SPEC 26301
HVTECK CU 1/C 175NLEPR TS PVC AIA PVC 15kV 100% CSA
Single Conductor, 175 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:175 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 175 NLEPR AIA 15kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 2 | 7 | 0.283 | 0.671 | 175 | 0.731 | 80 | 1.121 | 50 | 1.221 | 265 | 877 | 3 |
| 1 | 19 | 0.322 | 0.71 | 175 | 0.77 | 80 | 1.16 | 50 | 1.26 | 321 | 965 | 3 |
| 1/0 | 19 | 0.362 | 0.75 | 175 | 0.81 | 80 | 1.2 | 50 | 1.3 | 393 | 1069 | 3.5 |
| 2/0 | 19 | 0.405 | 0.793 | 175 | 0.853 | 80 | 1.243 | 50 | 1.343 | 481 | 1192 | 3.5 |
| 3/0 | 19 | 0.456 | 0.844 | 175 | 0.904 | 80 | 1.294 | 50 | 1.394 | 592 | 1345 | 3.5 |
| 4/0 | 19 | 0.512 | 0.9 | 175 | 0.96 | 80 | 1.35 | 50 | 1.45 | 732 | 1530 | 3.5 |
| 250 | 37 | 0.558 | 0.954 | 175 | 1.014 | 80 | 1.404 | 50 | 1.504 | 855 | 1701 | 4 |
| 350 | 37 | 0.661 | 1.057 | 175 | 1.117 | 80 | 1.607 | 60 | 1.727 | 1173 | 2281 | 4.5 |
| 500 | 37 | 0.789 | 1.185 | 175 | 1.245 | 80 | 1.735 | 60 | 1.855 | 1646 | 2872 | 5 |
| 750 | 61 | 0.968 | 1.374 | 175 | 1.434 | 80 | 1.924 | 60 | 2.044 | 2434 | 3844 | 5.5 |
| 1000 | 61 | 1.117 | 1.523 | 175 | 1.583 | 110 | 2.133 | 60 | 2.253 | 3218 | 4886 | 6 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 8.5 | 530 | 0.162 | 0.221 | 0.038 | 0.055 | 0.569+j0.494 | 0.222+j0.062 | 2296 | 215 | 221 |
| 1 | 8.8 | 669 | 0.128 | 0.175 | 0.035 | 0.053 | 0.526+j0.475 | 0.176+j0.059 | 2417 | 245 | 247 |
| 1/0 | 9.1 | 844 | 0.102 | 0.139 | 0.033 | 0.051 | 0.492+j0.457 | 0.140+j0.057 | 2541 | 278 | 275 |
| 2/0 | 9.4 | 1064 | 0.082 | 0.112 | 0.03 | 0.049 | 0.466+j0.439 | 0.113+j0.055 | 2674 | 317 | 306 |
| 3/0 | 9.8 | 1342 | 0.064 | 0.087 | 0.028 | 0.047 | 0.442+j0.419 | 0.088+j0.053 | 2832 | 357 | 335 |
| 4/0 | 10.2 | 1692 | 0.051 | 0.07 | 0.026 | 0.046 | 0.425+j0.398 | 0.071+j0.051 | 3005 | 404 | 369 |
| 250 | 10.5 | 2000 | 0.043 | 0.059 | 0.024 | 0.044 | 0.413+j0.379 | 0.060+j0.050 | 3173 | 456 | 412 |
| 350 | 12.1 | 2800 | 0.031 | 0.043 | 0.021 | 0.044 | 0.392+j0.345 | 0.044+j0.049 | 3492 | 537 | 456 |
| 500 | 13 | 4000 | 0.021 | 0.03 | 0.018 | 0.041 | 0.373+j0.309 | 0.031+j0.047 | 3888 | 616 | 497 |
| 750 | 14.3 | 6000 | 0.014 | 0.021 | 0.015 | 0.039 | 0.351+j0.265 | 0.023+j0.044 | 4474 | 706 | 551 |
| 1000 | 15.8 | 8000 | 0.011 | 0.018 | 0.014 | 0.038 | 0.337+j0.235 | 0.020+j0.043 | 4936 | 813 | 596 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | mm | mm | mm | mm | kg/km | kg/km | inch |
| 2 | 7 | 7.19 | 17.04 | 4.44 | 18.57 | 2.03 | 28.47 | 1.27 | 31.01 | 394 | 1305 | 3 |
| 1 | 19 | 8.18 | 18.03 | 4.44 | 19.56 | 2.03 | 29.46 | 1.27 | 32.00 | 478 | 1436 | 3 |
| 1/0 | 19 | 9.19 | 19.05 | 4.44 | 20.57 | 2.03 | 30.48 | 1.27 | 33.02 | 585 | 1591 | 3.5 |
| 2/0 | 19 | 10.29 | 20.14 | 4.44 | 21.67 | 2.03 | 31.57 | 1.27 | 34.11 | 716 | 1774 | 3.5 |
| 3/0 | 19 | 11.58 | 21.44 | 4.44 | 22.96 | 2.03 | 32.87 | 1.27 | 35.41 | 881 | 2002 | 3.5 |
| 4/0 | 19 | 13.00 | 22.86 | 4.44 | 24.38 | 2.03 | 34.29 | 1.27 | 36.83 | 1089 | 2277 | 3.5 |
| 250 | 37 | 14.17 | 24.23 | 4.44 | 25.76 | 2.03 | 35.66 | 1.27 | 38.20 | 1272 | 2531 | 4 |
| 350 | 37 | 16.79 | 26.85 | 4.44 | 28.37 | 2.03 | 40.82 | 1.52 | 43.87 | 1746 | 3395 | 4.5 |
| 500 | 37 | 20.04 | 30.10 | 4.44 | 31.62 | 2.03 | 44.07 | 1.52 | 47.12 | 2450 | 4274 | 5 |
| 750 | 61 | 24.59 | 34.90 | 4.44 | 36.42 | 2.03 | 48.87 | 1.52 | 51.92 | 3622 | 5721 | 5.5 |
| 1000 | 61 | 28.37 | 38.68 | 4.44 | 40.21 | 2.79 | 54.18 | 1.52 | 57.23 | 4789 | 7271 | 6 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 215.90 | 2359 | 0.5315 | 0.73 | 0.0116 | 0.1804 | 0.569+j0.494 | 0.222+j0.062 | 2296 | 215 | 221 |
| 1 | 223.52 | 2977 | 0.4199 | 0.57 | 0.0107 | 0.1739 | 0.526+j0.475 | 0.176+j0.059 | 2417 | 245 | 247 |
| 1/0 | 231.14 | 3756 | 0.3346 | 0.46 | 0.0101 | 0.1673 | 0.492+j0.457 | 0.140+j0.057 | 2541 | 278 | 275 |
| 2/0 | 238.76 | 4735 | 0.2690 | 0.37 | 0.0091 | 0.1608 | 0.466+j0.439 | 0.113+j0.055 | 2674 | 317 | 306 |
| 3/0 | 248.92 | 5972 | 0.2100 | 0.29 | 0.0085 | 0.1542 | 0.442+j0.419 | 0.088+j0.053 | 2832 | 357 | 335 |
| 4/0 | 259.08 | 7529 | 0.1673 | 0.23 | 0.0079 | 0.1509 | 0.425+j0.398 | 0.071+j0.051 | 3005 | 404 | 369 |
| 250 | 266.70 | 8900 | 0.1411 | 0.19 | 0.0073 | 0.1444 | 0.413+j0.379 | 0.060+j0.050 | 3173 | 456 | 412 |
| 350 | 307.34 | 12460 | 0.1017 | 0.14 | 0.0064 | 0.1444 | 0.392+j0.345 | 0.044+j0.049 | 3492 | 537 | 456 |
| 500 | 330.20 | 17800 | 0.0689 | 0.10 | 0.0055 | 0.1345 | 0.373+j0.309 | 0.031+j0.047 | 3888 | 616 | 497 |
| 750 | 363.22 | 26700 | 0.0459 | 0.07 | 0.0046 | 0.1280 | 0.351+j0.265 | 0.023+j0.044 | 4474 | 706 | 551 |
| 1000 | 401.32 | 35600 | 0.0361 | 0.06 | 0.0043 | 0.1247 | 0.337+j0.235 | 0.020+j0.043 | 4936 | 813 | 596 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A