SPEC 26441
HVTECK CU 3/C 260NLEPR TS PVC AIA PVC 25kV 100% CSA
3 Conductor, 260 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:260 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Filler:Interstices filled with non-hydroscoping/non-wicking fillers
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 260 NLEPR AIA 25kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch | |
| TBA | 1 | 19 | 0.322 | 0.88 | 260 | 0.94 | 1x6 | 110 | 2.586 | 75 | 2.736 | 1098 | 3014 | 3.5 |
| TBA | 1/0 | 19 | 0.362 | 0.92 | 260 | 0.98 | 1x6 | 110 | 2.673 | 75 | 2.823 | 1314 | 3329 | 3.5 |
| TBA | 2/0 | 19 | 0.405 | 0.963 | 260 | 1.023 | 1x6 | 110 | 2.766 | 75 | 2.916 | 1582 | 3704 | 4 |
| TBA | 3/0 | 19 | 0.456 | 1.014 | 260 | 1.074 | 1x4 | 110 | 2.876 | 75 | 3.026 | 1967 | 4215 | 4 |
| TBA | 4/0 | 19 | 0.512 | 1.07 | 260 | 1.13 | 1x4 | 110 | 2.997 | 75 | 3.147 | 2390 | 4777 | 4 |
| TBA | 250 | 37 | 0.558 | 1.124 | 260 | 1.184 | 1x4 | 125 | 3.143 | 85 | 3.313 | 2764 | 5366 | 4.5 |
| 647159 | 350 | 37 | 0.661 | 1.207 | 260 | 1.267 | 1x3 | 125 | 3.4 | 85 | 3.57 | 3763 | 7629 | 4.5 |
| 456806* | 500 | 37 | 0.789 | 1.332 | 260 | 1.392 | 1x3 | 125 | 3.67 | 85 | 3.84 | 5196 | 9460 | 5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Red jacket
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1 | 19.2 | 2008 | 0.128 | 0.175 | 0.047 | 0.031 | 0.545+j0.418 | 0.175+j0.047 | 2943 | 202 | 226 |
| 1/0 | 19.8 | 2534 | 0.102 | 0.139 | 0.043 | 0.029 | 0.508+j0.402 | 0.139+j0.045 | 3067 | 231 | 256 |
| 2/0 | 20.4 | 3194 | 0.082 | 0.112 | 0.041 | 0.027 | 0.480+j0.386 | 0.112+j0.044 | 3201 | 265 | 290 |
| 3/0 | 21.2 | 4027 | 0.064 | 0.087 | 0.038 | 0.026 | 0.452+j0.367 | 0.087+j0.042 | 3359 | 303 | 327 |
| 4/0 | 22 | 5078 | 0.051 | 0.07 | 0.035 | 0.024 | 0.432+j0.349 | 0.070+j0.041 | 3532 | 348 | 369 |
| 250 | 23.2 | 6000 | 0.043 | 0.059 | 0.032 | 0.023 | 0.418+j0.332 | 0.059+j0.039 | 3699 | 384 | 408 |
| 350 | 25 | 8400 | 0.031 | 0.043 | 0.028 | 0.021 | 0.396+j0.308 | 0.043+j0.037 | 3957 | 468 | 485 |
| 500 | 26.9 | 12000 | 0.021 | 0.03 | 0.024 | 0.019 | 0.373+j0.277 | 0.030+j0.035 | 4344 | 565 | 571 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
Table 3 – Weights and Measurements (Metric)
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km | kg/km | inch | |
| TBA | 1 | 19 | 8.18 | 22.35 | 6.60 | 23.88 | 1x6 | 2.79 | 65.68 | 1.91 | 69.49 | 1634 | 4485 | 3.5 |
| TBA | 1/0 | 19 | 9.19 | 23.37 | 6.60 | 24.89 | 1x6 | 2.79 | 67.89 | 1.91 | 71.70 | 1955 | 4954 | 3.5 |
| TBA | 2/0 | 19 | 10.29 | 24.46 | 6.60 | 25.98 | 1x6 | 2.79 | 70.26 | 1.91 | 74.07 | 2354 | 5512 | 4 |
| TBA | 3/0 | 19 | 11.58 | 25.76 | 6.60 | 27.28 | 1x4 | 2.79 | 73.05 | 1.91 | 76.86 | 2927 | 6273 | 4 |
| TBA | 4/0 | 19 | 13.00 | 27.18 | 6.60 | 28.70 | 1x4 | 2.79 | 76.12 | 1.91 | 79.93 | 3557 | 7109 | 4 |
| TBA | 250 | 37 | 14.17 | 28.55 | 6.60 | 30.07 | 1x4 | 3.18 | 79.83 | 2.16 | 84.15 | 4113 | 7985 | 4.5 |
| 647159 | 350 | 37 | 16.79 | 30.66 | 6.60 | 32.18 | 1x3 | 3.18 | 86.36 | 2.16 | 90.68 | 5600 | 11353 | 4.5 |
| 456806* | 500 | 37 | 20.04 | 33.83 | 6.60 | 35.36 | 1x3 | 3.18 | 93.22 | 2.16 | 97.54 | 7732 | 14078 | 5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Red jacket
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1 | 487.68 | 8936 | 0.4199 | 0.57 | 0.0143 | 0.1017 | 0.545+j0.418 | 0.175+j0.047 | 2943 | 202 | 226 |
| 1/0 | 502.92 | 11276 | 0.3346 | 0.46 | 0.0131 | 0.0951 | 0.508+j0.402 | 0.139+j0.045 | 3067 | 231 | 256 |
| 2/0 | 518.16 | 14213 | 0.2690 | 0.37 | 0.0125 | 0.0886 | 0.480+j0.386 | 0.112+j0.044 | 3201 | 265 | 290 |
| 3/0 | 538.48 | 17920 | 0.2100 | 0.29 | 0.0116 | 0.0853 | 0.452+j0.367 | 0.087+j0.042 | 3359 | 303 | 327 |
| 4/0 | 558.80 | 22597 | 0.1673 | 0.23 | 0.0107 | 0.0787 | 0.432+j0.349 | 0.070+j0.041 | 3532 | 348 | 369 |
| 250 | 589.28 | 26700 | 0.1411 | 0.19 | 0.0098 | 0.0755 | 0.418+j0.332 | 0.059+j0.039 | 3699 | 384 | 408 |
| 350 | 635.00 | 37380 | 0.1017 | 0.14 | 0.0085 | 0.0689 | 0.396+j0.308 | 0.043+j0.037 | 3957 | 468 | 485 |
| 500 | 683.26 | 53400 | 0.0689 | 0.10 | 0.0073 | 0.0623 | 0.373+j0.277 | 0.030+j0.035 | 4344 | 565 | 571 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
Revision: 1.000.001
Updated On: May 13, 2025, 2:23 p.m. UTC

