SPEC 45054

CU 600V XLPE Insulation Thermoplastic LSZH-TP Jacket XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Control Cable 600Volt Copper Conductors, Cross Linked Polyethylene (XLPE) Insulation XHHW-2 Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket, Control Cable Conductor Identification Method 1 Table 2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free.

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2 for cables 14 AWG or larger, 30 Mils thick for all cable sizes
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Overall Jacket:Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket

Applications and Features:

Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. 16 AWG wire is made in accordance with UL 66 Fixture Wire. Sunlight Resistant - For Direct Burial - Silicone Free

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 66 Fixture Wire
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Control, Thermocouple Extension, and Instrumentation Cables (applicable to sizes 20-9 AWG conductors)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    For 16 AWG:
    SOUTHWIRE {UL} AWG XX 7 CDRS TYPE TC-ER XLPE CDRS SOLONON 90C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    For 14 AWG and larger:
    SOUTHWIRE {UL} AWG XX 7 CDRS TYPE TC-ER XHHW-2 CDRS SOLONON 90C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    16 AWG
    TBA16770.05730450.447641284.1815.1890.0331.8-13BK
    14 AWG
    56131214270.07130450.34926672.6313.2650.0581.42025BK
    89015914370.07130450.37438932.6313.2650.0581.52025BK
    56131314470.07130450.403511112.6313.2650.0581.61620BK
    56338314570.07130600.444641352.6313.2650.0581.81620BK
    TBA14670.07130450.489911582.6313.2650.05821620BK
    TBA14770.07130450.4891041772.6313.2650.05821418BK
    TBA14870.07130600.561182142.6313.2650.0582.21418BK
    56131514970.07130600.5881152332.6313.2650.0582.41418BK
    597524141070.07130600.6661282692.6313.2650.0582.71012BK
    563194141970.07130600.7742434412.6313.2650.0583.11012BK
    TBA142070.07130600.8222754632.6313.2650.0583.31012BK
    TBA142570.07130800.9523415982.6313.2650.0583.8911BK
    TBA143070.07130801.0064066982.6313.2650.0585911BK
    12 AWG
    57461512270.08930450.39641921.6622.0630.0541.62530BK
    89012212370.08930450.412611221.6622.0630.0541.62530BK
    56131912470.08930600.445811531.6622.0630.0541.82024BK
    57461212570.08930600.4871021801.6622.0630.0541.92024BK
    TBA12670.08930600.5731412331.6622.0630.0542.32024BK
    57461312770.08930600.5851432651.6622.0630.0542.31821BK
    TBA12870.08930600.6191812911.6622.0630.0542.51821BK
    TBA12970.08930600.6642013221.6622.0630.0542.71821BK
    TBA121070.08930600.7222223551.6622.0630.0542.91215BK
    574614121270.08930600.7562444221.6622.0630.05431215BK
    TBA121570.08930800.8683235291.6622.0630.0543.51215BK
    TBA122070.08930800.9574246751.6622.0630.0543.81215BK
    TBA122570.08930801.065258211.6622.0630.0545.31114BK
    TBA123070.08930801.1216269631.6622.0630.0545.61114BK
    TBA123770.08930801.20976711611.6622.0630.05461012BK
    10 AWG
    56671910270.11330450.444651241.041.2910.051.83540BK
    57714410370.11330450.472971701.041.2910.051.93540BK
    56672010470.11330600.5471292351.041.2910.052.22832BK
    TBA10570.11330600.5931932871.041.2910.052.42832BK
    TBA10670.11330600.6452253331.041.2910.052.62832BK
    TBA10770.11330600.6452583731.041.2910.052.62428BK
    TBA10870.11330600.6992904191.041.2910.052.82428BK
    TBA101070.11330600.8183555111.041.2910.053.31820BK
    574619101270.11330800.9043886411.041.2910.053.61820BK
    TBA101570.11330800.9815167571.041.2910.053.91820BK
    TBA101970.11330801.0316469241.041.2910.055.21820BK
    TBA102070.11330801.0856789721.041.2910.055.41820BK
    TBA102570.11330801.20484011891.041.2910.0561618BK
    TBA103070.11330801.275100113981.041.2910.056.41618BK
    TBA103770.11330801.377122716911.041.2910.056.91416BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    *Ampacities have been adjusted for more than Three Current-Carrying Conductors.
    ! not UL listed
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.008