SPEC 26171
HVTECK AL 3/C 90TRXLPE TS PVC AIA PVC 5kV 100% CSA
3 Conductor, 90 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket.

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:90 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Filler:Interstices filled with non-hydroscoping/non-wicking fillers
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 90 TRXLPE AIA 5kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 2 | 7 | 0.268 | 0.486 | 90 | 0.546 | 1x8 | 80 | 1.675 | 60 | 1.795 | 190 | 1157 | 2 |
| 1 | 19 | 0.299 | 0.517 | 90 | 0.577 | 1x6 | 80 | 1.742 | 60 | 1.862 | 228 | 1287 | 2.5 |
| 1/0 | 19 | 0.336 | 0.554 | 90 | 0.614 | 1x6 | 80 | 1.822 | 60 | 1.942 | 237 | 1409 | 2.5 |
| 2/0 | 19 | 0.376 | 0.594 | 90 | 0.654 | 1x6 | 80 | 1.909 | 60 | 2.029 | 247 | 1555 | 2.5 |
| 3/0 | 19 | 0.423 | 0.641 | 90 | 0.701 | 1x6 | 110 | 2.07 | 60 | 2.19 | 259 | 1750 | 3 |
| 4/0 | 19 | 0.475 | 0.693 | 90 | 0.753 | 1x6 | 110 | 2.182 | 60 | 2.302 | 272 | 1961 | 3 |
| 250 | 37 | 0.52 | 0.746 | 90 | 0.806 | 1x4 | 110 | 2.297 | 75 | 2.447 | 332 | 2282 | 3 |
| 350 | 37 | 0.616 | 0.842 | 90 | 0.902 | 1x4 | 110 | 2.504 | 75 | 2.654 | 356 | 2734 | 3.5 |
| 500 | 37 | 0.736 | 0.962 | 90 | 1.022 | 1x3 | 110 | 2.764 | 75 | 2.914 | 423 | 3411 | 4 |
| 750 | 61 | 0.908 | 1.144 | 90 | 1.204 | 1x2 | 125 | 3.187 | 85 | 3.357 | 507 | 4575 | 4.5 |
| 1000 | 61 | 1.117 | 1.353 | 90 | 1.413 | 1x2 | 125 | 3.638 | 85 | 3.808 | 559 | 5666 | 5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 12.6 | 1194 | 0.266 | 0.365 | 0.031 | 0.023 | 0.711+j0.588 | 0.365+j0.039 | 1723 | 135 | 157 |
| 1 | 13 | 1506 | 0.211 | 0.289 | 0.029 | 0.021 | 0.640+j0.569 | 0.289+j0.036 | 1819 | 154 | 178 |
| 1/0 | 13.6 | 1900 | 0.167 | 0.229 | 0.027 | 0.02 | 0.585+j0.548 | 0.229+j0.035 | 1933 | 176 | 202 |
| 2/0 | 14.2 | 2395 | 0.133 | 0.182 | 0.025 | 0.019 | 0.543+j0.527 | 0.182+j0.034 | 2057 | 204 | 229 |
| 3/0 | 15.3 | 3020 | 0.105 | 0.144 | 0.022 | 0.018 | 0.509+j0.503 | 0.144+j0.033 | 2203 | 234 | 260 |
| 4/0 | 16.1 | 3808 | 0.084 | 0.115 | 0.02 | 0.017 | 0.483+j0.478 | 0.115+j0.031 | 2364 | 268 | 294 |
| 250 | 17.1 | 4500 | 0.07 | 0.096 | 0.019 | 0.016 | 0.466+j0.455 | 0.096+j0.031 | 2528 | 296 | 323 |
| 350 | 18.6 | 6300 | 0.051 | 0.07 | 0.016 | 0.015 | 0.441+j0.415 | 0.070+j0.029 | 2826 | 363 | 386 |
| 500 | 20.4 | 9000 | 0.036 | 0.05 | 0.014 | 0.014 | 0.418+j0.370 | 0.050+j0.028 | 3198 | 447 | 465 |
| 750 | 23.5 | 13500 | 0.023 | 0.033 | 0.012 | 0.012 | 0.390+j0.314 | 0.033+j0.027 | 3761 | 566 | 563 |
| 1000 | 26.7 | 18000 | 0.017 | 0.025 | 0.01 | 0.011 | 0.366+j0.264 | 0.025+j0.027 | 4409 | 661 | 638 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km | kg/km | inch |
| 2 | 7 | 6.81 | 12.34 | 2.29 | 13.87 | 1x8 | 2.03 | 42.55 | 1.52 | 45.59 | 283 | 1722 | 2 |
| 1 | 19 | 7.59 | 13.13 | 2.29 | 14.66 | 1x6 | 2.03 | 44.25 | 1.52 | 47.29 | 339 | 1915 | 2.5 |
| 1/0 | 19 | 8.53 | 14.07 | 2.29 | 15.60 | 1x6 | 2.03 | 46.28 | 1.52 | 49.33 | 353 | 2097 | 2.5 |
| 2/0 | 19 | 9.55 | 15.09 | 2.29 | 16.61 | 1x6 | 2.03 | 48.49 | 1.52 | 51.54 | 368 | 2314 | 2.5 |
| 3/0 | 19 | 10.74 | 16.28 | 2.29 | 17.81 | 1x6 | 2.79 | 52.58 | 1.52 | 55.63 | 385 | 2604 | 3 |
| 4/0 | 19 | 12.07 | 17.60 | 2.29 | 19.13 | 1x6 | 2.79 | 55.42 | 1.52 | 58.47 | 405 | 2918 | 3 |
| 250 | 37 | 13.21 | 18.95 | 2.29 | 20.47 | 1x4 | 2.79 | 58.34 | 1.91 | 62.15 | 494 | 3396 | 3 |
| 350 | 37 | 15.65 | 21.39 | 2.29 | 22.91 | 1x4 | 2.79 | 63.60 | 1.91 | 67.41 | 530 | 4069 | 3.5 |
| 500 | 37 | 18.69 | 24.43 | 2.29 | 25.96 | 1x3 | 2.79 | 70.21 | 1.91 | 74.02 | 629 | 5076 | 4 |
| 750 | 61 | 23.06 | 29.06 | 2.29 | 30.58 | 1x2 | 3.18 | 80.95 | 2.16 | 85.27 | 754 | 6808 | 4.5 |
| 1000 | 61 | 28.37 | 34.37 | 2.29 | 35.89 | 1x2 | 3.18 | 92.41 | 2.16 | 96.72 | 832 | 8432 | 5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 320.04 | 5313 | 0.8727 | 1.20 | 0.0094 | 0.0755 | 0.711+j0.588 | 0.365+j0.039 | 1723 | 135 | 157 |
| 1 | 330.20 | 6702 | 0.6923 | 0.95 | 0.0088 | 0.0689 | 0.640+j0.569 | 0.289+j0.036 | 1819 | 154 | 178 |
| 1/0 | 345.44 | 8455 | 0.5479 | 0.75 | 0.0082 | 0.0656 | 0.585+j0.548 | 0.229+j0.035 | 1933 | 176 | 202 |
| 2/0 | 360.68 | 10658 | 0.4364 | 0.60 | 0.0076 | 0.0623 | 0.543+j0.527 | 0.182+j0.034 | 2057 | 204 | 229 |
| 3/0 | 388.62 | 13439 | 0.3445 | 0.47 | 0.0067 | 0.0591 | 0.509+j0.503 | 0.144+j0.033 | 2203 | 234 | 260 |
| 4/0 | 408.94 | 16946 | 0.2756 | 0.38 | 0.0061 | 0.0558 | 0.483+j0.478 | 0.115+j0.031 | 2364 | 268 | 294 |
| 250 | 434.34 | 20025 | 0.2297 | 0.31 | 0.0058 | 0.0525 | 0.466+j0.455 | 0.096+j0.031 | 2528 | 296 | 323 |
| 350 | 472.44 | 28035 | 0.1673 | 0.23 | 0.0049 | 0.0492 | 0.441+j0.415 | 0.070+j0.029 | 2826 | 363 | 386 |
| 500 | 518.16 | 40050 | 0.1181 | 0.16 | 0.0043 | 0.0459 | 0.418+j0.370 | 0.050+j0.028 | 3198 | 447 | 465 |
| 750 | 596.90 | 60075 | 0.0755 | 0.11 | 0.0037 | 0.0394 | 0.390+j0.314 | 0.033+j0.027 | 3761 | 566 | 563 |
| 1000 | 678.18 | 80100 | 0.0558 | 0.08 | 0.0030 | 0.0361 | 0.366+j0.264 | 0.025+j0.027 | 4409 | 661 | 638 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
Revision: 1.000.003
Updated On: May 1, 2025, 7:39 p.m. UTC