SPEC 26125

HVTECK AL 1/C 90NLEPR CB PVC AIA PVC 5kV 100% CSA

Single Conductor, 90 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:90 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 90 NLEPR AIA 5kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ftlb/1000ftinch
    270.2680.486900.5465x12801.206501.3061269043.5
    1190.2990.517900.5775x12801.237501.3371299503.5
    1/0190.3360.554900.6145x12801.274501.37413210063.5
    2/0190.3760.594900.6547x12801.314501.41418311213.5
    3/0190.4230.641900.7017x12801.361501.46118712004
    4/0190.4750.693900.7537x12801.413501.51319112924
    250370.520.746900.8069x12801.566601.68623315964.5
    350370.6160.842900.90211x12801.662601.78227918344.5
    500370.7360.962901.02213x12801.782601.90234321635
    750610.9081.144901.20417x12801.964602.08442526765.5
    1000611.1171.353901.41317x121102.233602.35344232676
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    29.13980.2660.3650.0240.0580.667+j0.1910.369+j0.0632770169176
    19.45020.2110.2890.0220.0560.591+j0.1880.292+j0.0602770194198
    1/09.66330.1670.2290.020.0540.530+j0.1870.232+j0.0582770222223
    2/09.97980.1330.1820.0190.0520.427+j0.1180.186+j0.0553879255250
    3/010.210060.1050.1440.0170.050.388+j0.1170.148+j0.0543879290278
    4/010.612690.0840.1150.0160.0480.359+j0.1160.119+j0.0523879329309
    25011.815000.070.0960.0140.0490.298+j0.0810.102+j0.0524987370347
    35012.521000.0510.070.0130.0460.241+j0.0600.076+j0.0496095446402
    50013.330000.0360.050.0110.0440.197+j0.0470.057+j0.0467203533451
    75014.645000.0230.0330.0090.0410.148+j0.0320.041+j0.0429420631500
    100016.560000.0170.0250.0070.0390.140+j0.0330.033+j0.0429420707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/kmkg/kminch
    276.8112.342.2913.875x122.0330.631.2733.1718813453.5
    1197.5913.132.2914.665x122.0331.421.2733.9619214143.5
    1/0198.5314.072.2915.605x122.0332.361.2734.9019614973.5
    2/0199.5515.092.2916.617x122.0333.381.2735.9227216683.5
    3/01910.7416.282.2917.817x122.0334.571.2737.1127817864
    4/01912.0717.602.2919.137x122.0335.891.2738.4328419234
    2503713.2118.952.2920.479x122.0339.781.5242.8234723754.5
    3503715.6521.392.2922.9111x122.0342.211.5245.2641527294.5
    5003718.6924.432.2925.9613x122.0345.261.5248.3151032195
    7506123.0629.062.2930.5817x122.0349.891.5252.9363239825.5
    10006128.3734.372.2935.8917x122.7956.721.5259.7765848626
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2231.1417710.87271.200.00730.19030.667+j0.1910.369+j0.0632770169176
    1238.7622340.69230.950.00670.18370.591+j0.1880.292+j0.0602770194198
    1/0243.8428170.54790.750.00610.17720.530+j0.1870.232+j0.0582770222223
    2/0251.4635510.43640.600.00580.17060.427+j0.1180.186+j0.0553879255250
    3/0259.0844770.34450.470.00520.16400.388+j0.1170.148+j0.0543879290278
    4/0269.2456470.27560.380.00490.15750.359+j0.1160.119+j0.0523879329309
    250299.7266750.22970.310.00430.16080.298+j0.0810.102+j0.0524987370347
    350317.5093450.16730.230.00400.15090.241+j0.0600.076+j0.0496095446402
    500337.82133500.11810.160.00340.14440.197+j0.0470.057+j0.0467203533451
    750370.84200250.07550.110.00270.13450.148+j0.0320.041+j0.0429420631500
    1000419.10267000.05580.080.00210.12800.140+j0.0330.033+j0.0429420707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC