SPEC 45005
ROYAL GUARD™ CU 600V EPR Insulation Thermoset CPE-TS Jacket RHH/RHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free
Power Cable 600Volt Single Conductor Copper, Lead Free Ethylene Propylene Rubber (EPR) insulation RHH/RHW-2 USE-2 Cross-Linked/Thermoset Chlorinated Polyethylene (CPE-TS) Jacket. CT Rated 1/0 and Larger - For Direct Burial - Sunlight Resistant - Oil Resistant - Silicone Free

Construction:
- Conductor:Class B compressed stranded tinned copper per ASTM B33 and ASTM B8
- Binder Tape:Mylar Tape
- Insulation:Lead Free Ethylene Propylene Rubber (EPR) Type RHH/RHW-2 USE-2
- Overall Jacket:Lead Free & Silicone-Free Cross-Linked/Thermoset Chlorinated Polyethylene (CPE-TS) Jacket
Applications and Features:
Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. CT Rated 1/0 and Larger - Sunlight Resistant - Oil Resistant - Silicone Free.
Specifications:
Sample Print Legend:
SOUTHWIRE® ROYAL GUARD® XX AWG ({mm2}) E32071 {UL} RHH/RHW-2 OR USE-2 90°C 600V SUN RES VW-1 PRI PRII -40°C FT4 -- IEEE 1202 {MM/DD/YY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Strand | Insul. Thickness | Overall Jacket Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity In Raceway 90°C | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mil | mil | inch | lb/1000ft | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | ||
| 592004 | 8 | 7 | 45 | 15 | 0.288 | 80 | 1.2 | 132 | 0.653 | 0.81 | 0.052 | 55 | BK |
| 589493 | 6 | 7 | 45 | 30 | 0.354 | 126 | 1.4 | 209 | 0.411 | 0.51 | 0.051 | 75 | BK |
| 589492 | 4 | 7 | 45 | 30 | 0.404 | 182 | 1.6 | 333 | 0.258 | 0.32 | 0.048 | 95 | BK |
| 652233 | 4 | 7 | 45 | 30 | 0.404 | 182 | 1.6 | 333 | 0.258 | 0.32 | 0.048 | 95 | GN |
| 589491 | 2 | 7 | 45 | 30 | 0.471 | 270 | 1.9 | 530 | 0.162 | 0.201 | 0.045 | 130 | BK |
| 594504 | 2 | 7 | 45 | 30 | 0.471 | 270 | 1.9 | 530 | 0.162 | 0.201 | 0.045 | 130 | GN |
| 589490 | 1 | 19 | 55 | 45 | 0.556 | 356 | 2.2 | 669 | 0.128 | 0.159 | 0.046 | 145 | BK |
| 589495◊ | 1/0 | 19 | 55 | 45 | 0.596 | 433 | 2.4 | 844 | 0.102 | 0.127 | 0.044 | 170 | BK |
| 589496◊ | 2/0 | 19 | 55 | 45 | 0.642 | 528 | 2.6 | 1064 | 0.082 | 0.102 | 0.043 | 195 | BK |
| 594506◊ | 2/0 | 19 | 55 | 45 | 0.642 | 528 | 2.6 | 1064 | 0.082 | 0.102 | 0.043 | 195 | GN |
| 592011◊ | 3/0 | 19 | 55 | 45 | 0.683 | 644 | 2.7 | 1342 | 0.064 | 0.079 | 0.042 | 225 | BK |
| 594507 | 4/0 | 19 | 55 | 45 | 0.748 | 794 | 3 | 1692 | 0.051 | 0.063 | 0.041 | 260 | GN |
| 589500◊ | 4/0 | 19 | 55 | 45 | 0.748 | 795 | 3 | 1692 | 0.051 | 0.063 | 0.041 | 260 | BK |
| 589497◊ | 250 | 37 | 65 | 65 | 0.86 | 975 | 3.4 | 2000 | 0.043 | 0.053 | 0.041 | 290 | BK |
| 589499◊ | 350 | 37 | 65 | 65 | 0.963 | 1313 | 3.9 | 2800 | 0.031 | 0.039 | 0.04 | 350 | BK |
| 589501◊ | 500 | 37 | 65 | 65 | 1.092 | 1817 | 5.5 | 4000 | 0.021 | 0.027 | 0.039 | 430 | BK |
| 595421 | 600 | 61 | 80 | 65 | 1.239 | 2200 | 6.2 | 4800 | 0.018 | 0.024 | 0.039 | 475 | BK |
| 592017◊ | 750 | 61 | 80 | 65 | 1.314 | 2688 | 6.6 | 6000 | 0.014 | 0.019 | 0.038 | 535 | BK |
| 589488 | 1000 | 91 | 80 | 65 | 1.473 | 3505 | 7.4 | 8000 | 0.011 | 0.016 | 0.037 | 615 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Weights and Measurements (Metric)
| Stock Number | Cond. Size | Strand | Insul. Thickness | Jacket Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity In Raceway 90°C | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | kg/km | mm | newton | Ω/km | Ω/km | Ω/km | Amp | ||
| 592004 | 8 | 7 | 1.14 | 0.38 | 7.32 | 119 | 30.48 | 587 | 2.14 | 2.66 | 0.1706 | 55 | BK |
| 589493 | 6 | 7 | 1.14 | 0.76 | 8.99 | 188 | 35.56 | 930 | 1.35 | 1.67 | 0.1673 | 75 | BK |
| 589492 | 4 | 7 | 1.14 | 0.76 | 10.26 | 271 | 40.64 | 1482 | 0.85 | 1.05 | 0.1575 | 95 | BK |
| 652233 | 4 | 7 | 1.14 | 0.76 | 10.26 | 271 | 40.64 | 1482 | 0.85 | 1.05 | 0.1575 | 95 | GN |
| 589491 | 2 | 7 | 1.14 | 0.76 | 11.96 | 402 | 48.26 | 2359 | 0.53 | 0.66 | 0.1476 | 130 | BK |
| 594504 | 2 | 7 | 1.14 | 0.76 | 11.96 | 402 | 48.26 | 2359 | 0.53 | 0.66 | 0.1476 | 130 | GN |
| 589490 | 1 | 19 | 1.40 | 1.14 | 14.12 | 530 | 55.88 | 2977 | 0.42 | 0.52 | 0.1509 | 145 | BK |
| 589495◊ | 1/0 | 19 | 1.40 | 1.14 | 15.14 | 644 | 60.96 | 3756 | 0.33 | 0.42 | 0.1444 | 170 | BK |
| 589496◊ | 2/0 | 19 | 1.40 | 1.14 | 16.31 | 786 | 66.04 | 4735 | 0.27 | 0.33 | 0.1411 | 195 | BK |
| 594506◊ | 2/0 | 19 | 1.40 | 1.14 | 16.31 | 786 | 66.04 | 4735 | 0.27 | 0.33 | 0.1411 | 195 | GN |
| 592011◊ | 3/0 | 19 | 1.40 | 1.14 | 17.35 | 958 | 68.58 | 5972 | 0.21 | 0.26 | 0.1378 | 225 | BK |
| 594507 | 4/0 | 19 | 1.40 | 1.14 | 19.00 | 1182 | 76.20 | 7529 | 0.17 | 0.21 | 0.1345 | 260 | GN |
| 589500◊ | 4/0 | 19 | 1.40 | 1.14 | 19.00 | 1183 | 76.20 | 7529 | 0.17 | 0.21 | 0.1345 | 260 | BK |
| 589497◊ | 250 | 37 | 1.65 | 1.65 | 21.84 | 1451 | 86.36 | 8900 | 0.14 | 0.17 | 0.1345 | 290 | BK |
| 589499◊ | 350 | 37 | 1.65 | 1.65 | 24.46 | 1954 | 99.06 | 12460 | 0.10 | 0.13 | 0.1312 | 350 | BK |
| 589501◊ | 500 | 37 | 1.65 | 1.65 | 27.74 | 2704 | 139.70 | 17800 | 0.07 | 0.09 | 0.1280 | 430 | BK |
| 595421 | 600 | 61 | 2.03 | 1.65 | 31.47 | 3274 | 157.48 | 21360 | 0.06 | 0.08 | 0.1280 | 475 | BK |
| 592017◊ | 750 | 61 | 2.03 | 1.65 | 33.38 | 4000 | 167.64 | 26700 | 0.05 | 0.06 | 0.1247 | 535 | BK |
| 589488 | 1000 | 91 | 2.03 | 1.65 | 37.41 | 5216 | 187.96 | 35600 | 0.04 | 0.05 | 0.1214 | 615 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.