SPEC 26162

HVTECK AL 3/C 115NLEPR TS PVC AIA PVC 5kV 133% CSA

3 Conductor, 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 115 NLEPR AIA 5kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchAWGmilinchmilinchlb/1000ft
    270.2680.5361150.5968801.847601.9671499
    1190.2980.5661150.6266801.911602.0311625
    1/0190.3360.6041150.6646801.993602.1131776
    2/0190.3760.6441150.70461102.140602.2602072
    3/0190.4220.6901150.75061102.239602.3592284
    4/0190.4740.7421150.80261102.352752.5022613
    250370.5200.7961150.85641102.468752.6182886
    350370.6150.8911150.95141102.673752.8233419
    500370.7351.0111151.07131102.933753.0834185
    750610.9081.1941151.25421253.358853.5285606
    1000611.0601.3461151.40621253.686853.8566770
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    213.811940.2670.3360.0300.0410.705 + j0.5240.336 + j0.0411877135157
    114.215060.2110.2660.0300.0390.637 + j0.5040.266 + j0.0381970154178
    1/014.819000.1680.2110.0300.0380.584 + j0.4830.211 + j0.0372088176202
    2/015.823950.1330.1670.0300.0370.542 + j0.4620.167 + j0.0352212204229
    3/016.530200.1050.1330.0200.0350.509 + j0.4380.133 + j0.0342354234260
    4/017.538080.0840.1050.0200.0300.548 + j0.4140.105 + j0.0332515268294
    25018.345000.0710.0900.0200.0300.464 + j0.3900.090 + j0.0322683296323
    35019.863000.0500.0650.0200.0300.434 + j0.3530.065 + j0.0312977363386
    50021.690000.0350.0460.0140.0300.406 + j0.3120.046 + j0.0293349447465
    75024.7135000.0200.0300.0120.0300.376 + j0.2610.033 + j0.0283916566563
    100027.0180000.0200.0300.0110.0300.354 + j0.2270.027 + j0.0274387661638
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmAWGmmmmmmmmkg/km
    276.8113.612.9215.1482.0346.911.5249.962231
    1197.5714.382.9215.9062.0348.541.5251.592418
    1/0198.5315.342.9216.8762.0350.621.5253.672643
    2/0199.5516.362.9217.8862.7954.361.5257.403083
    3/01910.7217.532.9219.0562.7956.871.5259.923399
    4/01912.0418.852.9220.3762.7959.741.9163.553889
    2503713.2120.222.9221.7442.7962.691.9166.504295
    3503715.6222.632.9224.1642.7967.891.9171.705088
    5003718.6725.682.9227.2032.7974.501.9178.316228
    7506123.0630.332.9231.8523.1885.292.1689.618343
    10006126.9234.192.9235.7123.1893.622.1697.9410075
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2350.5253130.87601.100.00910.13450.705 + j0.5240.336 + j0.0411877135157
    1360.6867020.69230.870.00910.12800.637 + j0.5040.266 + j0.0381970154178
    1/0375.9284550.55120.690.00910.12470.584 + j0.4830.211 + j0.0372088176202
    2/0401.32106580.43640.550.00910.12140.542 + j0.4620.167 + j0.0352212204229
    3/0419.10134390.34450.440.00610.11480.509 + j0.4380.133 + j0.0342354234260
    4/0444.50169460.27560.340.00610.09840.548 + j0.4140.105 + j0.0332515268294
    250464.82200250.23290.300.00610.09840.464 + j0.3900.090 + j0.0322683296323
    350502.92280350.16400.210.00610.09840.434 + j0.3530.065 + j0.0312977363386
    500548.64400500.11480.150.00430.09840.406 + j0.3120.046 + j0.0293349447465
    750627.38600750.06560.100.00370.09840.376 + j0.2610.033 + j0.0283916566563
    1000685.80801000.06560.100.00340.09840.354 + j0.2270.027 + j0.0274387661638
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC