SPEC 26241

HVTECK CU 3/C 115NLEPR TS PVC AIA PVC 8kV 100% CSA

3 Conductor, 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 115 NLEPR AIA 8kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo.inchinchmilinchAWGmilinchmilinchlb/1000ftlb/1000ft
    270.2820.5501150.6106801.877601.9977382028
    1190.3220.5901150.6506801.963602.0839022282
    1/0190.3610.6291150.68961102.107602.22711082695
    2/0190.4050.6731150.73361102.202602.32213683062
    3/0190.4560.7241150.78441102.313752.46317443637
    4/0190.5120.7801150.84041102.434752.58421564190
    250370.5580.8341150.89441102.550752.70025194699
    350370.6610.9371150.99731102.773752.92334955945
    500370.7891.0651151.12531103.049853.21949047758
    750610.9681.2541151.31421253.487853.657729410798
    1000611.1171.4031151.46311253.809853.979969313639
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    214.015920.1620.2040.0300.0400.574 + j0.5160.204 + j0.0411920172201
    114.620080.1280.1620.0300.0390.535 + j0.4920.162 + j0.0392044197228
    1/015.625340.1020.1280.0300.0370.502 + j0.4710.128 + j0.0372165225257
    2/016.331940.0810.1020.0200.0360.477 + j0.4490.102 + j0.0362302260292
    3/017.240270.0640.0810.0200.0300.456 + j0.4240.081 + j0.0352459297330
    4/018.150780.0510.0650.0200.0300.439 + j0.3990.065 + j0.0342633342372
    25018.960000.0430.0560.0200.0300.428 + j0.3760.056 + j0.0332800376410
    35020.584000.0300.0410.0200.0300.406 + j0.3380.410 + j0.0323120460487
    50022.5120000.0200.0300.0140.0300.385 + j0.2970.030 + j0.0303516556573
    75025.6180000.0140.0200.0120.0300.360 + j0.2480.023 + j0.0294102678668
    100027.9240000.0110.0200.0100.0300.341 + j0.2170.020 + j0.0284563798772
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo.mmmmmmmmAWGmmmmmmmmkg/kmkg/km
    277.1613.972.9215.4962.0347.681.5250.7210983018
    1198.1814.992.9216.5162.0349.861.5252.9113423396
    1/0199.1715.982.9217.5062.7953.521.5256.5716494011
    2/01910.2917.092.9218.6262.7955.931.5258.9820364557
    3/01911.5818.392.9219.9142.7958.751.9162.5625955412
    4/01913.0019.812.9221.3442.7961.821.9165.6332086235
    2503714.1721.182.9222.7142.7964.771.9168.5837496993
    3503716.7923.802.9225.3232.7970.431.9174.2452018847
    5003720.0427.052.9228.5832.7977.442.1681.76729811545
    7506124.5931.852.9233.3823.1888.572.1692.891085516069
    10006128.3735.642.9237.1613.1896.752.16101.071442520297
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2355.6070840.53150.670.00910.13120.574 + j0.5160.204 + j0.0411920172201
    1370.8489360.41990.530.00910.12800.535 + j0.4920.162 + j0.0392044197228
    1/0396.24112760.33460.420.00910.12140.502 + j0.4710.128 + j0.0372165225257
    2/0414.02142130.26570.330.00610.11810.477 + j0.4490.102 + j0.0362302260292
    3/0436.88179200.21000.270.00610.09840.456 + j0.4240.081 + j0.0352459297330
    4/0459.74225970.16730.210.00610.09840.439 + j0.3990.065 + j0.0342633342372
    250480.06267000.14110.180.00610.09840.428 + j0.3760.056 + j0.0332800376410
    350520.70373800.09840.130.00610.09840.406 + j0.3380.410 + j0.0323120460487
    500571.50534000.06560.100.00430.09840.385 + j0.2970.030 + j0.0303516556573
    750650.24801000.04590.070.00370.09840.360 + j0.2480.023 + j0.0294102678668
    1000708.661068000.03610.070.00300.09840.341 + j0.2170.020 + j0.0284563798772
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E

    Revision: 1.000.000