SPEC 26606
HVTECK CU 1/C 420NLEPR CB PVC AIA PVC 35kV 133% CSA
Single Conductor, 420 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:420 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
- Neutral Separator:Mylar tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 35kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 420 NLEPR AIA 35kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Inner Jacket | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 1/0 | 19 | 0.362 | 1.24 | 420 | 1.3 | 7x12 | 110 | 1.81 | 2.12 | 60 | 2.24 | 562 | 2704 | 6 |
| 2/0 | 19 | 0.405 | 1.283 | 420 | 1.343 | 7x12 | 110 | 1.853 | 2.163 | 60 | 2.283 | 650 | 2862 | 6 |
| 3/0 | 19 | 0.456 | 1.334 | 420 | 1.394 | 9x12 | 110 | 1.904 | 2.214 | 60 | 2.334 | 796 | 3092 | 6 |
| 4/0 | 19 | 0.512 | 1.39 | 420 | 1.45 | 9x12 | 110 | 1.96 | 2.27 | 75 | 2.42 | 935 | 3387 | 6.5 |
| 250 | 37 | 0.558 | 1.444 | 420 | 1.504 | 11x12 | 110 | 2.014 | 2.324 | 75 | 2.474 | 1101 | 3648 | 6.5 |
| 350 | 37 | 0.661 | 1.547 | 420 | 1.607 | 13x12 | 110 | 2.117 | 2.427 | 75 | 2.577 | 1471 | 4191 | 7 |
| 500 | 37 | 0.789 | 1.675 | 420 | 1.735 | 17x12 | 110 | 2.245 | 2.555 | 75 | 2.705 | 2013 | 4948 | 7 |
| 750 | 61 | 0.968 | 1.864 | 420 | 1.924 | 21x12 | 110 | 2.434 | 2.744 | 75 | 2.894 | 2885 | 6146 | 7.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1/0 | 15.7 | 844 | 0.102 | 0.139 | 0.059 | 0.064 | 0.378+j0.139 | 0.143+j0.069 | 3879 | 278 | 272 |
| 2/0 | 16 | 1064 | 0.082 | 0.112 | 0.055 | 0.061 | 0.351+j0.137 | 0.115+j0.067 | 3879 | 316 | 303 |
| 3/0 | 16.3 | 1342 | 0.064 | 0.087 | 0.052 | 0.059 | 0.286+j0.100 | 0.091+j0.064 | 4987 | 356 | 333 |
| 4/0 | 16.9 | 1692 | 0.051 | 0.07 | 0.048 | 0.057 | 0.269+j0.098 | 0.074+j0.062 | 4987 | 403 | 367 |
| 250 | 17.3 | 2000 | 0.043 | 0.059 | 0.045 | 0.056 | 0.228+j0.077 | 0.064+j0.060 | 6095 | 455 | 411 |
| 350 | 18 | 2800 | 0.031 | 0.043 | 0.041 | 0.053 | 0.189+j0.062 | 0.049+j0.057 | 7203 | 537 | 459 |
| 500 | 18.9 | 4000 | 0.021 | 0.03 | 0.036 | 0.05 | 0.145+j0.046 | 0.037+j0.054 | 9420 | 616 | 499 |
| 750 | 20.3 | 6000 | 0.014 | 0.021 | 0.031 | 0.047 | 0.115+j0.037 | 0.029+j0.050 | 11636 | 716 | 557 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Inner Jacket | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | mm | kg/km | kg/km | inch |
| 1/0 | 19 | 9.19 | 31.50 | 10.67 | 33.02 | 7x12 | 2.79 | 45.97 | 53.85 | 1.52 | 56.90 | 836 | 4024 | 6 |
| 2/0 | 19 | 10.29 | 32.59 | 10.67 | 34.11 | 7x12 | 2.79 | 47.07 | 54.94 | 1.52 | 57.99 | 967 | 4259 | 6 |
| 3/0 | 19 | 11.58 | 33.88 | 10.67 | 35.41 | 9x12 | 2.79 | 48.36 | 56.24 | 1.52 | 59.28 | 1185 | 4601 | 6 |
| 4/0 | 19 | 13.00 | 35.31 | 10.67 | 36.83 | 9x12 | 2.79 | 49.78 | 57.66 | 1.91 | 61.47 | 1391 | 5040 | 6.5 |
| 250 | 37 | 14.17 | 36.68 | 10.67 | 38.20 | 11x12 | 2.79 | 51.16 | 59.03 | 1.91 | 62.84 | 1638 | 5429 | 6.5 |
| 350 | 37 | 16.79 | 39.29 | 10.67 | 40.82 | 13x12 | 2.79 | 53.77 | 61.65 | 1.91 | 65.46 | 2189 | 6237 | 7 |
| 500 | 37 | 20.04 | 42.55 | 10.67 | 44.07 | 17x12 | 2.79 | 57.02 | 64.90 | 1.91 | 68.71 | 2996 | 7363 | 7 |
| 750 | 61 | 24.59 | 47.35 | 10.67 | 48.87 | 21x12 | 2.79 | 61.82 | 69.70 | 1.91 | 73.51 | 4293 | 9146 | 7.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1/0 | 398.78 | 3756 | 0.3346 | 0.46 | 0.0180 | 0.2100 | 0.378+j0.139 | 0.143+j0.069 | 3879 | 278 | 272 |
| 2/0 | 406.40 | 4735 | 0.2690 | 0.37 | 0.0168 | 0.2001 | 0.351+j0.137 | 0.115+j0.067 | 3879 | 316 | 303 |
| 3/0 | 414.02 | 5972 | 0.2100 | 0.29 | 0.0158 | 0.1936 | 0.286+j0.100 | 0.091+j0.064 | 4987 | 356 | 333 |
| 4/0 | 429.26 | 7529 | 0.1673 | 0.23 | 0.0146 | 0.1870 | 0.269+j0.098 | 0.074+j0.062 | 4987 | 403 | 367 |
| 250 | 439.42 | 8900 | 0.1411 | 0.19 | 0.0137 | 0.1837 | 0.228+j0.077 | 0.064+j0.060 | 6095 | 455 | 411 |
| 350 | 457.20 | 12460 | 0.1017 | 0.14 | 0.0125 | 0.1739 | 0.189+j0.062 | 0.049+j0.057 | 7203 | 537 | 459 |
| 500 | 480.06 | 17800 | 0.0689 | 0.10 | 0.0110 | 0.1640 | 0.145+j0.046 | 0.037+j0.054 | 9420 | 616 | 499 |
| 750 | 515.62 | 26700 | 0.0459 | 0.07 | 0.0094 | 0.1542 | 0.115+j0.037 | 0.029+j0.050 | 11636 | 716 | 557 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Revision: 1.000.000
Updated On: Dec. 31, 2024, 11:07 p.m. UTC