SPEC 26672
HVTECK AL 3/C 420TRXLPE TS PVC AIA PVC 35kV 133% CSA
3 Conductor, 420 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:420 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Filler:Interstices filled with non-hydroscoping/non-wicking fillers
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 35kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 420 TRXLPE AIA 35kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 1/0 | 19 | 0.336 | 1.214 | 420 | 1.274 | 1x6 | 125 | 3.338 | 85 | 3.508 | 401 | 3985 | 4.5 |
| 2/0 | 19 | 0.376 | 1.254 | 420 | 1.314 | 1x6 | 125 | 3.424 | 85 | 3.594 | 411 | 4212 | 4.5 |
| 3/0 | 19 | 0.423 | 1.301 | 420 | 1.361 | 1x6 | 125 | 3.526 | 85 | 3.696 | 423 | 4487 | 5 |
| 4/0 | 19 | 0.475 | 1.353 | 420 | 1.413 | 1x6 | 125 | 3.638 | 85 | 3.808 | 436 | 4804 | 5 |
| 250 | 37 | 0.52 | 1.406 | 420 | 1.466 | 1x4 | 125 | 3.753 | 85 | 3.923 | 496 | 5169 | 5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1/0 | 24.6 | 1900 | 0.167 | 0.229 | 0.08 | 0.037 | 0.581+j0.320 | 0.229+j0.051 | 3978 | 181 | 200 |
| 2/0 | 25.2 | 2395 | 0.133 | 0.182 | 0.075 | 0.035 | 0.531+j0.309 | 0.182+j0.049 | 4102 | 208 | 228 |
| 3/0 | 25.9 | 3020 | 0.105 | 0.144 | 0.071 | 0.033 | 0.490+j0.296 | 0.144+j0.047 | 4248 | 239 | 258 |
| 4/0 | 26.7 | 3808 | 0.084 | 0.115 | 0.066 | 0.031 | 0.456+j0.282 | 0.115+j0.046 | 4409 | 273 | 292 |
| 250 | 27.5 | 4500 | 0.07 | 0.096 | 0.062 | 0.03 | 0.433+j0.270 | 0.096+j0.044 | 4573 | 302 | 321 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km | kg/km | inch |
| 1/0 | 19 | 8.53 | 30.84 | 10.67 | 32.36 | 1x6 | 3.18 | 84.79 | 2.16 | 89.10 | 597 | 5930 | 4.5 |
| 2/0 | 19 | 9.55 | 31.85 | 10.67 | 33.38 | 1x6 | 3.18 | 86.97 | 2.16 | 91.29 | 612 | 6268 | 4.5 |
| 3/0 | 19 | 10.74 | 33.05 | 10.67 | 34.57 | 1x6 | 3.18 | 89.56 | 2.16 | 93.88 | 629 | 6677 | 5 |
| 4/0 | 19 | 12.07 | 34.37 | 10.67 | 35.89 | 1x6 | 3.18 | 92.41 | 2.16 | 96.72 | 649 | 7149 | 5 |
| 250 | 37 | 13.21 | 35.71 | 10.67 | 37.24 | 1x4 | 3.18 | 95.33 | 2.16 | 99.64 | 738 | 7692 | 5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1/0 | 624.84 | 8455 | 0.5479 | 0.75 | 0.0244 | 0.1214 | 0.581+j0.320 | 0.229+j0.051 | 3978 | 181 | 200 |
| 2/0 | 640.08 | 10658 | 0.4364 | 0.60 | 0.0229 | 0.1148 | 0.531+j0.309 | 0.182+j0.049 | 4102 | 208 | 228 |
| 3/0 | 657.86 | 13439 | 0.3445 | 0.47 | 0.0216 | 0.1083 | 0.490+j0.296 | 0.144+j0.047 | 4248 | 239 | 258 |
| 4/0 | 678.18 | 16946 | 0.2756 | 0.38 | 0.0201 | 0.1017 | 0.456+j0.282 | 0.115+j0.046 | 4409 | 273 | 292 |
| 250 | 698.50 | 20025 | 0.2297 | 0.31 | 0.0189 | 0.0984 | 0.433+j0.270 | 0.096+j0.044 | 4573 | 302 | 321 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
Revision: 1.000.001
Updated On: Dec. 31, 2024, 11:07 p.m. UTC