SPEC 26242

HVTECK CU 3/C 140NLEPR TS PVC AIA PVC 8kV 133% CSA

3 Conductor, 140 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:140 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    {SQMTR} {CSA} SOUTHWIRE® POWER CABLE {NESC} 3/C XXX AWG CU X.XXmm (140 mils) NL-EPR AIA GW 1 X X AWG CU 8KV 133% INS LEVEL 25%TS SUN. RES. 105°C FT4 HL (-40°C) LTGG RoHS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ftlb/1000ftinch
    TBA270.2830.6011400.6611x6801.924602.04486819052.5
    TBA1190.3220.641400.71x61102.068602.188103921593
    TBA1/0190.3620.681400.741x61102.154602.274125524433
    TBA2/0190.4050.7231400.7831x61102.247602.367152327853
    6498422/0190.4050.7241400.7841x61102.285752.435154032403
    TBA3/0190.4560.7741400.8341x41102.357752.507190833233
    TBA4/0190.5120.831400.891x41102.478752.628233138453.5
    TBA250370.5580.8841400.9441x41102.595752.745270543283.5
    TBA350370.6610.9871401.0471x31102.818752.968370155094
    TBA500370.7891.1151401.1751x31253.124853.294513572404.5
    649834500370.7891.0921401.1521x31253.13853.3513979064.5
    TBA750610.9681.3041401.3641x21253.532853.7027563100425
    TBA1000611.1171.4531401.5131x11253.854854.0249993127505.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    ^Black outer jacket
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    214.315920.1620.2210.0330.0260.583+j0.5330.221+j0.0432079172201
    115.320080.1280.1750.030.0240.540+j0.5120.175+j0.0402200197228
    1/015.925340.1020.1390.0280.0230.507+j0.4920.139+j0.0392324225257
    2/016.631940.0820.1120.0260.0210.481+j0.4710.112+j0.0382457260292
    2/01731940.0820.1120.0260.0210.482+j0.4710.112+j0.0382460260292
    3/017.540270.0640.0870.0230.020.458+j0.4480.087+j0.0362615297330
    4/018.450780.0510.070.0210.0190.441+j0.4250.070+j0.0352789342372
    25019.260000.0430.0590.020.0180.429+j0.4040.059+j0.0342956376410
    35020.884000.0310.0430.0170.0170.409+j0.3670.043+j0.0333275460487
    50023.1120000.0210.030.0150.0150.389+j0.3270.030+j0.0313672556573
    50023.1120000.0210.030.0140.0150.391+j0.3330.030+j0.0313600556573
    75025.9180000.0140.0210.0130.0140.366+j0.2770.021+j0.0304257678668
    100028.2240000.0110.0180.0110.0130.351+j0.2460.018+j0.0294719798772
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/kmkg/kminch
    TBA277.1915.273.5616.791x62.0348.871.5251.92129228352.5
    TBA1198.1816.263.5617.781x62.7952.531.5255.58154632133
    TBA1/0199.1917.273.5618.801x62.7954.711.5257.76186836363
    TBA2/01910.2918.363.5619.891x62.7957.071.5260.12226641453
    6498422/01910.2918.393.5619.911x62.7958.041.9161.85229248223
    TBA3/01911.5819.663.5621.181x42.7959.871.9163.68283949453
    TBA4/01913.0021.083.5622.611x42.7962.941.9166.75346957223.5
    TBA2503714.1722.453.5623.981x42.7965.911.9169.72402564413.5
    TBA3503716.7925.073.5626.591x32.7971.581.9175.39550881984
    TBA5003720.0428.323.5629.851x33.1879.352.1683.677642107744.5
    6498345003720.0427.743.5629.261x33.1879.502.1683.827648117654.5
    TBA7506124.5933.123.5634.651x23.1889.712.1694.0311255149445
    TBA10006128.3736.913.5638.431x13.1897.892.16102.2114871189745.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    ^Black outer jacket
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2363.2270840.53150.730.01010.08530.583+j0.5330.221+j0.0432079172201
    1388.6289360.41990.570.00910.07870.540+j0.5120.175+j0.0402200197228
    1/0403.86112760.33460.460.00850.07550.507+j0.4920.139+j0.0392324225257
    2/0421.64142130.26900.370.00790.06890.481+j0.4710.112+j0.0382457260292
    2/0431.80142130.26900.370.00790.06890.482+j0.4710.112+j0.0382460260292
    3/0444.50179200.21000.290.00700.06560.458+j0.4480.087+j0.0362615297330
    4/0467.36225970.16730.230.00640.06230.441+j0.4250.070+j0.0352789342372
    250487.68267000.14110.190.00610.05910.429+j0.4040.059+j0.0342956376410
    350528.32373800.10170.140.00520.05580.409+j0.3670.043+j0.0333275460487
    500586.74534000.06890.100.00460.04920.389+j0.3270.030+j0.0313672556573
    500586.74534000.06890.100.00430.04920.391+j0.3330.030+j0.0313600556573
    750657.86801000.04590.070.00400.04590.366+j0.2770.021+j0.0304257678668
    1000716.281068000.03610.060.00340.04270.351+j0.2460.018+j0.0294719798772
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC