SPEC 26301

HVTECK CU 1/C 175NLEPR TS PVC AIA PVC 15kV 100% CSA

Single Conductor, 175 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:175 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 175 NLEPR AIA 15kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchmilinchmilinchlb/1000ftlb/1000ftinch
    270.2830.6711750.731801.121501.2212658773
    1190.3220.711750.77801.16501.263219653
    1/0190.3620.751750.81801.2501.339310693.5
    2/0190.4050.7931750.853801.243501.34348111923.5
    3/0190.4560.8441750.904801.294501.39459213453.5
    4/0190.5120.91750.96801.35501.4573215303.5
    250370.5580.9541751.014801.404501.50485517014
    350370.6611.0571751.117801.607601.727117322814.5
    500370.7891.1851751.245801.735601.855164628725
    750610.9681.3741751.434801.924602.044243438445.5
    1000611.1171.5231751.5831102.133602.253321848866
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    28.55300.1620.2210.0380.0550.569+j0.4940.222+j0.0622296215221
    18.86690.1280.1750.0350.0530.526+j0.4750.176+j0.0592417245247
    1/09.18440.1020.1390.0330.0510.492+j0.4570.140+j0.0572541278275
    2/09.410640.0820.1120.030.0490.466+j0.4390.113+j0.0552674317306
    3/09.813420.0640.0870.0280.0470.442+j0.4190.088+j0.0532832357335
    4/010.216920.0510.070.0260.0460.425+j0.3980.071+j0.0513005404369
    25010.520000.0430.0590.0240.0440.413+j0.3790.060+j0.0503173456412
    35012.128000.0310.0430.0210.0440.392+j0.3450.044+j0.0493492537456
    5001340000.0210.030.0180.0410.373+j0.3090.031+j0.0473888616497
    75014.360000.0140.0210.0150.0390.351+j0.2650.023+j0.0444474706551
    100015.880000.0110.0180.0140.0380.337+j0.2350.020+j0.0434936813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/kmkg/kminch
    277.1917.044.4418.572.0328.471.2731.0139413053
    1198.1818.034.4419.562.0329.461.2732.0047814363
    1/0199.1919.054.4420.572.0330.481.2733.0258515913.5
    2/01910.2920.144.4421.672.0331.571.2734.1171617743.5
    3/01911.5821.444.4422.962.0332.871.2735.4188120023.5
    4/01913.0022.864.4424.382.0334.291.2736.83108922773.5
    2503714.1724.234.4425.762.0335.661.2738.20127225314
    3503716.7926.854.4428.372.0340.821.5243.87174633954.5
    5003720.0430.104.4431.622.0344.071.5247.12245042745
    7506124.5934.904.4436.422.0348.871.5251.92362257215.5
    10006128.3738.684.4440.212.7954.181.5257.23478972716
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2215.9023590.53150.730.01160.18040.569+j0.4940.222+j0.0622296215221
    1223.5229770.41990.570.01070.17390.526+j0.4750.176+j0.0592417245247
    1/0231.1437560.33460.460.01010.16730.492+j0.4570.140+j0.0572541278275
    2/0238.7647350.26900.370.00910.16080.466+j0.4390.113+j0.0552674317306
    3/0248.9259720.21000.290.00850.15420.442+j0.4190.088+j0.0532832357335
    4/0259.0875290.16730.230.00790.15090.425+j0.3980.071+j0.0513005404369
    250266.7089000.14110.190.00730.14440.413+j0.3790.060+j0.0503173456412
    350307.34124600.10170.140.00640.14440.392+j0.3450.044+j0.0493492537456
    500330.20178000.06890.100.00550.13450.373+j0.3090.031+j0.0473888616497
    750363.22267000.04590.070.00460.12800.351+j0.2650.023+j0.0444474706551
    1000401.32356000.03610.060.00430.12470.337+j0.2350.020+j0.0434936813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.000