SPEC 26325

HVTECK AL 1/C 175NLEPR CB PVC AIA PVC 15kV 100% CSA

Single Conductor, 175 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:175 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 175 NLEPR AIA 15kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ft
    270.2680.6561750.7167x14801.336501.436785
    1190.2980.6861750.7467x14801.366501.466825
    1/0190.3360.7241750.7847x14801.404501.504875
    2/0190.3760.7641750.82411x14801.444501.544987
    3/0190.4220.8101750.87011x14801.490501.5901056
    4/0190.4740.8621750.92211x14801.542601.6621170
    250370.5200.9161750.97613x14801.596601.7161281
    350370.6151.0111751.07117x14801.749601.8691555
    500370.7351.1311751.19121x14801.869601.9891943
    750610.9081.3141751.37417x121102.112602.2322540
    1000611.0601.4661751.52617x121102.264752.4142991
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    217.23980.2670.3360.0430.0600.692 + j0.4620.337 + j0.0605458169176
    117.65020.2110.2660.0400.0580.624 + j0.4460.267 + j0.0575458194198
    1/018.06330.1680.2110.0370.0560.569 + j0.4280.212 + j0.0555458222223
    2/018.57980.1330.1670.0340.0540.526 + j0.4100.168 + j0.0538577255250
    3/019.110060.1050.1330.0310.0520.491 + j0.3900.134 + j0.0518577290278
    4/019.912690.0840.1050.0290.0500.462 + j0.3700.106 + j0.0498577329309
    25020.615000.0710.0900.0270.0490.444 + j0.3500.091 + j0.04810137370347
    35022.421000.0500.0650.0230.0470.413 + j0.3190.066 + j0.04613256446402
    50023.930000.0350.0460.0200.0450.385 + j0.2840.047 + j0.04316376533451
    75026.845000.0240.0330.0170.0420.356 + j0.2400.034 + j0.04121062631500
    100029.060000.0180.0260.0150.0410.335 + j0.2100.027 + j0.03921062707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/km
    276.8116.664.4418.197x142.0333.931.2736.471168
    1197.5717.424.4418.957x142.0334.701.2737.241228
    1/0198.5318.394.4419.917x142.0335.661.2738.201302
    2/0199.5519.414.4420.9311x142.0336.681.2739.221469
    3/01910.7220.574.4422.1011x142.0337.851.2740.391572
    4/01912.0421.894.4423.4211x142.0339.171.5242.211741
    2503713.2123.274.4424.7913x142.0340.541.5243.591906
    3503715.6225.684.4427.2017x142.0344.421.5247.472314
    5003718.6728.734.4430.2521x142.0347.471.5250.522892
    7506123.0633.384.4434.9017x122.7953.641.5256.693780
    10006126.9237.244.4438.7617x122.7957.511.9161.324451
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2436.8817710.87601.100.01310.19690.692 + j0.4620.337 + j0.0605458169176
    1447.0422340.69230.870.01220.19030.624 + j0.4460.267 + j0.0575458194198
    1/0457.2028170.55120.690.01130.18370.569 + j0.4280.212 + j0.0555458222223
    2/0469.9035510.43640.550.01040.17720.526 + j0.4100.168 + j0.0538577255250
    3/0485.1444770.34450.440.00940.17060.491 + j0.3900.134 + j0.0518577290278
    4/0505.4656470.27560.340.00880.16400.462 + j0.3700.106 + j0.0498577329309
    250523.2466750.23290.300.00820.16080.444 + j0.3500.091 + j0.04810137370347
    350568.9693450.16400.210.00700.15420.413 + j0.3190.066 + j0.04613256446402
    500607.06133500.11480.150.00610.14760.385 + j0.2840.047 + j0.04316376533451
    750680.72200250.07870.110.00520.13780.356 + j0.2400.034 + j0.04121062631500
    1000736.60267000.05910.090.00460.13450.335 + j0.2100.027 + j0.03921062707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A