SPEC 45268

AL 600V PVC-Nylon Insulation PVC Jacket THHN/THWN-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Power Cable 600Volt Four Conductor Aluminum, Polyvinyl Chloride (PVC) with nylon layer insulation THHN Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN
  3. Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE® {UL} 3/0 AWG AL 4 CDRS TYPE TC-ER THHN OR THWN-2 CDRS AL GW 1 X 4 AWG 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {YYYY}
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODAluminum WeightApprox. WeightJacket Color
    AWG/KcmilNo. of StrandsinchmilNo. x AWGmilinchlb/1000ftlb/1000ft
    TBA8470.134351 x 8600.6283185BK
    TBA6470.169351 x 8600.704119240BK
    TBA4470.213501 x 6800.923184398BK
    TBA2470.268501 x 6801.057280533BK
    TBA14190.299601 x 4801.18358669BK
    TBA1/04190.336601 x 4801.27438777BK
    6756332/04120.376501 x 4801.3575461014BK
    6756353/04150.423501 x 4801.4716781187BK
    TBA4/04190.475601 x 2801.6068611309BK
    TBA2504370.52701 x 21101.82310051636BK
    TBA3004350.57701 x 21101.94411931873BK
    TBA3504370.616701 x 21102.05613812105BK
    TBA5004350.736701 x 11102.34619652806BK
    6684515004340.736601 x 11152.35219833038BK
    6732616004410.813701 x 3/01102.57824433652BK
    TBA7504610.908801 x 1/01402.87129254169BK
    5975407504580.908701 x 3/01402.92530144600BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    TBA842.53961.0711.3340.0523236
    TBA642.86290.6740.840.0514044
    TBA443.710010.4240.5280.0485260
    TBA245.315920.2660.3310.0457280
    TBA145.920080.2110.2630.0468092
    TBA1/046.425340.1670.2080.04496108
    6756332/046.831940.1330.1660.043108120
    6756353/047.440270.1050.1310.042124140
    TBA4/04850780.0840.1050.041144164
    TBA25049.160000.070.0870.041164184
    TBA30049.772000.0590.0710.041184208
    TBA350412.384000.0510.0640.04200224
    TBA500414.1120000.0360.0450.039248280
    668451500414.1120000.0360.0450.039248280
    673261600415.5144000.030.0380.039272308
    TBA750417.2180000.0230.030.038308348
    597540750417.5180000.0230.030.038308348
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.006

    Updated On: Oct. 5, 2026, 4:11 p.m. UTC