SPEC 26306

HVTECK CU 1/C 220NLEPR CB PVC AIA PVC 15kV 133% CSA

Single Conductor, 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 220 NLEPR AIA 15kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchinchmilinchlb/1000ftlb/1000ftinch
    TBA270.2830.7612200.8215x12801.2711.581601.70135415864.5
    TBA1190.3220.82200.867x12801.311.62601.7445817384.5
    TBA1/0190.3620.842200.97x12801.351.66601.7852918584.5
    6469112/0190.4050.8842200.9447x12801.3941.424501.52455413984
    TBA3/0190.4560.9342200.9949x12801.4441.754601.87476322095
    TBA4/0190.5120.992201.059x12801.51.81601.9390224175
    TBA250370.5581.0442201.10411x12801.5541.864601.984106826545
    TBA350370.6611.1472201.20713x12801.6571.967602.087143831525.5
    646932500370.7891.2522201.31217x121101.8221.951602.071190432155.5
    587685750610.9681.4642201.52421x121102.0342.276752.426288746256.5
    TBA750610.9681.4642201.52421x121102.0342.344752.494285251656.5
    TBA1000611.1171.6132201.67321x121102.1832.493752.643363761497
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    211.95300.1620.2210.0450.0630.518+j0.2020.224+j0.0692770215221
    112.26690.1280.1750.0420.060.418+j0.1300.179+j0.0663879245247
    1/012.58440.1020.1390.0390.0580.381+j0.1290.143+j0.0633879278275
    2/010.710640.0820.1120.0360.0520.355+j0.1270.115+j0.0573879317306
    3/013.113420.0640.0870.0330.0540.288+j0.0910.092+j0.0594987357335
    4/013.516920.0510.070.0310.0520.270+j0.0900.075+j0.0574987404369
    25013.920000.0430.0590.0290.0510.229+j0.0690.065+j0.0556095456412
    35014.628000.0310.0430.0250.0480.190+j0.0550.049+j0.0527203537456
    50014.540000.0210.030.0210.0440.145+j0.0390.037+j0.0489420616497
    7501760000.0140.0210.0190.0430.115+j0.0310.030+j0.04511636706551
    75017.560000.0140.0210.0190.0430.115+j0.0310.030+j0.04611636706551
    100018.580000.0110.0180.0170.0410.112+j0.0300.027+j0.04411636813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmmmkg/kmkg/kminch
    TBA277.1919.335.5920.855x122.0332.2840.161.5243.2152723604.5
    TBA1198.1820.325.5921.847x122.0333.2741.151.5244.2068225864.5
    TBA1/0199.1921.345.5922.867x122.0334.2942.161.5245.2178727654.5
    6469112/01910.2922.455.5923.987x122.0335.4136.171.2738.7182420804
    TBA3/01911.5823.725.5925.259x122.0336.6844.551.5247.60113532875
    TBA4/01913.0025.155.5926.679x122.0338.1045.971.5249.02134235975
    TBA2503714.1726.525.5928.0411x122.0339.4747.351.5250.39158939505
    TBA3503716.7929.135.5930.6613x122.0342.0949.961.5253.01214046915.5
    6469325003720.0431.805.5933.3217x122.7946.2849.561.5252.60283347845.5
    5876857506124.5937.195.5938.7121x122.7951.6657.811.9161.62429668836.5
    TBA7506124.5937.195.5938.7121x122.7951.6659.541.9163.35424476866.5
    TBA10006128.3740.975.5942.4921x122.7955.4563.321.9167.13541291517
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2302.2623590.53150.730.01370.20670.518+j0.2020.224+j0.0692770215221
    1309.8829770.41990.570.01280.19690.418+j0.1300.179+j0.0663879245247
    1/0317.5037560.33460.460.01190.19030.381+j0.1290.143+j0.0633879278275
    2/0271.7847350.26900.370.01100.17060.355+j0.1270.115+j0.0573879317306
    3/0332.7459720.21000.290.01010.17720.288+j0.0910.092+j0.0594987357335
    4/0342.9075290.16730.230.00940.17060.270+j0.0900.075+j0.0574987404369
    250353.0689000.14110.190.00880.16730.229+j0.0690.065+j0.0556095456412
    350370.84124600.10170.140.00760.15750.190+j0.0550.049+j0.0527203537456
    500368.30178000.06890.100.00640.14440.145+j0.0390.037+j0.0489420616497
    750431.80267000.04590.070.00580.14110.115+j0.0310.030+j0.04511636706551
    750444.50267000.04590.070.00580.14110.115+j0.0310.030+j0.04611636706551
    1000469.90356000.03610.060.00520.13450.112+j0.0300.027+j0.04411636813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC