450.221+j0.3370.117+j0.0483839235285
    250 (37)0.23290.300.00850.14110.99474.14700.144 + j0.9290.090 + j0.2384533256309
    350 (37)0.16400.210.00760.13121.12583.66140.119 + j0.8810.065 + j0.1946277310370
    500 (37)0.11480.150.00640.12801.29996.78480.100 + j0.8360.046 + j0.1568865370445
    750 (61)0.07870.110.00550.12141.539114.50130.087 + j0.7920.033 + j0.12113298460525
    750 (61)0.07870.110.00550.12471.539114.50130.087 + j0.7900.033 + j0.12213211460525
    1000 (61)0.05910.090.00490.11811.729128.93700.080 + j0.7640.026 + j0.10117615520575
    1500 (91)0.03940.070.00400.11152.028150.91860.075 + j0.7320.021 + j0.07726423
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.