SPEC 26112
HVTECK CU 1/C 115TRXLPE TS PVC AIA PVC 5kV 133% CSA
Single Conductor, 115 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:115 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 115 TRXLPE AIA 5kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch | |
| TBA | 2 | 7 | 0.283 | 0.551 | 115 | 0.611 | 65 | 0.971 | 50 | 1.071 | 255 | 717 | 2.5 |
| TBA | 1 | 19 | 0.322 | 0.59 | 115 | 0.65 | 65 | 1.01 | 50 | 1.11 | 312 | 800 | 3 |
| TBA | 1/0 | 19 | 0.362 | 0.63 | 115 | 0.69 | 80 | 1.08 | 50 | 1.18 | 383 | 929 | 3 |
| TBA | 2/0 | 19 | 0.405 | 0.673 | 115 | 0.733 | 80 | 1.123 | 50 | 1.223 | 471 | 1048 | 3 |
| TBA | 3/0 | 19 | 0.456 | 0.724 | 115 | 0.784 | 80 | 1.174 | 50 | 1.274 | 583 | 1196 | 3 |
| TBA | 4/0 | 19 | 0.512 | 0.78 | 115 | 0.84 | 80 | 1.23 | 50 | 1.33 | 722 | 1374 | 3.5 |
| TBA | 250 | 37 | 0.558 | 0.834 | 115 | 0.894 | 80 | 1.284 | 50 | 1.384 | 846 | 1541 | 3.5 |
| TBA | 350 | 37 | 0.661 | 0.937 | 115 | 0.997 | 80 | 1.387 | 50 | 1.487 | 1163 | 1931 | 4 |
| 137803 | 500 | 37 | 0.789 | 1.042 | 115 | 1.102 | 80 | 1.614 | 60 | 1.734 | 1638 | 2502 | 4.5 |
| TBA | 500 | 37 | 0.789 | 1.065 | 115 | 1.125 | 80 | 1.615 | 60 | 1.735 | 1637 | 2675 | 4.5 |
| TBA | 750 | 61 | 0.968 | 1.254 | 115 | 1.314 | 80 | 1.804 | 60 | 1.924 | 2424 | 3625 | 5 |
| TBA | 1000 | 61 | 1.117 | 1.403 | 115 | 1.463 | 80 | 1.953 | 60 | 2.073 | 3208 | 4533 | 5.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 7.5 | 530 | 0.162 | 0.221 | 0.037 | 0.052 | 0.556+j0.543 | 0.222+j0.059 | 1924 | 215 | 221 |
| 1 | 7.8 | 669 | 0.128 | 0.175 | 0.034 | 0.05 | 0.516+j0.523 | 0.176+j0.056 | 2045 | 245 | 247 |
| 1/0 | 8.3 | 844 | 0.102 | 0.139 | 0.031 | 0.049 | 0.483+j0.503 | 0.140+j0.054 | 2169 | 278 | 275 |
| 2/0 | 8.6 | 1064 | 0.082 | 0.112 | 0.028 | 0.047 | 0.460+j0.484 | 0.113+j0.053 | 2302 | 317 | 306 |
| 3/0 | 8.9 | 1342 | 0.064 | 0.087 | 0.026 | 0.045 | 0.438+j0.461 | 0.088+j0.051 | 2460 | 357 | 335 |
| 4/0 | 9.3 | 1692 | 0.051 | 0.07 | 0.024 | 0.044 | 0.424+j0.438 | 0.071+j0.049 | 2634 | 404 | 369 |
| 250 | 9.7 | 2000 | 0.043 | 0.059 | 0.022 | 0.043 | 0.414+j0.417 | 0.060+j0.048 | 2801 | 456 | 412 |
| 350 | 10.4 | 2800 | 0.031 | 0.043 | 0.019 | 0.04 | 0.397+j0.380 | 0.044+j0.046 | 3120 | 537 | 456 |
| 500 | 12.1 | 4000 | 0.021 | 0.03 | 0.015 | 0.04 | 0.379+j0.345 | 0.031+j0.045 | 3445 | 616 | 497 |
| 500 | 12.1 | 4000 | 0.021 | 0.03 | 0.017 | 0.04 | 0.379+j0.339 | 0.031+j0.045 | 3517 | 616 | 497 |
| 750 | 13.5 | 6000 | 0.014 | 0.021 | 0.014 | 0.037 | 0.359+j0.289 | 0.022+j0.043 | 4102 | 706 | 551 |
| 1000 | 14.5 | 8000 | 0.011 | 0.018 | 0.012 | 0.036 | 0.346+j0.256 | 0.020+j0.041 | 4564 | 813 | 596 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | mm | mm | mm | mm | kg/km | kg/km | inch | |
| TBA | 2 | 7 | 7.19 | 14.00 | 2.92 | 15.52 | 1.65 | 24.66 | 1.27 | 27.20 | 379 | 1067 | 2.5 |
| TBA | 1 | 19 | 8.18 | 14.99 | 2.92 | 16.51 | 1.65 | 25.65 | 1.27 | 28.19 | 464 | 1191 | 3 |
| TBA | 1/0 | 19 | 9.19 | 16.00 | 2.92 | 17.53 | 2.03 | 27.43 | 1.27 | 29.97 | 570 | 1383 | 3 |
| TBA | 2/0 | 19 | 10.29 | 17.09 | 2.92 | 18.62 | 2.03 | 28.52 | 1.27 | 31.06 | 701 | 1560 | 3 |
| TBA | 3/0 | 19 | 11.58 | 18.39 | 2.92 | 19.91 | 2.03 | 29.82 | 1.27 | 32.36 | 868 | 1780 | 3 |
| TBA | 4/0 | 19 | 13.00 | 19.81 | 2.92 | 21.34 | 2.03 | 31.24 | 1.27 | 33.78 | 1074 | 2045 | 3.5 |
| TBA | 250 | 37 | 14.17 | 21.18 | 2.92 | 22.71 | 2.03 | 32.61 | 1.27 | 35.15 | 1259 | 2293 | 3.5 |
| TBA | 350 | 37 | 16.79 | 23.80 | 2.92 | 25.32 | 2.03 | 35.23 | 1.27 | 37.77 | 1731 | 2874 | 4 |
| 137803 | 500 | 37 | 20.04 | 26.47 | 2.92 | 27.99 | 2.03 | 41.00 | 1.52 | 44.04 | 2438 | 3723 | 4.5 |
| TBA | 500 | 37 | 20.04 | 27.05 | 2.92 | 28.58 | 2.03 | 41.02 | 1.52 | 44.07 | 2436 | 3981 | 4.5 |
| TBA | 750 | 61 | 24.59 | 31.85 | 2.92 | 33.38 | 2.03 | 45.82 | 1.52 | 48.87 | 3607 | 5395 | 5 |
| TBA | 1000 | 61 | 28.37 | 35.64 | 2.92 | 37.16 | 2.03 | 49.61 | 1.52 | 52.65 | 4774 | 6746 | 5.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 190.50 | 2359 | 0.5315 | 0.73 | 0.0113 | 0.1706 | 0.556+j0.543 | 0.222+j0.059 | 1924 | 215 | 221 |
| 1 | 198.12 | 2977 | 0.4199 | 0.57 | 0.0104 | 0.1640 | 0.516+j0.523 | 0.176+j0.056 | 2045 | 245 | 247 |
| 1/0 | 210.82 | 3756 | 0.3346 | 0.46 | 0.0094 | 0.1608 | 0.483+j0.503 | 0.140+j0.054 | 2169 | 278 | 275 |
| 2/0 | 218.44 | 4735 | 0.2690 | 0.37 | 0.0085 | 0.1542 | 0.460+j0.484 | 0.113+j0.053 | 2302 | 317 | 306 |
| 3/0 | 226.06 | 5972 | 0.2100 | 0.29 | 0.0079 | 0.1476 | 0.438+j0.461 | 0.088+j0.051 | 2460 | 357 | 335 |
| 4/0 | 236.22 | 7529 | 0.1673 | 0.23 | 0.0073 | 0.1444 | 0.424+j0.438 | 0.071+j0.049 | 2634 | 404 | 369 |
| 250 | 246.38 | 8900 | 0.1411 | 0.19 | 0.0067 | 0.1411 | 0.414+j0.417 | 0.060+j0.048 | 2801 | 456 | 412 |
| 350 | 264.16 | 12460 | 0.1017 | 0.14 | 0.0058 | 0.1312 | 0.397+j0.380 | 0.044+j0.046 | 3120 | 537 | 456 |
| 500 | 307.34 | 17800 | 0.0689 | 0.10 | 0.0046 | 0.1312 | 0.379+j0.345 | 0.031+j0.045 | 3445 | 616 | 497 |
| 500 | 307.34 | 17800 | 0.0689 | 0.10 | 0.0052 | 0.1312 | 0.379+j0.339 | 0.031+j0.045 | 3517 | 616 | 497 |
| 750 | 342.90 | 26700 | 0.0459 | 0.07 | 0.0043 | 0.1214 | 0.359+j0.289 | 0.022+j0.043 | 4102 | 706 | 551 |
| 1000 | 368.30 | 35600 | 0.0361 | 0.06 | 0.0037 | 0.1181 | 0.346+j0.256 | 0.020+j0.041 | 4564 | 813 | 596 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Revision: 1.000.000
Updated On: Dec. 31, 2024, 11:07 p.m. UTC