SPEC 26361

HVTECK AL 3/C 175NLEPR TS PVC AIA PVC 15kV 100% CSA

3 Conductor, 175 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:175 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 175 NLEPR AIA 15kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundGround SizeInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGAWGmilinchinchmilinchlb/1000ftlb/1000ftinch
    TBA270.2680.6561750.7161x881101.7932.103602.22323216343
    TBA1190.2990.6871750.7471x661101.862.17602.2927017793
    TBA1/0190.3360.7241750.7841x661101.9392.249602.36927919203
    TBA2/0190.3760.7641750.8241x661102.0262.336752.48628921513
    TBA3/0190.4230.8111750.8711x661102.1272.437752.58730123563.5
    578144^4/0180.4750.8631750.9231x441102.242.607602.72737032103.5
    578135^250350.520.9161750.9761x441102.3542.722602.84238235273.5
    TBA350370.6161.0121751.0721x441102.5622.872753.02239833834
    TBA500370.7361.1321751.1921x331252.8513.161853.33146641894.5
    578149^750580.9081.3261751.4061x1/01/01253.3133.701703.84168765105
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    215.611940.2660.3650.040.0290.731+j0.5080.365+j0.0452249135157
    11615060.2110.2890.0370.0270.657+j0.4910.289+j0.0422345154178
    1/016.619000.1670.2290.0340.0260.599+j0.4730.229+j0.0402460176202
    2/017.423950.1330.1820.0320.0240.553+j0.4550.182+j0.0392584204229
    3/018.130200.1050.1440.0290.0230.515+j0.4350.144+j0.0372730234260
    4/019.138080.0840.1150.0270.0210.485+j0.4130.115+j0.0362891268294
    25019.945000.070.0960.0250.020.465+j0.3930.096+j0.0353055296323
    35021.263000.0510.070.0220.0190.435+j0.3590.070+j0.0333352363386
    50023.390000.0360.050.0190.0170.408+j0.3220.050+j0.0323724447465
    75026.9135000.0230.0330.0170.0160.375+j0.2690.033+j0.0314387566563
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundGround SizeInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGAWGmmmmmmmmmmkg/kmkg/kminch
    TBA276.8116.664.4418.191x882.7945.5453.421.5256.4634524323
    TBA1197.5917.454.4418.971x662.7947.2455.121.5258.1740226473
    TBA1/0198.5318.394.4419.911x662.7949.2557.121.5260.1741528573
    TBA2/0199.5519.414.4420.931x662.7951.4659.331.9163.1443032013
    TBA3/01910.7420.604.4422.121x662.7954.0361.901.9165.7144835063.5
    578144^4/01812.0721.924.4423.441x442.7956.9066.221.5269.2755147773.5
    578135^2503513.2123.274.4424.791x442.7959.7969.141.5272.1956852493.5
    TBA3503715.6525.704.4427.231x442.7965.0772.951.9176.7659250344
    TBA5003718.6928.754.4430.281x333.1872.4280.292.1684.6169362344.5
    578149^7505823.0633.684.4435.711x1/01/03.1884.1594.011.7897.56102296885
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2396.2453130.87271.200.01220.09510.731+j0.5080.365+j0.0452249135157
    1406.4067020.69230.950.01130.08860.657+j0.4910.289+j0.0422345154178
    1/0421.6484550.54790.750.01040.08530.599+j0.4730.229+j0.0402460176202
    2/0441.96106580.43640.600.00980.07870.553+j0.4550.182+j0.0392584204229
    3/0459.74134390.34450.470.00880.07550.515+j0.4350.144+j0.0372730234260
    4/0485.14169460.27560.380.00820.06890.485+j0.4130.115+j0.0362891268294
    250505.46200250.22970.310.00760.06560.465+j0.3930.096+j0.0353055296323
    350538.48280350.16730.230.00670.06230.435+j0.3590.070+j0.0333352363386
    500591.82400500.11810.160.00580.05580.408+j0.3220.050+j0.0323724447465
    750683.26600750.07550.110.00520.05250.375+j0.2690.033+j0.0314387566563
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E