SPEC 26435
HVTECK AL 1/C 260TRXLPE CB PVC AIA PVC 25kV 100% CSA
Single Conductor, 260 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:260 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
- Neutral Separator:Mylar tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 260 TRXLPE AIA 25kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 1 | 19 | 0.299 | 0.857 | 260 | 0.917 | 5x12 | 80 | 1.677 | 60 | 1.797 | 157 | 1611 | 4.5 |
| 1/0 | 19 | 0.336 | 0.894 | 260 | 0.954 | 5x12 | 80 | 1.714 | 60 | 1.834 | 160 | 1682 | 5 |
| 2/0 | 19 | 0.376 | 0.934 | 260 | 0.994 | 7x12 | 80 | 1.754 | 60 | 1.874 | 211 | 1813 | 5 |
| 3/0 | 19 | 0.423 | 0.981 | 260 | 1.041 | 7x12 | 80 | 1.801 | 60 | 1.921 | 215 | 1911 | 5 |
| 4/0 | 19 | 0.475 | 1.033 | 260 | 1.093 | 7x12 | 80 | 1.853 | 60 | 1.973 | 219 | 2024 | 5 |
| 250 | 37 | 0.52 | 1.086 | 260 | 1.146 | 9x12 | 80 | 1.906 | 60 | 2.026 | 261 | 2177 | 5.5 |
| 350 | 37 | 0.616 | 1.182 | 260 | 1.242 | 11x12 | 110 | 2.062 | 60 | 2.182 | 307 | 2559 | 5.5 |
| 500 | 37 | 0.736 | 1.302 | 260 | 1.362 | 13x12 | 110 | 2.182 | 60 | 2.302 | 371 | 2930 | 6 |
| 750 | 61 | 0.908 | 1.484 | 260 | 1.544 | 17x12 | 110 | 2.364 | 75 | 2.514 | 453 | 3574 | 6.5 |
| 1000 | 61 | 1.117 | 1.693 | 260 | 1.753 | 17x12 | 110 | 2.573 | 75 | 2.723 | 470 | 4121 | 7 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1 | 12.6 | 502 | 0.211 | 0.289 | 0.064 | 0.063 | 0.584+j0.201 | 0.292+j0.067 | 2770 | 193 | 194 |
| 1/0 | 12.8 | 633 | 0.167 | 0.229 | 0.059 | 0.061 | 0.524+j0.199 | 0.232+j0.064 | 2770 | 221 | 219 |
| 2/0 | 13.1 | 798 | 0.133 | 0.182 | 0.055 | 0.059 | 0.424+j0.129 | 0.186+j0.062 | 3879 | 253 | 246 |
| 3/0 | 13.4 | 1006 | 0.105 | 0.144 | 0.051 | 0.056 | 0.385+j0.127 | 0.148+j0.060 | 3879 | 288 | 275 |
| 4/0 | 13.8 | 1269 | 0.084 | 0.115 | 0.048 | 0.054 | 0.356+j0.126 | 0.119+j0.058 | 3879 | 327 | 305 |
| 250 | 14.2 | 1500 | 0.07 | 0.096 | 0.044 | 0.053 | 0.296+j0.090 | 0.101+j0.056 | 4987 | 367 | 343 |
| 350 | 15.3 | 2100 | 0.051 | 0.07 | 0.039 | 0.051 | 0.240+j0.068 | 0.076+j0.054 | 6095 | 443 | 399 |
| 500 | 16.1 | 3000 | 0.036 | 0.05 | 0.035 | 0.048 | 0.197+j0.054 | 0.056+j0.050 | 7203 | 529 | 451 |
| 750 | 17.6 | 4500 | 0.023 | 0.033 | 0.029 | 0.045 | 0.148+j0.038 | 0.041+j0.047 | 9420 | 633 | 505 |
| 1000 | 19.1 | 6000 | 0.017 | 0.025 | 0.025 | 0.042 | 0.140+j0.038 | 0.032+j0.046 | 9420 | 711 | 544 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km | kg/km | inch |
| 1 | 19 | 7.59 | 21.77 | 6.60 | 23.29 | 5x12 | 2.03 | 42.60 | 1.52 | 45.64 | 234 | 2397 | 4.5 |
| 1/0 | 19 | 8.53 | 22.71 | 6.60 | 24.23 | 5x12 | 2.03 | 43.54 | 1.52 | 46.58 | 238 | 2503 | 5 |
| 2/0 | 19 | 9.55 | 23.72 | 6.60 | 25.25 | 7x12 | 2.03 | 44.55 | 1.52 | 47.60 | 314 | 2698 | 5 |
| 3/0 | 19 | 10.74 | 24.92 | 6.60 | 26.44 | 7x12 | 2.03 | 45.75 | 1.52 | 48.79 | 320 | 2844 | 5 |
| 4/0 | 19 | 12.07 | 26.24 | 6.60 | 27.76 | 7x12 | 2.03 | 47.07 | 1.52 | 50.11 | 326 | 3012 | 5 |
| 250 | 37 | 13.21 | 27.58 | 6.60 | 29.11 | 9x12 | 2.03 | 48.41 | 1.52 | 51.46 | 388 | 3240 | 5.5 |
| 350 | 37 | 15.65 | 30.02 | 6.60 | 31.55 | 11x12 | 2.79 | 52.37 | 1.52 | 55.42 | 457 | 3808 | 5.5 |
| 500 | 37 | 18.69 | 33.07 | 6.60 | 34.59 | 13x12 | 2.79 | 55.42 | 1.52 | 58.47 | 552 | 4360 | 6 |
| 750 | 61 | 23.06 | 37.69 | 6.60 | 39.22 | 17x12 | 2.79 | 60.05 | 1.91 | 63.86 | 674 | 5319 | 6.5 |
| 1000 | 61 | 28.37 | 43.00 | 6.60 | 44.53 | 17x12 | 2.79 | 65.35 | 1.91 | 69.16 | 699 | 6133 | 7 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1 | 320.04 | 2234 | 0.6923 | 0.95 | 0.0195 | 0.2067 | 0.584+j0.201 | 0.292+j0.067 | 2770 | 193 | 194 |
| 1/0 | 325.12 | 2817 | 0.5479 | 0.75 | 0.0180 | 0.2001 | 0.524+j0.199 | 0.232+j0.064 | 2770 | 221 | 219 |
| 2/0 | 332.74 | 3551 | 0.4364 | 0.60 | 0.0168 | 0.1936 | 0.424+j0.129 | 0.186+j0.062 | 3879 | 253 | 246 |
| 3/0 | 340.36 | 4477 | 0.3445 | 0.47 | 0.0155 | 0.1837 | 0.385+j0.127 | 0.148+j0.060 | 3879 | 288 | 275 |
| 4/0 | 350.52 | 5647 | 0.2756 | 0.38 | 0.0146 | 0.1772 | 0.356+j0.126 | 0.119+j0.058 | 3879 | 327 | 305 |
| 250 | 360.68 | 6675 | 0.2297 | 0.31 | 0.0134 | 0.1739 | 0.296+j0.090 | 0.101+j0.056 | 4987 | 367 | 343 |
| 350 | 388.62 | 9345 | 0.1673 | 0.23 | 0.0119 | 0.1673 | 0.240+j0.068 | 0.076+j0.054 | 6095 | 443 | 399 |
| 500 | 408.94 | 13350 | 0.1181 | 0.16 | 0.0107 | 0.1575 | 0.197+j0.054 | 0.056+j0.050 | 7203 | 529 | 451 |
| 750 | 447.04 | 20025 | 0.0755 | 0.11 | 0.0088 | 0.1476 | 0.148+j0.038 | 0.041+j0.047 | 9420 | 633 | 505 |
| 1000 | 485.14 | 26700 | 0.0558 | 0.08 | 0.0076 | 0.1378 | 0.140+j0.038 | 0.032+j0.046 | 9420 | 711 | 544 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A