SPEC 45258

CU 600/1000V XLPE Insulation PVC Jacket XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Power Cable 600 or 1000 Volt Four Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. Silicone Free. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8 (cable size 8 & 6 has insulated green ground)
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE® {UL} XXX KCMIL (XXX{mm2}) CU 4/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG CU 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE {YYYY}
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilNo. x AWGmilinchlb/1000ftlb/1000ft
    5570098470.141451 x 10600.755238403
    5601026470.177451 x 8600.902378613
    5569934470.225451 x 8800.918572804
    5543032470.282451 x 6801.0469091185
    60201114190.322551 x 6801.20211251496
    5544361/04190.361551 x 6801.29913991754
    5569852/04190.405551 x 6801.42017422144
    6020373/04190.456551 x 4801.52122232693
    5544444/04190.512551 x 41101.72127693425
    6020522504370.558651 x 41101.84232484003
    6757133504370.661651 x 11102.08146275524
    6445473504370.661651 x 31102.09345305437
    6020783504370.661651 x 31102.09545305351
    TBA3504370.661651 x 31102.13645255275
    6722375004370.789651 x 1/01102.38265667656
    6757115004370.789651 x 2/01102.38266527742
    6722355004370.789651 x 11102.38264987588
    5544695004370.789651 x 21102.38264437427
    6722405004370.789651 x 4/01102.51168968014
    6757066004610.865801 x 1/01402.72378139264
    6657726004610.865801 x 3501452.858857510061
    6496496004610.865801 x 4/01402.86781449633
    6757086004610.865801 x 2501402.90382639741
    5709617504610.968801 x 11402.962961611320
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    557009843.04220.6530.7860.0524044
    560102643.66710.4110.4950.0515260
    556993443.710680.2580.3100.0486876
    554303245.216980.1620.1950.04592104
    602011146.021420.1280.1540.046104116
    5544361/046.527030.1020.1220.044120136
    5569852/047.134070.0810.0970.043140156
    6020373/047.642950.0640.0780.042160180
    5544444/048.654160.0510.0620.041184208
    60205225049.264000.0430.0530.041204232
    675713350412.589600.0310.0390.040248280
    644547350412.689600.0310.0390.040248280
    602078350412.689600.0310.0390.040248280
    TBA350412.889600.0310.0390.040248280
    672237500414.3128000.0220.0290.039304344
    675711500414.3128000.0220.0290.039304344
    672235500414.3128000.0220.0290.039304344
    554469500414.3128000.0220.0290.039304344
    672240500415.1128000.0220.0290.039304344
    675706600416.3153600.0180.0250.039336380
    665772600417.1153600.0180.0250.039336380
    649649600417.2153600.0180.0250.039336380
    675708600417.4153600.0180.0250.039336380
    570961750417.8192000.0140.0220.038380428
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.003

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC