SPEC 26321

HVTECK AL 1/C 175NLEPR TS PVC AIA PVC 15kV 100% CSA

Single Conductor, 175 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:175 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 175 NLEPR AIA 15kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchmilinchmilinchlb/1000ftlb/1000ftinch
    270.2680.6561750.716801.106501.206597223
    1190.2990.6871750.747801.137501.237627663
    1/0190.3360.7241750.784801.174501.274658193
    2/0190.3760.7641750.824801.214501.314688823.5
    3/0190.4230.8111750.871801.261501.361729573.5
    4/0190.4750.8631750.923801.313501.4137610453.5
    250370.520.9161750.976801.366501.4668011334
    350370.6161.0121751.072801.562601.6828814874.5
    500370.7361.1321751.192801.682601.8029817514.5
    750610.9081.3141751.374801.864601.98411321805
    1000611.1171.5231751.5831102.133602.25313027486
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    28.43980.2660.3650.040.0560.712+j0.4990.366+j0.0612249169176
    18.75020.2110.2890.0370.0540.638+j0.4830.290+j0.0582345194198
    1/08.96330.1670.2290.0340.0520.580+j0.4670.230+j0.0562460222223
    2/09.27980.1330.1820.0320.050.535+j0.4490.183+j0.0542584255250
    3/09.510060.1050.1440.0290.0490.499+j0.4300.145+j0.0522730290278
    4/09.912690.0840.1150.0270.0470.470+j0.4100.116+j0.0512891329309
    25010.315000.070.0960.0250.0460.451+j0.3900.097+j0.0493055370347
    35011.821000.0510.070.0220.0450.421+j0.3580.071+j0.0493352446402
    50012.630000.0360.050.0190.0420.396+j0.3220.051+j0.0463724533451
    75013.945000.0230.0330.0160.040.367+j0.2760.035+j0.0434288631500
    100015.860000.0170.0250.0140.0380.344+j0.2350.027+j0.0434936707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/kmkg/kminch
    276.8116.664.4418.192.0328.091.2730.638810743
    1197.5917.454.4418.972.0328.881.2731.429211403
    1/0198.5318.394.4419.912.0329.821.2732.369712193
    2/0199.5519.414.4420.932.0330.841.2733.3810113133.5
    3/01910.7420.604.4422.122.0332.031.2734.5710714243.5
    4/01912.0721.924.4423.442.0333.351.2735.8911315553.5
    2503713.2123.274.4424.792.0334.701.2737.2411916864
    3503715.6525.704.4427.232.0339.671.5242.7213122134.5
    5003718.6928.754.4430.282.0342.721.5245.7714626064.5
    7506123.0633.384.4434.902.0347.351.5250.3916832445
    10006128.3738.684.4440.212.7954.181.5257.2319340896
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2213.3617710.87271.200.01220.18370.712+j0.4990.366+j0.0612249169176
    1220.9822340.69230.950.01130.17720.638+j0.4830.290+j0.0582345194198
    1/0226.0628170.54790.750.01040.17060.580+j0.4670.230+j0.0562460222223
    2/0233.6835510.43640.600.00980.16400.535+j0.4490.183+j0.0542584255250
    3/0241.3044770.34450.470.00880.16080.499+j0.4300.145+j0.0522730290278
    4/0251.4656470.27560.380.00820.15420.470+j0.4100.116+j0.0512891329309
    250261.6266750.22970.310.00760.15090.451+j0.3900.097+j0.0493055370347
    350299.7293450.16730.230.00670.14760.421+j0.3580.071+j0.0493352446402
    500320.04133500.11810.160.00580.13780.396+j0.3220.051+j0.0463724533451
    750353.06200250.07550.110.00490.13120.367+j0.2760.035+j0.0434288631500
    1000401.32267000.05580.080.00430.12470.344+j0.2350.027+j0.0434936707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.000