SPEC 26202
HVTECK CU 1/C 140NLEPR TS PVC AIA PVC 8kV 133% CSA
Single Conductor, 140 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:140 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 140 NLEPR AIA 8kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 2 | 7 | 0.283 | 0.601 | 140 | 0.661 | 65 | 1.021 | 50 | 1.121 | 260 | 769 | 3 |
| 1 | 19 | 0.322 | 0.64 | 140 | 0.7 | 80 | 1.09 | 50 | 1.19 | 316 | 885 | 3 |
| 1/0 | 19 | 0.362 | 0.68 | 140 | 0.74 | 80 | 1.13 | 50 | 1.23 | 387 | 986 | 3 |
| 2/0 | 19 | 0.405 | 0.723 | 140 | 0.783 | 80 | 1.173 | 50 | 1.273 | 476 | 1107 | 3 |
| 3/0 | 19 | 0.456 | 0.774 | 140 | 0.834 | 80 | 1.224 | 50 | 1.324 | 587 | 1256 | 3.5 |
| 4/0 | 19 | 0.512 | 0.83 | 140 | 0.89 | 80 | 1.28 | 50 | 1.38 | 726 | 1438 | 3.5 |
| 250 | 37 | 0.558 | 0.884 | 140 | 0.944 | 80 | 1.334 | 50 | 1.434 | 850 | 1606 | 3.5 |
| 350 | 37 | 0.661 | 0.987 | 140 | 1.047 | 80 | 1.437 | 50 | 1.537 | 1167 | 2001 | 4 |
| 500 | 37 | 0.789 | 1.115 | 140 | 1.175 | 80 | 1.665 | 60 | 1.785 | 1641 | 2756 | 4.5 |
| 750 | 61 | 0.968 | 1.304 | 140 | 1.364 | 80 | 1.854 | 60 | 1.974 | 2428 | 3715 | 5 |
| 1000 | 61 | 1.117 | 1.453 | 140 | 1.513 | 110 | 2.063 | 60 | 2.183 | 3212 | 4743 | 5.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 7.8 | 530 | 0.162 | 0.221 | 0.033 | 0.053 | 0.563+j0.522 | 0.222+j0.060 | 2079 | 215 | 221 |
| 1 | 8.3 | 669 | 0.128 | 0.175 | 0.03 | 0.052 | 0.520+j0.502 | 0.176+j0.057 | 2200 | 245 | 247 |
| 1/0 | 8.6 | 844 | 0.102 | 0.139 | 0.028 | 0.05 | 0.488+j0.484 | 0.140+j0.055 | 2324 | 278 | 275 |
| 2/0 | 8.9 | 1064 | 0.082 | 0.112 | 0.026 | 0.048 | 0.463+j0.464 | 0.113+j0.054 | 2457 | 317 | 306 |
| 3/0 | 9.3 | 1342 | 0.064 | 0.087 | 0.023 | 0.046 | 0.441+j0.443 | 0.088+j0.052 | 2615 | 357 | 335 |
| 4/0 | 9.7 | 1692 | 0.051 | 0.07 | 0.021 | 0.044 | 0.425+j0.421 | 0.071+j0.050 | 2789 | 404 | 369 |
| 250 | 10 | 2000 | 0.043 | 0.059 | 0.02 | 0.043 | 0.414+j0.401 | 0.060+j0.049 | 2956 | 456 | 412 |
| 350 | 10.8 | 2800 | 0.031 | 0.043 | 0.017 | 0.041 | 0.396+j0.365 | 0.044+j0.046 | 3275 | 537 | 456 |
| 500 | 12.5 | 4000 | 0.021 | 0.03 | 0.015 | 0.04 | 0.377+j0.326 | 0.031+j0.046 | 3672 | 616 | 497 |
| 750 | 13.8 | 6000 | 0.014 | 0.021 | 0.013 | 0.038 | 0.356+j0.278 | 0.023+j0.043 | 4257 | 706 | 551 |
| 1000 | 15.3 | 8000 | 0.011 | 0.018 | 0.011 | 0.037 | 0.342+j0.247 | 0.020+j0.042 | 4719 | 813 | 596 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | mm | mm | mm | mm | kg/km | kg/km | inch |
| 2 | 7 | 7.19 | 15.27 | 3.56 | 16.79 | 1.65 | 25.93 | 1.27 | 28.47 | 387 | 1144 | 3 |
| 1 | 19 | 8.18 | 16.26 | 3.56 | 17.78 | 2.03 | 27.69 | 1.27 | 30.23 | 470 | 1317 | 3 |
| 1/0 | 19 | 9.19 | 17.27 | 3.56 | 18.80 | 2.03 | 28.70 | 1.27 | 31.24 | 576 | 1467 | 3 |
| 2/0 | 19 | 10.29 | 18.36 | 3.56 | 19.89 | 2.03 | 29.79 | 1.27 | 32.33 | 708 | 1647 | 3 |
| 3/0 | 19 | 11.58 | 19.66 | 3.56 | 21.18 | 2.03 | 31.09 | 1.27 | 33.63 | 874 | 1869 | 3.5 |
| 4/0 | 19 | 13.00 | 21.08 | 3.56 | 22.61 | 2.03 | 32.51 | 1.27 | 35.05 | 1080 | 2140 | 3.5 |
| 250 | 37 | 14.17 | 22.45 | 3.56 | 23.98 | 2.03 | 33.88 | 1.27 | 36.42 | 1265 | 2390 | 3.5 |
| 350 | 37 | 16.79 | 25.07 | 3.56 | 26.59 | 2.03 | 36.50 | 1.27 | 39.04 | 1737 | 2978 | 4 |
| 500 | 37 | 20.04 | 28.32 | 3.56 | 29.85 | 2.03 | 42.29 | 1.52 | 45.34 | 2442 | 4101 | 4.5 |
| 750 | 61 | 24.59 | 33.12 | 3.56 | 34.65 | 2.03 | 47.09 | 1.52 | 50.14 | 3613 | 5529 | 5 |
| 1000 | 61 | 28.37 | 36.91 | 3.56 | 38.43 | 2.79 | 52.40 | 1.52 | 55.45 | 4780 | 7058 | 5.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 198.12 | 2359 | 0.5315 | 0.73 | 0.0101 | 0.1739 | 0.563+j0.522 | 0.222+j0.060 | 2079 | 215 | 221 |
| 1 | 210.82 | 2977 | 0.4199 | 0.57 | 0.0091 | 0.1706 | 0.520+j0.502 | 0.176+j0.057 | 2200 | 245 | 247 |
| 1/0 | 218.44 | 3756 | 0.3346 | 0.46 | 0.0085 | 0.1640 | 0.488+j0.484 | 0.140+j0.055 | 2324 | 278 | 275 |
| 2/0 | 226.06 | 4735 | 0.2690 | 0.37 | 0.0079 | 0.1575 | 0.463+j0.464 | 0.113+j0.054 | 2457 | 317 | 306 |
| 3/0 | 236.22 | 5972 | 0.2100 | 0.29 | 0.0070 | 0.1509 | 0.441+j0.443 | 0.088+j0.052 | 2615 | 357 | 335 |
| 4/0 | 246.38 | 7529 | 0.1673 | 0.23 | 0.0064 | 0.1444 | 0.425+j0.421 | 0.071+j0.050 | 2789 | 404 | 369 |
| 250 | 254.00 | 8900 | 0.1411 | 0.19 | 0.0061 | 0.1411 | 0.414+j0.401 | 0.060+j0.049 | 2956 | 456 | 412 |
| 350 | 274.32 | 12460 | 0.1017 | 0.14 | 0.0052 | 0.1345 | 0.396+j0.365 | 0.044+j0.046 | 3275 | 537 | 456 |
| 500 | 317.50 | 17800 | 0.0689 | 0.10 | 0.0046 | 0.1312 | 0.377+j0.326 | 0.031+j0.046 | 3672 | 616 | 497 |
| 750 | 350.52 | 26700 | 0.0459 | 0.07 | 0.0040 | 0.1247 | 0.356+j0.278 | 0.023+j0.043 | 4257 | 706 | 551 |
| 1000 | 388.62 | 35600 | 0.0361 | 0.06 | 0.0034 | 0.1214 | 0.342+j0.247 | 0.020+j0.042 | 4719 | 813 | 596 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Revision: 1.000.000