SPEC 26312

HVTECK CU 1/C 220TRXLPE TS PVC AIA PVC 15kV 133% CSA

Single Conductor, 220 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:220 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 220 TRXLPE AIA 15kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchmilinchmilinchlb/1000ftlb/1000ftinch
    TBA270.2830.7612200.821801.211501.3112739843.5
    TBA1190.3220.82200.86801.25501.3532910753.5
    TBA1/0190.3620.842200.9801.29501.3940011823.5
    6709652/0190.4050.8842200.944801.468501.56849313274
    TBA3/0190.4560.9342200.994801.384501.48460014664
    672441^4/0190.5120.992201.05801.574601.69474416934.5
    TBA250370.5581.0442201.104801.594601.71486320074.5
    671319350370.6611.1472201.207801.731601.851118322745
    672047500370.7891.2752201.335801.859601.979165628565
    641194750610.9681.4642201.5241102.108602.228244339286
    6720461000611.1171.6132201.6731102.257752.407322649186.5
    672445^1000611.1171.6132201.6731102.257752.407322649096.5
    TBA1250911.251.752201.811102.36752.51400860756.5
    TBA1500911.371.872201.931102.48752.63479069887
    TBA20001271.5832.0832202.1431102.693752.843635187837.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    29.25300.1620.2210.0590.0570.574+j0.4590.222+j0.0632575215221
    19.56690.1280.1750.0540.0550.529+j0.4420.176+j0.0602696245247
    1/09.78440.1020.1390.050.0530.494+j0.4250.140+j0.0582820278275
    2/01110640.0820.1120.0470.0530.465+j0.4080.113+j0.0582956317306
    3/010.413420.0640.0870.0430.0490.441+j0.3900.088+j0.0543111357335
    4/011.916920.0510.070.040.0490.421+j0.3700.071+j0.0553284404369
    2501220000.0430.0590.0370.0470.409+j0.3530.060+j0.0533452456412
    3501328000.0310.0430.0330.0450.387+j0.3220.044+j0.0513771537456
    50013.940000.0210.030.0290.0430.367+j0.2890.032+j0.0484167616497
    75015.660000.0140.0210.0240.0410.344+j0.2490.023+j0.0464753706551
    100016.880000.0110.0180.0220.0390.329+j0.2220.020+j0.0445215813596
    100016.880000.0110.0180.0220.0390.329+j0.2220.020+j0.0445215813596
    125017.6100000.0080.0140.020.0380.315+j0.2010.016+j0.0435639889632
    150018.4120000.0070.0140.0180.0370.305+j0.1850.016+j0.0426011956663
    200019.9160000.0050.0130.0160.0350.288+j0.1600.015+j0.04066711073715
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/kmkg/kminch
    TBA277.1919.335.5920.852.0330.761.2733.3040614643.5
    TBA1198.1820.325.5921.842.0331.751.2734.2949016003.5
    TBA1/0199.1921.345.5922.862.0332.771.2735.3159517593.5
    6709652/01910.2922.455.5923.982.0337.291.2739.8373419754
    TBA3/01911.5823.725.5925.252.0335.151.2737.6989321824
    672441^4/01913.0025.155.5926.672.0339.981.5243.03110725194.5
    TBA2503714.1726.525.5928.042.0340.491.5243.54128429874.5
    6713193503716.7929.135.5930.662.0343.971.5247.02176033845
    6720475003720.0432.395.5933.912.0347.221.5250.27246442505
    6411947506124.5937.195.5938.712.7953.541.5256.59363658466
    67204610006128.3740.975.5942.492.7957.331.9161.14480173196.5
    672445^10006128.3740.975.5942.492.7957.331.9161.14480173056.5
    TBA12509131.7544.455.5945.972.7959.941.9163.75596590416.5
    TBA15009134.8047.505.5949.022.7962.991.9166.807128103997
    TBA200012740.2152.915.5954.432.7968.401.9172.219451130717.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2233.6823590.53150.730.01800.18700.574+j0.4590.222+j0.0632575215221
    1241.3029770.41990.570.01650.18040.529+j0.4420.176+j0.0602696245247
    1/0246.3837560.33460.460.01520.17390.494+j0.4250.140+j0.0582820278275
    2/0279.4047350.26900.370.01430.17390.465+j0.4080.113+j0.0582956317306
    3/0264.1659720.21000.290.01310.16080.441+j0.3900.088+j0.0543111357335
    4/0302.2675290.16730.230.01220.16080.421+j0.3700.071+j0.0553284404369
    250304.8089000.14110.190.01130.15420.409+j0.3530.060+j0.0533452456412
    350330.20124600.10170.140.01010.14760.387+j0.3220.044+j0.0513771537456
    500353.06178000.06890.100.00880.14110.367+j0.2890.032+j0.0484167616497
    750396.24267000.04590.070.00730.13450.344+j0.2490.023+j0.0464753706551
    1000426.72356000.03610.060.00670.12800.329+j0.2220.020+j0.0445215813596
    1000426.72356000.03610.060.00670.12800.329+j0.2220.020+j0.0445215813596
    1250447.04445000.02620.050.00610.12470.315+j0.2010.016+j0.0435639889632
    1500467.36534000.02300.050.00550.12140.305+j0.1850.016+j0.0426011956663
    2000505.46712000.01640.040.00490.11480.288+j0.1600.015+j0.04066711073715
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.001