SPEC 26452
HVTECK CU 3/C 320TRXLPE TS PVC AIA PVC 25kV 133% CSA
3 Conductor, 320 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:320 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Filler:Non-wicking, non-hygroscopic and flame retardant polypropylene filler
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 320 TRXLPE AIA 25kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch | |
| TBA | 1 | 19 | 0.322 | 1 | 320 | 1.06 | 1x6 | 110 | 2.846 | 75 | 2.996 | 1128 | 3477 | 4 |
| TBA | 1/0 | 19 | 0.362 | 1.04 | 320 | 1.1 | 1x6 | 110 | 2.932 | 75 | 3.082 | 1344 | 3806 | 4 |
| 139407 | 2/0 | 19 | 0.405 | 1.084 | 320 | 1.144 | 1x6 | 110 | 3.135 | 85 | 3.305 | 1623 | 5051 | 4.5 |
| TBA | 3/0 | 19 | 0.456 | 1.134 | 320 | 1.194 | 1x4 | 125 | 3.165 | 85 | 3.335 | 1997 | 4793 | 4.5 |
| 678745 | 4/0 | 19 | 0.512 | 1.19 | 320 | 1.25 | 1x4 | 125 | 3.364 | 85 | 3.534 | 2430 | 6162 | 4.5 |
| TBA | 250 | 37 | 0.558 | 1.244 | 320 | 1.304 | 1x4 | 125 | 3.403 | 85 | 3.573 | 2794 | 5920 | 4.5 |
| 138182 | 350 | 37 | 0.661 | 1.327 | 320 | 1.387 | 1x3 | 125 | 3.66 | 85 | 3.83 | 3791 | 7915 | 5 |
| 137995! | 350 | 37 | 0.661 | 1.327 | 320 | 1.387 | 1x3 | 125 | 3.66 | 85 | 3.83 | 3791 | 7927 | 5 |
| 678737 | 500 | 37 | 0.789 | 1.475 | 320 | 1.535 | 1x3 | 125 | 3.979 | 85 | 4.149 | 5230 | 9786 | 5.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
! Gray Jacket Color
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1 | 21 | 2008 | 0.128 | 0.175 | 0.07 | 0.033 | 0.541+j0.380 | 0.175+j0.050 | 3315 | 202 | 226 |
| 1/0 | 21.6 | 2534 | 0.102 | 0.139 | 0.065 | 0.032 | 0.503+j0.365 | 0.139+j0.048 | 3439 | 231 | 256 |
| 2/0 | 23.1 | 3194 | 0.082 | 0.112 | 0.061 | 0.03 | 0.473+j0.350 | 0.112+j0.046 | 3576 | 265 | 290 |
| 3/0 | 23.3 | 4027 | 0.064 | 0.087 | 0.057 | 0.028 | 0.445+j0.335 | 0.087+j0.044 | 3730 | 303 | 327 |
| 4/0 | 24.7 | 5078 | 0.051 | 0.07 | 0.053 | 0.026 | 0.424+j0.318 | 0.070+j0.043 | 3904 | 348 | 369 |
| 250 | 25 | 6000 | 0.043 | 0.059 | 0.049 | 0.025 | 0.409+j0.303 | 0.059+j0.042 | 4071 | 384 | 408 |
| 350 | 26.8 | 8400 | 0.031 | 0.043 | 0.043 | 0.023 | 0.386+j0.282 | 0.043+j0.039 | 4328 | 468 | 485 |
| 350 | 26.8 | 8400 | 0.031 | 0.043 | 0.043 | 0.023 | 0.386+j0.282 | 0.043+j0.039 | 4328 | 468 | 485 |
| 500 | 29 | 12000 | 0.021 | 0.03 | 0.039 | 0.021 | 0.361+j0.250 | 0.030+j0.037 | 4787 | 565 | 571 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
Table 3 – Weights and Measurements (Metric)
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km | kg/km | inch | |
| TBA | 1 | 19 | 8.18 | 25.40 | 8.13 | 26.92 | 1x6 | 2.79 | 72.29 | 1.91 | 76.10 | 1679 | 5174 | 4 |
| TBA | 1/0 | 19 | 9.19 | 26.42 | 8.13 | 27.94 | 1x6 | 2.79 | 74.47 | 1.91 | 78.28 | 2000 | 5664 | 4 |
| 139407 | 2/0 | 19 | 10.29 | 27.53 | 8.13 | 29.06 | 1x6 | 2.79 | 79.63 | 2.16 | 83.95 | 2415 | 7517 | 4.5 |
| TBA | 3/0 | 19 | 11.58 | 28.80 | 8.13 | 30.33 | 1x4 | 3.18 | 80.39 | 2.16 | 84.71 | 2972 | 7133 | 4.5 |
| 678745 | 4/0 | 19 | 13.00 | 30.23 | 8.13 | 31.75 | 1x4 | 3.18 | 85.45 | 2.16 | 89.76 | 3616 | 9170 | 4.5 |
| TBA | 250 | 37 | 14.17 | 31.60 | 8.13 | 33.12 | 1x4 | 3.18 | 86.44 | 2.16 | 90.75 | 4158 | 8810 | 4.5 |
| 138182 | 350 | 37 | 16.79 | 33.71 | 8.13 | 35.23 | 1x3 | 3.18 | 92.96 | 2.16 | 97.28 | 5642 | 11779 | 5 |
| 137995! | 350 | 37 | 16.79 | 33.71 | 8.13 | 35.23 | 1x3 | 3.18 | 92.96 | 2.16 | 97.28 | 5642 | 11797 | 5 |
| 678737 | 500 | 37 | 20.04 | 37.47 | 8.13 | 38.99 | 1x3 | 3.18 | 101.07 | 2.16 | 105.38 | 7783 | 14563 | 5.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
! Gray Jacket Color
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1 | 533.40 | 8936 | 0.4199 | 0.57 | 0.0213 | 0.1083 | 0.541+j0.380 | 0.175+j0.050 | 3315 | 202 | 226 |
| 1/0 | 548.64 | 11276 | 0.3346 | 0.46 | 0.0198 | 0.1050 | 0.503+j0.365 | 0.139+j0.048 | 3439 | 231 | 256 |
| 2/0 | 586.74 | 14213 | 0.2690 | 0.37 | 0.0186 | 0.0984 | 0.473+j0.350 | 0.112+j0.046 | 3576 | 265 | 290 |
| 3/0 | 591.82 | 17920 | 0.2100 | 0.29 | 0.0174 | 0.0919 | 0.445+j0.335 | 0.087+j0.044 | 3730 | 303 | 327 |
| 4/0 | 627.38 | 22597 | 0.1673 | 0.23 | 0.0162 | 0.0853 | 0.424+j0.318 | 0.070+j0.043 | 3904 | 348 | 369 |
| 250 | 635.00 | 26700 | 0.1411 | 0.19 | 0.0149 | 0.0820 | 0.409+j0.303 | 0.059+j0.042 | 4071 | 384 | 408 |
| 350 | 680.72 | 37380 | 0.1017 | 0.14 | 0.0131 | 0.0755 | 0.386+j0.282 | 0.043+j0.039 | 4328 | 468 | 485 |
| 350 | 680.72 | 37380 | 0.1017 | 0.14 | 0.0131 | 0.0755 | 0.386+j0.282 | 0.043+j0.039 | 4328 | 468 | 485 |
| 500 | 736.60 | 53400 | 0.0689 | 0.10 | 0.0119 | 0.0689 | 0.361+j0.250 | 0.030+j0.037 | 4787 | 565 | 571 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
Revision: 1.000.007
Updated On: Dec. 31, 2024, 11:07 p.m. UTC