SPEC 26406

HVTECK CU 1/C 320NLEPR CB PVC AIA PVC 25kV 133% CSA

Single Conductor, 320 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:320 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 320 NLEPR AIA 25kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ftlb/1000ftinch
    1190.32213201.067x12801.82601.9447420765
    1/0190.3621.043201.17x12801.86601.9854622055
    2/0190.4051.0833201.1437x12801.903602.02363423545.5
    3/0190.4561.1343201.1949x12801.954602.07477925715.5
    4/0190.5121.193201.259x121102.07602.1991929055.5
    250370.5581.2443201.30411x121102.124602.244108431546
    350370.6611.3473201.40713x121102.227602.347145536776
    500370.7891.4753201.53517x121102.355752.505199644736.5
    750610.9681.6643201.72421x121102.544752.694286956387
    1000611.1171.8133201.87321x121102.693752.843365366487.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    113.66690.1280.1750.0530.0630.416+j0.1360.179+j0.0683879245244
    1/013.98440.1020.1390.050.0610.380+j0.1340.143+j0.0663879278272
    2/014.210640.0820.1120.0470.0590.353+j0.1330.116+j0.0643879316303
    3/014.513420.0640.0870.0430.0570.287+j0.0960.092+j0.0614987356333
    4/015.316920.0510.070.040.0550.270+j0.0940.075+j0.0604987403367
    25015.720000.0430.0590.0380.0540.228+j0.0730.064+j0.0586095455411
    35016.428000.0310.0430.0340.0510.190+j0.0590.049+j0.0557203537459
    50017.540000.0210.030.030.0480.145+j0.0430.038+j0.0529420616499
    75018.960000.0140.0210.0250.0450.115+j0.0340.030+j0.04811636716557
    100019.980000.0110.0180.0230.0430.112+j0.0330.026+j0.04611636825608
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/kmkg/kminch
    1198.1825.408.1326.927x122.0346.231.5249.2870530895
    1/0199.1926.428.1327.947x122.0347.241.5250.2981332815
    2/01910.2927.518.1329.037x122.0348.341.5251.3894335035.5
    3/01911.5828.808.1330.339x122.0349.631.5252.68115938265.5
    4/01913.0030.238.1331.759x122.7952.581.5255.63136843235.5
    2503714.1731.608.1333.1211x122.7953.951.5257.00161346946
    3503716.7934.218.1335.7413x122.7956.571.5259.61216554726
    5003720.0437.478.1338.9917x122.7959.821.9163.63297066576.5
    7506124.5942.278.1343.7921x122.7964.621.9168.43427083907
    10006128.3746.058.1347.5721x122.7968.401.9172.21543698937.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1345.4429770.41990.570.01620.20670.416+j0.1360.179+j0.0683879245244
    1/0353.0637560.33460.460.01520.20010.380+j0.1340.143+j0.0663879278272
    2/0360.6847350.26900.370.01430.19360.353+j0.1330.116+j0.0643879316303
    3/0368.3059720.21000.290.01310.18700.287+j0.0960.092+j0.0614987356333
    4/0388.6275290.16730.230.01220.18040.270+j0.0940.075+j0.0604987403367
    250398.7889000.14110.190.01160.17720.228+j0.0730.064+j0.0586095455411
    350416.56124600.10170.140.01040.16730.190+j0.0590.049+j0.0557203537459
    500444.50178000.06890.100.00910.15750.145+j0.0430.038+j0.0529420616499
    750480.06267000.04590.070.00760.14760.115+j0.0340.030+j0.04811636716557
    1000505.46356000.03610.060.00700.14110.112+j0.0330.026+j0.04611636825608
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A