SPEC 26302

HVTECK CU 1/C 220NLEPR TS PVC AIA PVC 15kV 133% CSA

Single Conductor, 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 220 NLEPR AIA 15kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchmilinchmilinchlb/1000ftlb/1000ftinch
    TBA270.2830.7612200.821801.211501.3112739843.5
    TBA1190.3220.82200.86801.25501.3532910753.5
    TBA1/0190.3620.842200.9801.29501.3940011823.5
    TBA2/0190.4050.8832200.943801.333501.43348913093.5
    TBA3/0190.4560.9342200.994801.384501.48460014664
    582434^^4/0190.5120.992201.05801.424551.53474415884
    586051250370.5581.0442201.124801.636601.75686819024.5
    TBA350370.6611.1472201.207801.697601.817118024274.5
    576699500370.7891.2522201.312801.836601.956165428975
    582433^^500370.7891.2752201.335801.839661.971165628525
    TBA750610.9681.4642201.5241102.074602.194244141316
    6792471000611.1171.6132201.6731102.237662.369322648386
    5865351000611.1171.6132201.6731102.237662.369322648356
    6745671250911.251.782201.881102.464752.614401560717
    5867141250911.251.782201.881102.464752.614401560607
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    ^^ Tinned Conductors
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    29.25300.1620.2210.0450.0570.574+j0.4590.222+j0.0632575215221
    19.56690.1280.1750.0420.0550.529+j0.4420.176+j0.0602696245247
    1/09.78440.1020.1390.0390.0530.494+j0.4250.140+j0.0582820278275
    2/01010640.0820.1120.0360.0510.467+j0.4080.113+j0.0562953317306
    3/010.413420.0640.0870.0330.0490.441+j0.3900.088+j0.0543111357335
    4/010.716920.0510.070.0310.0470.423+j0.3700.071+j0.0523284404369
    25012.320000.0430.0590.0290.0480.408+j0.3470.060+j0.0533514456412
    35012.728000.0310.0430.0250.0450.388+j0.3220.044+j0.0503771537456
    50013.740000.0210.030.0210.0430.368+j0.2940.032+j0.0484096616497
    50013.840000.0210.030.0220.0430.367+j0.2890.032+j0.0484167616497
    75015.460000.0140.0210.0190.0410.344+j0.2490.023+j0.0464753706551
    100016.680000.0110.0180.0170.0390.329+j0.2220.020+j0.0445215813596
    100016.680000.0110.0180.0170.0390.329+j0.2220.020+j0.0445215813596
    125018.3100000.0080.0140.0160.0390.309+j0.1920.016+j0.0445856889632
    125018.3100000.0080.0140.0160.0390.309+j0.1920.016+j0.0445856889632
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/kmkg/kminch
    TBA277.1919.335.5920.852.0330.761.2733.3040614643.5
    TBA1198.1820.325.5921.842.0331.751.2734.2949016003.5
    TBA1/0199.1921.345.5922.862.0332.771.2735.3159517593.5
    TBA2/01910.2922.435.5923.952.0333.861.2736.4072819483.5
    TBA3/01911.5823.725.5925.252.0335.151.2737.6989321824
    582434^^4/01913.0025.155.5926.672.0336.171.4038.96110723634
    5860512503714.1726.525.5928.552.0341.551.5244.60129228304.5
    TBA3503716.7929.135.5930.662.0343.101.5246.15175636124.5
    5766995003720.0431.805.5933.322.0346.631.5249.68246143115
    582433^^5003720.0432.395.5933.912.0346.711.6850.06246442445
    TBA7506124.5937.195.5938.712.7952.681.5255.73363361486
    67924710006128.3740.975.5942.492.7956.821.6860.17480172006
    58653510006128.3740.975.5942.492.7956.821.6860.17480171956
    67456712509131.7545.215.5947.752.7962.591.9166.40597590357
    58671412509131.7545.215.5947.752.7962.591.9166.40597590187
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    ^^ Tinned Conductors
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2233.6823590.53150.730.01370.18700.574+j0.4590.222+j0.0632575215221
    1241.3029770.41990.570.01280.18040.529+j0.4420.176+j0.0602696245247
    1/0246.3837560.33460.460.01190.17390.494+j0.4250.140+j0.0582820278275
    2/0254.0047350.26900.370.01100.16730.467+j0.4080.113+j0.0562953317306
    3/0264.1659720.21000.290.01010.16080.441+j0.3900.088+j0.0543111357335
    4/0271.7875290.16730.230.00940.15420.423+j0.3700.071+j0.0523284404369
    250312.4289000.14110.190.00880.15750.408+j0.3470.060+j0.0533514456412
    350322.58124600.10170.140.00760.14760.388+j0.3220.044+j0.0503771537456
    500347.98178000.06890.100.00640.14110.368+j0.2940.032+j0.0484096616497
    500350.52178000.06890.100.00670.14110.367+j0.2890.032+j0.0484167616497
    750391.16267000.04590.070.00580.13450.344+j0.2490.023+j0.0464753706551
    1000421.64356000.03610.060.00520.12800.329+j0.2220.020+j0.0445215813596
    1000421.64356000.03610.060.00520.12800.329+j0.2220.020+j0.0445215813596
    1250464.82445000.02620.050.00490.12800.309+j0.1920.016+j0.0445856889632
    1250464.82445000.02620.050.00490.12800.309+j0.1920.016+j0.0445856889632
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.001

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC