SPEC 26171

HVTECK AL 3/C 90TRXLPE TS PVC AIA PVC 5kV 100% CSA

3 Conductor, 90 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket.

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:90 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 90 TRXLPE AIA 5kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ftlb/1000ftinch
    270.2680.486900.5461x8801.675601.79519011572
    1190.2990.517900.5771x6801.742601.86222812872.5
    1/0190.3360.554900.6141x6801.822601.94223714092.5
    2/0190.3760.594900.6541x6801.909602.02924715552.5
    3/0190.4230.641900.7011x61102.07602.1925917503
    4/0190.4750.693900.7531x61102.182602.30227219613
    250370.520.746900.8061x41102.297752.44733222823
    350370.6160.842900.9021x41102.504752.65435627343.5
    500370.7360.962901.0221x31102.764752.91442334114
    750610.9081.144901.2041x21253.187853.35750745754.5
    1000611.1171.353901.4131x21253.638853.80855956665
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    212.611940.2660.3650.0310.0230.711+j0.5880.365+j0.0391723135157
    11315060.2110.2890.0290.0210.640+j0.5690.289+j0.0361819154178
    1/013.619000.1670.2290.0270.020.585+j0.5480.229+j0.0351933176202
    2/014.223950.1330.1820.0250.0190.543+j0.5270.182+j0.0342057204229
    3/015.330200.1050.1440.0220.0180.509+j0.5030.144+j0.0332203234260
    4/016.138080.0840.1150.020.0170.483+j0.4780.115+j0.0312364268294
    25017.145000.070.0960.0190.0160.466+j0.4550.096+j0.0312528296323
    35018.663000.0510.070.0160.0150.441+j0.4150.070+j0.0292826363386
    50020.490000.0360.050.0140.0140.418+j0.3700.050+j0.0283198447465
    75023.5135000.0230.0330.0120.0120.390+j0.3140.033+j0.0273761566563
    100026.7180000.0170.0250.010.0110.366+j0.2640.025+j0.0274409661638
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/kmkg/kminch
    276.8112.342.2913.871x82.0342.551.5245.5928317222
    1197.5913.132.2914.661x62.0344.251.5247.2933919152.5
    1/0198.5314.072.2915.601x62.0346.281.5249.3335320972.5
    2/0199.5515.092.2916.611x62.0348.491.5251.5436823142.5
    3/01910.7416.282.2917.811x62.7952.581.5255.6338526043
    4/01912.0717.602.2919.131x62.7955.421.5258.4740529183
    2503713.2118.952.2920.471x42.7958.341.9162.1549433963
    3503715.6521.392.2922.911x42.7963.601.9167.4153040693.5
    5003718.6924.432.2925.961x32.7970.211.9174.0262950764
    7506123.0629.062.2930.581x23.1880.952.1685.2775468084.5
    10006128.3734.372.2935.891x23.1892.412.1696.7283284325
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2320.0453130.87271.200.00940.07550.711+j0.5880.365+j0.0391723135157
    1330.2067020.69230.950.00880.06890.640+j0.5690.289+j0.0361819154178
    1/0345.4484550.54790.750.00820.06560.585+j0.5480.229+j0.0351933176202
    2/0360.68106580.43640.600.00760.06230.543+j0.5270.182+j0.0342057204229
    3/0388.62134390.34450.470.00670.05910.509+j0.5030.144+j0.0332203234260
    4/0408.94169460.27560.380.00610.05580.483+j0.4780.115+j0.0312364268294
    250434.34200250.22970.310.00580.05250.466+j0.4550.096+j0.0312528296323
    350472.44280350.16730.230.00490.04920.441+j0.4150.070+j0.0292826363386
    500518.16400500.11810.160.00430.04590.418+j0.3700.050+j0.0283198447465
    750596.90600750.07550.110.00370.03940.390+j0.3140.033+j0.0273761566563
    1000678.18801000.05580.080.00300.03610.366+j0.2640.025+j0.0274409661638
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E