SPEC 26406
HVTECK CU 1/C 320NLEPR CB PVC AIA PVC 25kV 133% CSA
Single Conductor, 320 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:320 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
- Neutral Separator:Mylar tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 320 NLEPR AIA 25kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 1 | 19 | 0.322 | 1 | 320 | 1.06 | 7x12 | 80 | 1.82 | 60 | 1.94 | 474 | 2076 | 5 |
| 1/0 | 19 | 0.362 | 1.04 | 320 | 1.1 | 7x12 | 80 | 1.86 | 60 | 1.98 | 546 | 2205 | 5 |
| 2/0 | 19 | 0.405 | 1.083 | 320 | 1.143 | 7x12 | 80 | 1.903 | 60 | 2.023 | 634 | 2354 | 5.5 |
| 3/0 | 19 | 0.456 | 1.134 | 320 | 1.194 | 9x12 | 80 | 1.954 | 60 | 2.074 | 779 | 2571 | 5.5 |
| 4/0 | 19 | 0.512 | 1.19 | 320 | 1.25 | 9x12 | 110 | 2.07 | 60 | 2.19 | 919 | 2905 | 5.5 |
| 250 | 37 | 0.558 | 1.244 | 320 | 1.304 | 11x12 | 110 | 2.124 | 60 | 2.244 | 1084 | 3154 | 6 |
| 350 | 37 | 0.661 | 1.347 | 320 | 1.407 | 13x12 | 110 | 2.227 | 60 | 2.347 | 1455 | 3677 | 6 |
| 500 | 37 | 0.789 | 1.475 | 320 | 1.535 | 17x12 | 110 | 2.355 | 75 | 2.505 | 1996 | 4473 | 6.5 |
| 750 | 61 | 0.968 | 1.664 | 320 | 1.724 | 21x12 | 110 | 2.544 | 75 | 2.694 | 2869 | 5638 | 7 |
| 1000 | 61 | 1.117 | 1.813 | 320 | 1.873 | 21x12 | 110 | 2.693 | 75 | 2.843 | 3653 | 6648 | 7.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1 | 13.6 | 669 | 0.128 | 0.175 | 0.053 | 0.063 | 0.416+j0.136 | 0.179+j0.068 | 3879 | 245 | 244 |
| 1/0 | 13.9 | 844 | 0.102 | 0.139 | 0.05 | 0.061 | 0.380+j0.134 | 0.143+j0.066 | 3879 | 278 | 272 |
| 2/0 | 14.2 | 1064 | 0.082 | 0.112 | 0.047 | 0.059 | 0.353+j0.133 | 0.116+j0.064 | 3879 | 316 | 303 |
| 3/0 | 14.5 | 1342 | 0.064 | 0.087 | 0.043 | 0.057 | 0.287+j0.096 | 0.092+j0.061 | 4987 | 356 | 333 |
| 4/0 | 15.3 | 1692 | 0.051 | 0.07 | 0.04 | 0.055 | 0.270+j0.094 | 0.075+j0.060 | 4987 | 403 | 367 |
| 250 | 15.7 | 2000 | 0.043 | 0.059 | 0.038 | 0.054 | 0.228+j0.073 | 0.064+j0.058 | 6095 | 455 | 411 |
| 350 | 16.4 | 2800 | 0.031 | 0.043 | 0.034 | 0.051 | 0.190+j0.059 | 0.049+j0.055 | 7203 | 537 | 459 |
| 500 | 17.5 | 4000 | 0.021 | 0.03 | 0.03 | 0.048 | 0.145+j0.043 | 0.038+j0.052 | 9420 | 616 | 499 |
| 750 | 18.9 | 6000 | 0.014 | 0.021 | 0.025 | 0.045 | 0.115+j0.034 | 0.030+j0.048 | 11636 | 716 | 557 |
| 1000 | 19.9 | 8000 | 0.011 | 0.018 | 0.023 | 0.043 | 0.112+j0.033 | 0.026+j0.046 | 11636 | 825 | 608 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km | kg/km | inch |
| 1 | 19 | 8.18 | 25.40 | 8.13 | 26.92 | 7x12 | 2.03 | 46.23 | 1.52 | 49.28 | 705 | 3089 | 5 |
| 1/0 | 19 | 9.19 | 26.42 | 8.13 | 27.94 | 7x12 | 2.03 | 47.24 | 1.52 | 50.29 | 813 | 3281 | 5 |
| 2/0 | 19 | 10.29 | 27.51 | 8.13 | 29.03 | 7x12 | 2.03 | 48.34 | 1.52 | 51.38 | 943 | 3503 | 5.5 |
| 3/0 | 19 | 11.58 | 28.80 | 8.13 | 30.33 | 9x12 | 2.03 | 49.63 | 1.52 | 52.68 | 1159 | 3826 | 5.5 |
| 4/0 | 19 | 13.00 | 30.23 | 8.13 | 31.75 | 9x12 | 2.79 | 52.58 | 1.52 | 55.63 | 1368 | 4323 | 5.5 |
| 250 | 37 | 14.17 | 31.60 | 8.13 | 33.12 | 11x12 | 2.79 | 53.95 | 1.52 | 57.00 | 1613 | 4694 | 6 |
| 350 | 37 | 16.79 | 34.21 | 8.13 | 35.74 | 13x12 | 2.79 | 56.57 | 1.52 | 59.61 | 2165 | 5472 | 6 |
| 500 | 37 | 20.04 | 37.47 | 8.13 | 38.99 | 17x12 | 2.79 | 59.82 | 1.91 | 63.63 | 2970 | 6657 | 6.5 |
| 750 | 61 | 24.59 | 42.27 | 8.13 | 43.79 | 21x12 | 2.79 | 64.62 | 1.91 | 68.43 | 4270 | 8390 | 7 |
| 1000 | 61 | 28.37 | 46.05 | 8.13 | 47.57 | 21x12 | 2.79 | 68.40 | 1.91 | 72.21 | 5436 | 9893 | 7.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 1 | 345.44 | 2977 | 0.4199 | 0.57 | 0.0162 | 0.2067 | 0.416+j0.136 | 0.179+j0.068 | 3879 | 245 | 244 |
| 1/0 | 353.06 | 3756 | 0.3346 | 0.46 | 0.0152 | 0.2001 | 0.380+j0.134 | 0.143+j0.066 | 3879 | 278 | 272 |
| 2/0 | 360.68 | 4735 | 0.2690 | 0.37 | 0.0143 | 0.1936 | 0.353+j0.133 | 0.116+j0.064 | 3879 | 316 | 303 |
| 3/0 | 368.30 | 5972 | 0.2100 | 0.29 | 0.0131 | 0.1870 | 0.287+j0.096 | 0.092+j0.061 | 4987 | 356 | 333 |
| 4/0 | 388.62 | 7529 | 0.1673 | 0.23 | 0.0122 | 0.1804 | 0.270+j0.094 | 0.075+j0.060 | 4987 | 403 | 367 |
| 250 | 398.78 | 8900 | 0.1411 | 0.19 | 0.0116 | 0.1772 | 0.228+j0.073 | 0.064+j0.058 | 6095 | 455 | 411 |
| 350 | 416.56 | 12460 | 0.1017 | 0.14 | 0.0104 | 0.1673 | 0.190+j0.059 | 0.049+j0.055 | 7203 | 537 | 459 |
| 500 | 444.50 | 17800 | 0.0689 | 0.10 | 0.0091 | 0.1575 | 0.145+j0.043 | 0.038+j0.052 | 9420 | 616 | 499 |
| 750 | 480.06 | 26700 | 0.0459 | 0.07 | 0.0076 | 0.1476 | 0.115+j0.034 | 0.030+j0.048 | 11636 | 716 | 557 |
| 1000 | 505.46 | 35600 | 0.0361 | 0.06 | 0.0070 | 0.1411 | 0.112+j0.033 | 0.026+j0.046 | 11636 | 825 | 608 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Revision: 1.000.000
Updated On: Dec. 31, 2024, 11:07 p.m. UTC