SPEC 26205

HVTECK CU 1/C 115NLEPR CB PVC AIA PVC 8kV 100% CSA

Single Conductor, 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 115 NLEPR AIA 8kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ftlb/1000ft
    270.2820.5501150.6107x14801.120501.220299812
    1190.3220.5901150.65011x14801.160501.260407947
    1/0190.3610.6291150.68911x14801.199501.2994741041
    2/0190.4050.6731150.73311x14801.353501.4535591167
    3/0190.4560.7241150.78413x14801.404501.5046941337
    4/0190.5120.7801150.84013x14801.460501.5608291510
    250370.5580.8341150.89417x14801.514601.63410011755
    350370.6610.9371150.99721x14801.675601.79513652241
    500370.7891.0651151.12526x14801.803601.92318962866
    750610.9681.2541151.31421x12801.992602.11227533968
    1000611.1171.4031151.46321x121102.201602.32135254985
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    214.65300.1620.2040.0310.0550.554 + j0.5110.205 + j0.0565458215221
    115.16690.1280.1620.0280.0530.516 + j0.4880.163 + j0.0538577245247
    1/015.68440.1020.1280.0260.0510.485 + j0.4680.129 + j0.0518577278275
    2/017.410640.0810.1020.0240.0510.459 + j0.4460.103 + j0.0518577317306
    3/018.013420.0640.0810.0210.0490.439 + j0.4230.082 + j0.04910137357335
    4/018.716920.0510.0650.0200.0470.424 + j0.3990.066 + j0.04810137404369
    25019.620000.0430.0560.0180.0460.414 + j0.3770.057 + j0.04613256456412
    35021.528000.0310.0410.0160.0450.393 + j0.3400.042 + j0.04516376537456
    50023.140000.0220.0300.0140.0420.374 + j0.3000.031 + j0.04220275616497
    75025.360000.0140.0230.0120.0400.352 + j0.2520.024 + j0.04026018706551
    100027.980000.0110.0190.0100.0390.334 + j0.2210.020 + j0.03826018813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/kmkg/km
    277.1613.972.9215.497x142.0328.451.2730.994451208
    1198.1814.992.9216.5111x142.0329.461.2732.006061409
    1/0199.1715.982.9217.5011x142.0330.451.2732.997051549
    2/01910.2917.092.9218.6211x142.0334.371.2736.918321737
    3/01911.5818.392.9219.9113x142.0335.661.2738.2010331990
    4/01913.0019.812.9221.3413x142.0337.081.2739.6212342247
    2503714.1721.182.9222.7117x142.0338.461.5241.5014902612
    3503716.7923.802.9225.3221x142.0342.551.5245.5920313335
    5003720.0427.052.9228.5826x142.0345.801.5248.8428224265
    7506124.5931.852.9233.3821x122.0350.601.5253.6440975905
    10006128.3735.642.9237.1621x122.7955.911.5258.9552467418
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2370.8423590.53150.670.00940.18040.554 + j0.5110.205 + j0.0565458215221
    1383.5429770.41990.530.00850.17390.516 + j0.4880.163 + j0.0538577245247
    1/0396.2437560.33460.420.00790.16730.485 + j0.4680.129 + j0.0518577278275
    2/0441.9647350.26570.330.00730.16730.459 + j0.4460.103 + j0.0518577317306
    3/0457.2059720.21000.270.00640.16080.439 + j0.4230.082 + j0.04910137357335
    4/0474.9875290.16730.210.00610.15420.424 + j0.3990.066 + j0.04810137404369
    250497.8489000.14110.180.00550.15090.414 + j0.3770.057 + j0.04613256456412
    350546.10124600.10170.130.00490.14760.393 + j0.3400.042 + j0.04516376537456
    500586.74178000.07220.100.00430.13780.374 + j0.3000.031 + j0.04220275616497
    750642.62267000.04590.080.00370.13120.352 + j0.2520.024 + j0.04026018706551
    1000708.66356000.03610.060.00300.12800.334 + j0.2210.020 + j0.03826018813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.000

    Updated On: July 12, 2024, 5:43 p.m. UTC