SPEC 26322

HVTECK AL 1/C 220NLEPR TS PVC AIA PVC 15kV 133% CSA

Single Conductor, 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 220 NLEPR AIA 15kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchmilinchmilinchlb/1000ftlb/1000ftinch
    270.2680.7462200.806801.196501.296668283.5
    1190.2990.7772200.837801.227501.327698743.5
    1/0190.3360.8142200.874801.264501.364729303.5
    2/0190.3760.8542200.914801.304501.404759963.5
    3/0190.4230.9012200.961801.351501.4517910753.5
    4/0190.4750.9532201.013801.403501.5038311674
    250370.521.0062201.066801.456501.5568812594
    350370.6161.1022201.162801.652601.7729616304.5
    500370.7361.2222201.282801.772601.89210519045
    750610.9081.4042201.464801.954602.07412023485.5
    1000611.1171.6132201.6731102.223602.34313829376
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    29.13980.2660.3650.0460.0580.718+j0.4650.366+j0.0632528169176
    19.35020.2110.2890.0440.0560.643+j0.4500.290+j0.0602624194198
    1/09.56330.1670.2290.0410.0540.584+j0.4340.230+j0.0582739222223
    2/09.87980.1330.1820.0380.0520.537+j0.4180.183+j0.0562863255250
    3/010.210060.1050.1440.0350.050.499+j0.4000.145+j0.0543009290278
    4/010.512690.0840.1150.0320.0480.469+j0.3810.116+j0.0523170329309
    25010.915000.070.0960.030.0470.449+j0.3640.097+j0.0513334370347
    35012.421000.0510.070.0270.0460.417+j0.3340.071+j0.0503631446402
    50013.230000.0360.050.0230.0430.391+j0.3010.051+j0.0474003533451
    75014.545000.0230.0330.020.0410.361+j0.2590.035+j0.0444567631500
    100016.460000.0170.0250.0170.0390.337+j0.2220.027+j0.0445215707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/kmkg/kminch
    276.8118.955.5920.472.0330.381.2732.929812323.5
    1197.5919.745.5921.262.0331.171.2733.7110313013.5
    1/0198.5320.685.5922.202.0332.111.2734.6510713843.5
    2/0199.5521.695.5923.222.0333.121.2735.6611214823.5
    3/01910.7422.895.5924.412.0334.321.2736.8611816003.5
    4/01912.0724.215.5925.732.0335.641.2738.1812417374
    2503713.2125.555.5927.082.0336.981.2739.5213118744
    3503715.6527.995.5929.512.0341.961.5245.0114324264.5
    5003718.6931.045.5932.562.0345.011.5248.0615628335
    7506123.0635.665.5937.192.0349.631.5252.6817934945.5
    10006128.3740.975.5942.492.7956.461.5259.5120543716
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2231.1417710.87271.200.01400.19030.718+j0.4650.366+j0.0632528169176
    1236.2222340.69230.950.01340.18370.643+j0.4500.290+j0.0602624194198
    1/0241.3028170.54790.750.01250.17720.584+j0.4340.230+j0.0582739222223
    2/0248.9235510.43640.600.01160.17060.537+j0.4180.183+j0.0562863255250
    3/0259.0844770.34450.470.01070.16400.499+j0.4000.145+j0.0543009290278
    4/0266.7056470.27560.380.00980.15750.469+j0.3810.116+j0.0523170329309
    250276.8666750.22970.310.00910.15420.449+j0.3640.097+j0.0513334370347
    350314.9693450.16730.230.00820.15090.417+j0.3340.071+j0.0503631446402
    500335.28133500.11810.160.00700.14110.391+j0.3010.051+j0.0474003533451
    750368.30200250.07550.110.00610.13450.361+j0.2590.035+j0.0444567631500
    1000416.56267000.05580.080.00520.12800.337+j0.2220.027+j0.0445215707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC