SPEC 45055

TCU 600/1000V EPR Insulation XHHW-2 Thermoplastic CPE-TP Jacket. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Control Cable, 600/1000 Volt, Tinned Copper Conductors, Ethylene Propylene Rubber (EPR) Insulation XHHW-2, Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket, Control Cable Conductor Identification Method 1 Table 2, VW-1 Rated 14 - 10 AWG, CT Rated, Sunlight Resistant, For Direct Burial, Silicone Free

...

Construction:

  1. Conductor:7-strand class B compressed tinned copper per ASTM B33 and B8
  2. Insulation:Ethylene Propylene Rubber (EPR) Type XHHW-2
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Overall Jacket:Thermoplastic Chlorinated Polyethylene (CPE-TP)

Applications and Features:

Southwire’s 600/1000 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Constructions with 2 conductors are rated TC. VW-1 rated for sizes 14 - 10 AWG. Sunlight Resistant. For Direct Burial. Silicone Free.

Specifications:

  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 44 VW-1 Vertical flame test on individual conductors
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE® XX AWG (X.XX{MM2}) X/C EPR/CPE TYPE TC-ER XHHW-2 CDRS E75755 {UL} 600V/1000V 90°C DRY/90°C WET OIL RES I SUNLIGHT RESISTANT DIRECT BURIAL FT4/IEEE 1202 -- {NOM}-ANCE EPR/CPE Tipo XHHW-2 SR FT4 600V/1000V 90°C USA
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    16 AWG
    591931162730450.33216524.1815.0370.0331.3-18Black
    591932163730450.35124664.1815.0370.0331.4-18Black
    591933164730450.38232824.1815.0370.0331.5-14Black
    591934165730450.415401004.1815.0370.0331.7-14Black
    591935167730450.451561284.1815.0370.0331.8-12Black
    591936169730450.555721784.1815.0370.0332.2-12Black
    5919371612730600.618962254.1815.0370.0332.5-9Black
    5919381615730600.6841202734.1815.0370.0332.7-9Black
    14 AWG
    591944142730450.36625652.6313.1700.0581.52025Black
    591947143730450.38837862.6313.1700.0581.62025Black
    591948144730450.423501072.6313.1700.0581.71620Black
    591949145730450.461621292.6313.1700.0581.81620Black
    591950147730450.502871702.6313.1700.0582.01417Black
    591951149730600.6161122322.6313.1700.0582.51417Black
    5919521412730600.6921502992.6313.1700.0582.81012Black
    5919531415730600.7431873652.6313.1700.0582.21012Black
    5919541419730600.8052374472.6313.1700.0582.21012Black
    5919551425730800.9493326112.6313.1700.0583.8911Black
    TBA1430730800.9953966882.6313.1700.0584.0911Black
    12 AWG
    591959122730450.40440861.6622.0020.0541.62530Black
    591960123730450.466611161.6622.0020.0541.92530Black
    591962124730450.469811471.6622.0020.0541.92024Black
    591963125730450.5431011981.6622.0020.0542.22024Black
    591964127730600.5891422531.6622.0020.0542.41721Black
    591965129730600.5891833071.6622.0020.0542.41721Black
    5919661212730600.7672444111.6622.0020.0543.11215Black
    5919671215730600.8643055421.6622.0020.0543.51215Black
    5919681219730800.9343866591.6622.0020.0543.71215Black
    10 AWG
    591973102730450.448641161.0401.2530.0501.83540Black
    591974103730450.476971601.0401.2530.0501.93540Black
    591976104730450.5601292251.0401.2530.0502.22832Black
    591977105730600.6021612671.0401.2530.0502.42832Black
    591978107730600.6552263551.0401.2530.0502.62428Black
    591979109730600.7652914501.0401.2530.0503.12428Black
    5919801012730800.8993886191.0401.2530.0503.61720Black
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    *Ampacities have been adjusted for more than Three Current-Carrying Conductors.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.015

    Updated On: March 9, 2026, 7:31 p.m. UTC