SPEC 26626
HVTECK AL 1/C 420NLEPR CB PVC AIA PVC 35kV 133% CSA
Single Conductor, 420 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:420 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
- Neutral Separator:Mylar tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 35kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 420 NLEPR AIA 35kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 1/0 | 19 | 0.336 | 1.214 | 420 | 1.274 | 5x12 | 110 | 2.094 | 60 | 2.214 | 186 | 2384 | 6 |
| 2/0 | 19 | 0.376 | 1.254 | 420 | 1.314 | 7x12 | 110 | 2.134 | 60 | 2.254 | 237 | 2528 | 6 |
| 3/0 | 19 | 0.423 | 1.301 | 420 | 1.361 | 7x12 | 110 | 2.181 | 60 | 2.301 | 241 | 2642 | 6 |
| 4/0 | 19 | 0.475 | 1.353 | 420 | 1.413 | 7x12 | 110 | 2.233 | 60 | 2.353 | 245 | 2773 | 6 |
| 250 | 37 | 0.52 | 1.406 | 420 | 1.466 | 9x12 | 110 | 2.286 | 75 | 2.436 | 288 | 3008 | 6.5 |
| 350 | 37 | 0.616 | 1.502 | 420 | 1.562 | 11x12 | 110 | 2.382 | 75 | 2.532 | 333 | 3310 | 6.5 |
| 500 | 37 | 0.736 | 1.622 | 420 | 1.682 | 13x12 | 110 | 2.502 | 75 | 2.652 | 397 | 3718 | 7 |
| 750 | 61 | 0.908 | 1.804 | 420 | 1.864 | 17x12 | 110 | 2.684 | 75 | 2.834 | 479 | 4352 | 7.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1/0 | 15.5 | 633 | 0.167 | 0.229 | 0.061 | 0.065 | 0.520+j0.207 | 0.232+j0.069 | 2770 | 221 | 219 |
| 2/0 | 15.8 | 798 | 0.133 | 0.182 | 0.058 | 0.063 | 0.421+j0.136 | 0.186+j0.066 | 3879 | 253 | 246 |
| 3/0 | 16.1 | 1006 | 0.105 | 0.144 | 0.054 | 0.061 | 0.383+j0.135 | 0.147+j0.064 | 3879 | 288 | 275 |
| 4/0 | 16.5 | 1269 | 0.084 | 0.115 | 0.051 | 0.058 | 0.354+j0.133 | 0.118+j0.062 | 3879 | 327 | 305 |
| 250 | 17.1 | 1500 | 0.07 | 0.096 | 0.047 | 0.057 | 0.295+j0.096 | 0.100+j0.060 | 4987 | 367 | 343 |
| 350 | 17.7 | 2100 | 0.051 | 0.07 | 0.043 | 0.054 | 0.239+j0.074 | 0.075+j0.057 | 6095 | 443 | 399 |
| 500 | 18.6 | 3000 | 0.036 | 0.05 | 0.038 | 0.051 | 0.196+j0.059 | 0.056+j0.054 | 7203 | 529 | 451 |
| 750 | 19.8 | 4500 | 0.023 | 0.033 | 0.033 | 0.048 | 0.148+j0.043 | 0.040+j0.050 | 9420 | 633 | 505 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km | kg/km | inch |
| 1/0 | 19 | 8.53 | 30.84 | 10.67 | 32.36 | 5x12 | 2.79 | 53.19 | 1.52 | 56.24 | 277 | 3548 | 6 |
| 2/0 | 19 | 9.55 | 31.85 | 10.67 | 33.38 | 7x12 | 2.79 | 54.20 | 1.52 | 57.25 | 353 | 3762 | 6 |
| 3/0 | 19 | 10.74 | 33.05 | 10.67 | 34.57 | 7x12 | 2.79 | 55.40 | 1.52 | 58.45 | 359 | 3932 | 6 |
| 4/0 | 19 | 12.07 | 34.37 | 10.67 | 35.89 | 7x12 | 2.79 | 56.72 | 1.52 | 59.77 | 365 | 4127 | 6 |
| 250 | 37 | 13.21 | 35.71 | 10.67 | 37.24 | 9x12 | 2.79 | 58.06 | 1.91 | 61.87 | 429 | 4476 | 6.5 |
| 350 | 37 | 15.65 | 38.15 | 10.67 | 39.67 | 11x12 | 2.79 | 60.50 | 1.91 | 64.31 | 496 | 4926 | 6.5 |
| 500 | 37 | 18.69 | 41.20 | 10.67 | 42.72 | 13x12 | 2.79 | 63.55 | 1.91 | 67.36 | 591 | 5533 | 7 |
| 750 | 61 | 23.06 | 45.82 | 10.67 | 47.35 | 17x12 | 2.79 | 68.17 | 1.91 | 71.98 | 713 | 6476 | 7.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1/0 | 393.70 | 2817 | 0.5479 | 0.75 | 0.0186 | 0.2133 | 0.520+j0.207 | 0.232+j0.069 | 2770 | 221 | 219 |
| 2/0 | 401.32 | 3551 | 0.4364 | 0.60 | 0.0177 | 0.2067 | 0.421+j0.136 | 0.186+j0.066 | 3879 | 253 | 246 |
| 3/0 | 408.94 | 4477 | 0.3445 | 0.47 | 0.0165 | 0.2001 | 0.383+j0.135 | 0.147+j0.064 | 3879 | 288 | 275 |
| 4/0 | 419.10 | 5647 | 0.2756 | 0.38 | 0.0155 | 0.1903 | 0.354+j0.133 | 0.118+j0.062 | 3879 | 327 | 305 |
| 250 | 434.34 | 6675 | 0.2297 | 0.31 | 0.0143 | 0.1870 | 0.295+j0.096 | 0.100+j0.060 | 4987 | 367 | 343 |
| 350 | 449.58 | 9345 | 0.1673 | 0.23 | 0.0131 | 0.1772 | 0.239+j0.074 | 0.075+j0.057 | 6095 | 443 | 399 |
| 500 | 472.44 | 13350 | 0.1181 | 0.16 | 0.0116 | 0.1673 | 0.196+j0.059 | 0.056+j0.054 | 7203 | 529 | 451 |
| 750 | 502.92 | 20025 | 0.0755 | 0.11 | 0.0101 | 0.1575 | 0.148+j0.043 | 0.040+j0.050 | 9420 | 633 | 505 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Revision: 1.000.000
Updated On: Dec. 31, 2024, 11:07 p.m. UTC

