SPEC 70066

600V SEOPRENE® SEOOW Power Cord with Black Jacket 105°C. Silicone-Free

600 Volt Cord. -50°C to maximum 105°C, Power Sizes, High Degree of Flexibility, Premium Oil Resistance, Sunlight, Water Resistance and Flame Retardant, UL/CSA Listed

...

Construction:

  1. Conductor:Class K stranded bare copper per ASTM B-174
  2. Insulation:Heat, moisture and oil resistant TPE
  3. Filler:Non-wicking polypropylene fillers, with a tissue-paper separator wrapped around the assembly
  4. Jacket:Black TPE (other colors available upon request)

Applications and Features:

Southwire Type SEOOW Flexible Cords are permitted for Indoor and outdoor temporary power uses, portable industrial machinery and compressors, food processing and washdown facilities. Type SEOOW Cords are suitable for use in temperatures between -50°C to maximum 105°C.

Specifications:

  • UL 62 Flexible Cords and Cables
  • CSA C22.2 No. 49 Flexible Cords and Cables
  • Passes CSA FT2 Flame Test
  • RoHS-3 Complies with European Directive 2015/863
  • NEC Article 400 Flexible Cords, Cables and Fixture Wire
  • NEC Article 501.140 Class I Division 2
  • Sample Print Legend:

    SOUTHWIRE{R} SEOPRENE{R} CORD X/C X AWG (XX.XX{mm2}) SEOOW E46194 {UL} 600V -50{D}C TO 105{D}C -- CSA LL90458 SEOOW 600V -50{D}C TO 105{D}C FT2 WATER RESISTANT

    Packaging:

    Standard lengths: 250', 500' and 1,000' reels. Other lengths available upon request.
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacityDC ResistanceInsul. ColorJacket Color
    AWG/KcmilNo.No.milmilinchlb/1000ftAmpΩ/1000ft
    5504661632630650.39781104.181BK,WE,GNWE
    59832783133601100.854404350.708BK,WE,GNBK
    59832884133601300.952526280.708BK,WE,RD,GNBK
    58693963133601451602450.446GN,WE,BKBK
    59832964133601401.074734360.446BK,WE,RD,GNBK
    59833244133601701.281079480.279BK,WE,RD,GNBK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *DC ResistanceInsul. ColorJacket Color
    AWG/KcmilNo.No.mmmmmmkg/kmAmpΩ/km
    550466163260.761.6510.081211013.72BK,WE,GNWE
    598327831331.522.7921.69601352.32BK,WE,GNBK
    598328841331.523.3024.18783282.32BK,WE,RD,GNBK
    586939631331.523.6825.40896451.46GN,WE,BKBK
    598329641331.523.5627.281092361.46BK,WE,RD,GNBK
    598332441331.524.3232.511606480.92BK,WE,RD,GNBK
    * Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.

    Revision: 1.000.004

    Updated On: May 6, 2025, 9:25 p.m. UTC