SPEC 45410
AL 2000V XLPE Insulation. RHH/RHW-2 PV
Single Conductor Photovoltaic (Type PV) Power Cable 2000 Volt Aluminum Conductor XLPE Insulation. Sizes 6AWG through 1000 kcmil. Heat, Moisture, and Sunlight Resistant RoHS. 90°C
![...](https://d3sx0rvep9h73z.cloudfront.net/cable_image/SPEC45410.png)
Construction:
- Conductor:AlumaFlex® Compact Stranded Aluminum Alloy (AA-8176)
- Insulation: Cross-linked Polyethylene (XLPE)
Applications and Features:
The cable is available in sizes 6 AWG through 1000 kcmil. The product is approved for use in solar power applications per the NEC article 690 and is rated 90°C for exposed or concealed wiring in wet or dry locations. Individual conductors are stranded aluminum alloy covered with a cross-linked polyethylene (XLPE) insulation and is rated for direct burial. The cable is sunlight resistant, oil resistant PRI and PRII, RoHS compliant, passes -40°C cold bend.
Specifications:
Sample Print Legend:
SOUTHWIRE E316464 {UL} PV WIRE XXX KCMIL (XXX.XXX{mm2}) COMPACT AL. --- AlumaFlex® AA8176 2000V 90°C WET OR DRY -40°C SUN RES DIRECT BURIAL OR RHH-RHW-2 2000V --- RoHS {MMM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Approx. OD | Aluminum Weight | Approx. Weight |
---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | inch | lb/1000ft | lb/1000ft | |
585843 | 6 | 7 | 0.169 | 85 | 0.349 | 24 | 59 |
586673 | 4 | 7 | 0.212 | 85 | 0.383 | 39 | 77 |
586672 | 2 | 6 | 0.268 | 85 | 0.438 | 62 | 104 |
589171 | 2 | 6 | 0.268 | 85 | 0.438 | 62 | 104 |
619879 | 1 | 8 | 0.298 | 105 | 0.519 | 78 | 146 |
589051 | 1 | 8 | 0.298 | 105 | 0.519 | 78 | 146 |
591256 | 1/0 | 10 | 0.336 | 105 | 0.546 | 99 | 164 |
591241 | 1/0 | 10 | 0.336 | 105 | 0.546 | 99 | 164 |
583673 | 2/0 | 12 | 0.376 | 105 | 0.586 | 125 | 195 |
577100 | 3/0 | 16 | 0.422 | 105 | 0.633 | 158 | 235 |
669515 | 3/0 | 16 | 0.422 | 105 | 0.633 | 158 | 235 |
669518 | 3/0 | 16 | 0.422 | 105 | 0.633 | 158 | 235 |
669516 | 3/0 | 16 | 0.422 | 105 | 0.633 | 158 | 235 |
577843 | 3/0 | 16 | 0.422 | 105 | 0.633 | 158 | 235 |
669517 | 3/0 | 16 | 0.422 | 105 | 0.633 | 158 | 235 |
583678 | 4/0 | 19 | 0.474 | 105 | 0.685 | 199 | 284 |
591242 | 4/0 | 19 | 0.474 | 105 | 0.685 | 199 | 284 |
607400 | 4/0 | 19 | 0.474 | 105 | 0.685 | 199 | 284 |
597698 | 4/0 | 19 | 0.474 | 105 | 0.685 | 199 | 284 |
577101 | 250 | 22 | 0.520 | 120 | 0.760 | 235 | 350 |
668535 | 250 | 22 | 0.520 | 120 | 0.760 | 235 | 350 |
577844 | 250 | 22 | 0.520 | 120 | 0.760 | 235 | 350 |
584290 | 300 | 21 | 0.569 | 120 | 0.810 | 282 | 397 |
675225 | 300 | 21 | 0.569 | 120 | 0.810 | 282 | 397 |
589170 | 300 | 21 | 0.569 | 120 | 0.810 | 282 | 397 |
582174 | 350 | 35 | 0.615 | 120 | 0.856 | 329 | 462 |
592618 | 350 | 35 | 0.615 | 120 | 0.856 | 329 | 462 |
597996 | 350 | 35 | 0.615 | 120 | 0.856 | 329 | 462 |
584291 | 400 | 35 | 0.659 | 120 | 0.899 | 376 | 518 |
652801 | 400 | 35 | 0.659 | 120 | 0.899 | 376 | 518 |
596689 | 400 | 35 | 0.659 | 120 | 0.899 | 376 | 518 |
582267 | 500 | 34 | 0.735 | 120 | 0.978 | 471 | 615 |
591243 | 500 | 34 | 0.735 | 120 | 0.978 | 471 | 615 |
591246 | 500 | 34 | 0.735 | 120 | 0.978 | 471 | 615 |
591244 | 500 | 34 | 0.735 | 120 | 0.978 | 471 | 615 |
588797 | 500 | 34 | 0.735 | 120 | 0.978 | 471 | 615 |
586671 | 500 | 34 | 0.735 | 120 | 0.978 | 471 | 615 |
591245 | 500 | 34 | 0.735 | 120 | 0.978 | 471 | 615 |
585499 | 600 | 37 | 0.812 | 135 | 1.083 | 565 | 745 |
588799 | 600 | 37 | 0.812 | 135 | 1.083 | 565 | 745 |
591247 | 600 | 37 | 0.812 | 135 | 1.083 | 565 | 745 |
586013 | 750 | 61 | 0.908 | 135 | 1.178 | 706 | 904 |
592619 | 750 | 61 | 0.908 | 135 | 1.178 | 706 | 904 |
589375 | 750 | 61 | 0.908 | 135 | 1.178 | 706 | 904 |
641387 | 1000 | 58 | 1.060 | 135 | 1.330 | 942 | 1168 |
641386 | 1000 | 58 | 1.060 | 135 | 1.330 | 942 | 1168 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | |
585843 | 6 | 1.4 | 157 | 0.674 | 0.812 | 0.051 | 50 | 55 |
586673 | 4 | 1.5 | 250 | 0.424 | 0.510 | 0.048 | 65 | 75 |
586672 | 2 | 1.8 | 398 | 0.267 | 0.321 | 0.045 | 90 | 100 |
589171 | 2 | 1.8 | 398 | 0.267 | 0.321 | 0.045 | 90 | 100 |
619879 | 1 | 2.1 | 502 | 0.211 | 0.254 | 0.046 | 100 | 115 |
589051 | 1 | 2.1 | 502 | 0.211 | 0.254 | 0.046 | 100 | 115 |
591256 | 1/0 | 2.2 | 633 | 0.168 | 0.201 | 0.044 | 120 | 135 |
591241 | 1/0 | 2.2 | 633 | 0.168 | 0.201 | 0.044 | 120 | 135 |
583673 | 2/0 | 2.3 | 798 | 0.133 | 0.160 | 0.043 | 135 | 150 |
577100 | 3/0 | 2.5 | 1006 | 0.105 | 0.126 | 0.042 | 155 | 175 |
669515 | 3/0 | 2.5 | 1006 | 0.105 | 0.126 | 0.042 | 155 | 175 |
669518 | 3/0 | 2.5 | 1006 | 0.105 | 0.126 | 0.042 | 155 | 175 |
669516 | 3/0 | 2.5 | 1006 | 0.105 | 0.126 | 0.042 | 155 | 175 |
577843 | 3/0 | 2.5 | 1006 | 0.105 | 0.126 | 0.042 | 155 | 175 |
669517 | 3/0 | 2.5 | 1006 | 0.105 | 0.126 | 0.042 | 155 | 175 |
583678 | 4/0 | 2.7 | 1269 | 0.084 | 0.100 | 0.041 | 180 | 205 |
591242 | 4/0 | 2.7 | 1269 | 0.084 | 0.100 | 0.041 | 180 | 205 |
607400 | 4/0 | 2.7 | 1269 | 0.084 | 0.100 | 0.041 | 180 | 205 |
597698 | 4/0 | 2.7 | 1269 | 0.084 | 0.100 | 0.041 | 180 | 205 |
577101 | 250 | 3.0 | 1500 | 0.071 | 0.086 | 0.041 | 205 | 230 |
668535 | 250 | 3.0 | 1500 | 0.071 | 0.086 | 0.041 | 205 | 230 |
577844 | 250 | 3.0 | 1500 | 0.071 | 0.086 | 0.041 | 205 | 230 |
584290 | 300 | 3.2 | 1800 | 0.059 | 0.071 | 0.041 | 230 | 260 |
675225 | 300 | 3.2 | 1800 | 0.059 | 0.071 | 0.041 | 230 | 260 |
589170 | 300 | 3.2 | 1800 | 0.059 | 0.071 | 0.041 | 230 | 260 |
582174 | 350 | 3.4 | 2100 | 0.050 | 0.062 | 0.040 | 250 | 280 |
592618 | 350 | 3.4 | 2100 | 0.050 | 0.062 | 0.040 | 250 | 280 |
597996 | 350 | 3.4 | 2100 | 0.050 | 0.062 | 0.040 | 250 | 280 |
584291 | 400 | 3.6 | 2400 | 0.044 | 0.054 | 0.040 | 270 | 305 |
652801 | 400 | 3.6 | 2400 | 0.044 | 0.054 | 0.040 | 270 | 305 |
596689 | 400 | 3.6 | 2400 | 0.044 | 0.054 | 0.040 | 270 | 305 |
582267 | 500 | 3.9 | 3000 | 0.035 | 0.044 | 0.039 | 310 | 350 |
591243 | 500 | 3.9 | 3000 | 0.035 | 0.044 | 0.039 | 310 | 350 |
591246 | 500 | 3.9 | 3000 | 0.035 | 0.044 | 0.039 | 310 | 350 |
591244 | 500 | 3.9 | 3000 | 0.035 | 0.044 | 0.039 | 310 | 350 |
588797 | 500 | 3.9 | 3000 | 0.035 | 0.044 | 0.039 | 310 | 350 |
586671 | 500 | 3.9 | 3000 | 0.035 | 0.044 | 0.039 | 310 | 350 |
591245 | 500 | 3.9 | 3000 | 0.035 | 0.044 | 0.039 | 310 | 350 |
585499 | 600 | 5.4 | 3600 | 0.029 | 0.037 | 0.039 | 340 | 385 |
588799 | 600 | 5.4 | 3600 | 0.029 | 0.037 | 0.039 | 340 | 385 |
591247 | 600 | 5.4 | 3600 | 0.029 | 0.037 | 0.039 | 340 | 385 |
586013 | 750 | 5.9 | 4500 | 0.024 | 0.031 | 0.038 | 385 | 435 |
592619 | 750 | 5.9 | 4500 | 0.024 | 0.031 | 0.038 | 385 | 435 |
589375 | 750 | 5.9 | 4500 | 0.024 | 0.031 | 0.038 | 385 | 435 |
641387 | 1000 | 6.7 | 6000 | 0.018 | 0.025 | 0.037 | 445 | 500 |
641386 | 1000 | 6.7 | 6000 | 0.018 | 0.025 | 0.037 | 445 | 500 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.
Stock Codes and Colors
Size | Black | Brown | Orange | Yellow | White | Red | Green |
---|---|---|---|---|---|---|---|
AWG/Kcmil | ![]() | ![]() | ![]() | ![]() | ![]() | ![]() | ![]() |
6 | 585843 | ||||||
4 | 586673 | ||||||
2 | 586672 | 589171 | |||||
1 | 619879 | 589051 | |||||
1/0 | 591256 | 591241 | |||||
2/0 | 583673 | ||||||
3/0 | 577100 | 669515 | 669516 | 669517 | 577843 | 669518 | |
4/0 | 583678 | 597698 | 607400 | 591242 | |||
250 | 577101 | 577844 | 668535 | ||||
300 | 584290 | 589170 | 675225 | ||||
350 | 582174 | 597996 | 592618 | ||||
400 | 584291 | 596689 | 652801 | ||||
500 | 582267 | 591243 | 591244 | 591245 | 586671 | 588797 | 591246 |
600 | 585499 | 591247 | 588799 | ||||
750 | 586013 | 589375 | 592619 | ||||
1000 | 641387 | 641386 |
Revision: 1.000.006
Updated On: Dec. 31, 2024, 11:07 p.m. UTC