SPEC 45311

AL 600/1000V XLPE Insulation AIA PVC Jacket XHHW-2. CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free

Type MC Power Cable 600Volt Three Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free.

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polypropylene tape
  6. Armor:Aluminum Interlocked Armor (AIA)
  7. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Silicone Free.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    {SQFTG_DUAL} SOUTHWIRE {UL} E96627 3/C XXX KCMIL COMPACT AL.--- {ALUMAFLEX}® AA8176 XX MILS XLP 600 VOLTS GW 1 X X AWG 3E AL TYPE MC FOR CT USE SUN. RES. DIRECT BURIAL 90°C USA
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessGroundDiameter Over ArmorJacket ThicknessApprox. ODApprox. WeightJacket Color
    AWG/KcmilNo. of StrandsinchmilNo. x AWGinchmilinchlb/1000ft
    TBA8370.134451 x 80.697500.797304BK
    TBA6370.169451 x 80.772500.872363BK
    TBA4370.213451 x 60.867500.967454BK
    TBA2370.268451 x 60.986501.086579BK
    TBA13190.299551 x 41.096501.196705BK
    TBA1/03190.336551 x 41.176501.276802BK
    TBA2/03190.376551 x 41.263501.363922BK
    TBA3/03190.423551 x 41.364501.4641068BK
    TBA4/03190.475551 x 21.577501.6771438BK
    TBA2503370.52651 x 21.717501.8171654BK
    TBA3003370.57651 x 21.825601.9451895BK
    6716583503350.616651 x 21.951602.0771896BK
    5610535003340.736651 x 12.21602.3362491BK
    6466585003340.736651 x 2502.21602.3362629BK
    TBA6003610.813801 x 12.415602.5353201BK
    6414787503580.908801 x 1/02.651752.8083545BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    TBA835.62971.0711.3340.0524045
    TBA636.14720.6740.840.0515055
    TBA436.87510.4240.5280.0486575
    TBA237.611940.2660.3310.04590100
    TBA138.415060.2110.2630.046100115
    TBA1/038.919000.1670.2080.044120135
    TBA2/039.523950.1330.1660.043135150
    TBA3/0310.230200.1050.1310.042155175
    TBA4/0311.738080.0840.1050.041180205
    TBA250312.745000.070.0870.041205230
    TBA300313.654000.0590.0740.041230260
    671658350314.563000.0510.0640.04250280
    561053500316.490000.0360.0450.039310350
    646658500316.490000.0360.0450.039310350
    TBA600317.7108000.030.0380.039340385
    641478750319.7135000.0230.030.038385435
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.

    Revision: 1.000.007

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC