SPEC 45252

CU 600/1000V XLPE Insulation PVC Jacket XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Power Cable 600 or 1000 Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Copper Ground (Bare or Insulated). CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free.

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8. (When present, cable conductor sizes 8 & 6 AWG have an insulated green ground)
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 383 Flame Test (70,000 btu)
  • Sample Print Legend:

    Bare Ground: {SQFTG} SOUTHWIRE® {UL} XX AWG (X.XX{mm2}) 3/C TYPE TC-ER XHHW-2 CDRS 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE XHHW-2 CT SR 600V 90C

    Green Ground: {SQFTG} SOUTHWIRE® {UL} XX AWG (X.XX{mm2}) CU 3/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG CU GREEN INSULATED 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE XHHW-2 CT SR 600V 90C
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessDiameter Over InsulationGroundJacket ThicknessApprox. ODCopper WeightApprox. WeightJacket Color
    AWG/KcmilNo. of StrandsinchmilinchNo. x AWGmilinchlb/1000ftlb/1000ft
    555196◊8370.142450.236N/A x N/A600.627154283BK
    480590◊8370.142450.2321 x 10600.688187327BK
    5551956370.178450.268N/A x N/A600.714246390BK
    480608◊6370.178450.2681 x 8600.783297467BK
    480616◊4370.225450.3151 x 8600.815442613BK
    480624◊2370.283450.3731 x 6800.982703923BK
    480632◊13190.322550.4321 x 6801.1178651137BK
    480640◊1/03190.362550.4721 x 6801.21310701396BK
    480657◊2/03190.405550.5151 x 6801.30413271684BK
    480665◊3/03190.456550.5661 x 4801.41217002073BK
    480673◊4/03190.512550.6221 x 4801.50721102540BK
    480681◊2503370.558650.6881 x 4801.64124692939BK
    6722063503370.661650.7911 x 11151.91535364258BK
    480707◊3503370.661650.7911 x 31151.91934394088BK
    5880133503370.661650.7911 x 3/01152.11737984531BK
    4807154003370.706650.8361 x 31152.01439064644BK
    5824355003370.789650.9191 x 21102.17748855728BK
    8901485003370.789650.9191 x 1/01152.18950075824BK
    5836975003370.789650.9191 x 2/01152.27450935956BK
    6657666003610.866801.0261 x 1/01152.41859426926BK
    5931736003610.866801.0261 x 3/01152.41861367120BK
    890388◊6003610.866801.0261 x 21152.41858206736BK
    6657686003610.866801.0261 x 4001152.50368607877BK
    6722106003610.866801.0261 x 2501152.54663937418BK
    5544107503610.968801.1281 x 11152.69472778521BK
    5893597503610.968801.1281 x 4/01152.69476768919BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    GG: Green Insulated Ground
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    555196◊832.53960.6530.810.0525055
    480590◊832.83960.6530.810.0525055
    555195632.96290.4110.510.0516575
    480608◊633.16290.4110.510.0516575
    480616◊433.310010.2580.320.0488595
    480624◊233.915920.1620.2010.045115130
    480632◊135.620080.1280.1590.046130145
    480640◊1/036.125340.1020.1270.044150170
    480657◊2/036.531940.0820.1020.043175195
    480665◊3/037.140270.0640.0790.042200225
    480673◊4/037.550780.0510.0630.041230260
    480681◊25038.260000.0430.0530.041255290
    67220635039.684000.0310.0390.04310350
    480707◊35039.684000.0310.0390.04310350
    588013350312.784000.0310.0390.04310350
    480715400312.196000.0270.0350.04335380
    582435500313.1120000.0210.0270.039380430
    890148500313.1120000.0210.0270.039380430
    583697500313.6120000.0210.0270.039380430
    665766600314.5144000.0180.0240.039420475
    593173600314.5144000.0180.0240.039420475
    890388◊600314.5144000.0180.0240.039420475
    665768600315144000.0180.0240.039420475
    672210600315.3144000.0180.0240.039420475
    554410750316.2180000.0140.0190.038475535
    589359750316.2180000.0140.0190.038475535
    *Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.

    Revision: 1.000.012