SPEC 70000

600V ROYAL® SOOW Cord with Black Jacket 90°C. MSHA Approved

600 Volt 90°C Flexible Cord. Heat, Moisture and Oil Resistant EPDM Rubber Insulation, Heat, Moisture and Oil Resistant Flexible CPE Jacket.

...

Construction:

  1. Conductor:Class K stranded bare copper per ASTM B-174
  2. Insulation:Heat, moisture and oil resistant EPDM
  3. Filler:Waxed paper or rubber fillers, with a full cotton serve or paper separator wrapped around the assembly
  4. Jacket:Heat, moisture and oil resistant flexible black CPE jacket

Applications and Features:

Southwire Type SOOW Flexible Cords UL/ CSA listed are permitted for use as specified by Article 400 and related articles of the 2014 National Electrical Code. The cable is rated -40°C to 90°C, water, oil, and weather resistant. Southwire Type SOOW Flexible Cords are designed for extra hard usage on industrial equipment, heavy tools, battery chargers, portable lights, welding leads, marine dockside power, power extensions and mining applications.

Specifications:

  • UL 62 Flexible Cords and Cables
  • CSA C22.2 No. 49 Flexible Cords and Cables
  • MSHA Approved
  • MSHA flame test - P07-KA070018-1MSHA
  • Passes CSA FT2 Flame Test
  • RoHS-3 Complies with European Directive 2015/863
  • NEC Article 400 Flexible Cords, Cables and Fixture Wire
  • Federal Specification J-C-580B
  • Sample Print Legend:

    SOUTHWIRE® ROYAL® CORD X/C X AWG (XX.X{mm2}) SOOW E46194 {UL} 600V -40°C TO 90°C -- {CSA} LL90458 SOOW 600V -40°C TO 90°C FT2 WATER RESISTANT {NOM}-ANCE -- {MSHA}

    Packaging:

    Standard lengths: 250', 500' and 1,000' reels. Other lengths available upon request.
    Table 1 – Weights and Measurements
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacityInsul. ColorJacket Color
    AWG/KcmilNo.No.milmilinchlb/1000ftAmp
    5581408222251821630700.3486710BK,WEBK
    5581428223251831630700.370807BK,WE,GNBK
    5581438224251841630700.390955BK,WE,RD,GNBK
    5582358305051851630950.4651345BK,WE,RD,GN,OEBK
    5600188222261622630700.3707613BK,WEBK
    5581008223261632630700.3959410BK,WE,GNBK
    5581018224261642630650.4201118BK,WE,RD,GNBK
    5582318305061652630950.5141628BK,WE,RD,GN,OEBK
    5581388222271424145850.50113218BK,WEBK
    5580998223271434145900.53016515BK,WE,GNBK
    5581028224271444145900.57020112BK,WE,RD,GNBK
    55814783050714541451050.65525412BK,WE,RD,GN,OEBK
    55813982222812265451050.58018225BK,WEBK
    585842-12365451150.60522120GN,WE,BKBK
    55809482232812365451150.60622420BK,WE,GNBK
    55809582242812465451050.64426616BK,WE,RD,GNBK
    55810483050812565451000.70929516BK,WE,RD,GN,OEBK
    558141822229102104451050.63022230BK,WEBK
    558097822329103104451200.66529525BK,WE,GNBK
    558096822429104104451050.71534720BK,WE,RD,GNBK
    558103830509105104451200.77244420BK,WE,RD,GN,OEBK
    56003982231683133601250.84842635BK,WE,GNBK
    631387-83133601250.84944435BK,RD,GNBK
    63072682259184133601550.95459628BK,WE,RD,GNBK
    59696182254085133601651.03671728BK,WE,RD,GN,OEBK
    56004182239163133601950.99067545BK,WE,GNBK
    56004282258964133602051.07583036BK,WE,RD,GNBK
    56206882239265133602151.192103636BK,WE,RD,GN,OEBK
    57005482260143427601751.13788960BK,WE,GNBK
    56092582247144427601651.257115248BK,WE,RD,GNBK
    56206782254245427601851.395144648BK,WE,RD,GN,OEBK
    56092882249124168602051.480170664BK,WE,RD,GNBK
    56206582249225168602551.716206464BK,WE,RD,GN,OEBK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.
    ! Orange jacket
    ^ Color sequence: black, red, green
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *Insul. ColorJacket Color
    AWG/KcmilNo.No.mmmmmmkg/kmAmp
    558140822225182160.761.788.8410010BK,WEBK
    558142822325183160.761.789.401197BK,WE,GNBK
    558143822425184160.761.789.911415BK,WE,RD,GNBK
    558235830505185160.762.4111.811995BK,WE,RD,GN,OEBK
    560018822226162260.761.789.4011313BK,WEBK
    558100822326163260.761.7810.0314010BK,WE,GNBK
    558101822426164260.761.6510.671658BK,WE,RD,GNBK
    558231830506165260.762.4113.062418BK,WE,RD,GN,OEBK
    558138822227142411.142.1612.7319618BK,WEBK
    558099822327143411.142.2913.4624615BK,WE,GNBK
    558102822427144411.142.2914.4829912BK,WE,RD,GNBK
    558147830507145411.142.6716.6437812BK,WE,RD,GN,OEBK
    558139822228122651.142.6714.7327125BK,WEBK
    585842-123651.142.9215.3732920GN,WE,BKBK
    558094822328123651.142.9215.3933320BK,WE,GNBK
    558095822428124651.142.6716.3639616BK,WE,RD,GNBK
    558104830508125651.142.5418.0143916BK,WE,RD,GN,OEBK
    5581418222291021041.142.6716.0033030BK,WEBK
    5580978223291031041.143.0516.8943925BK,WE,GNBK
    5580968224291041041.142.6718.1651620BK,WE,RD,GNBK
    5581038305091051041.143.0519.6166120BK,WE,RD,GN,OEBK
    560039822316831331.523.1821.5463435BK,WE,GNBK
    631387-831331.523.1821.5666135BK,RD,GNBK
    630726822591841331.523.9424.2388728BK,WE,RD,GNBK
    596961822540851331.524.1926.31106728BK,WE,RD,GN,OEBK
    560041822391631331.524.9525.15100545BK,WE,GNBK
    560042822589641331.525.2127.30123536BK,WE,RD,GNBK
    562068822392651331.525.4630.28154236BK,WE,RD,GN,OEBK
    570054822601434271.524.4428.88132360BK,WE,GNBK
    560925822471444271.524.1931.93171448BK,WE,RD,GNBK
    562067822542454271.524.7035.43215248BK,WE,RD,GN,OEBK
    560928822491241681.525.2137.59253964BK,WE,RD,GNBK
    562065822492251681.526.4843.59307264BK,WE,RD,GN,OEBK
    * Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.

    Revision: 1.000.004

    Updated On: Aug. 30, 2024, 9:23 p.m. UTC