SPEC 25076

AL 1000V LSZH RW90 SOLONONplus™

SOLONONplus™ Single Aluminum Conductor, Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Insulation Type RW90, Sunlight Resistant, 600 or 1000V, 90ºC MAX, -40ºC MIN, Gasoline & Oil Resistant

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series Aluminum ACM in accordance with ASTM B801
  2. Insulation:SOLONONplus™ Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH)

Applications and Features:

Southwire’s 600 or 1000 Volt SOLONONplus™ Type RW 90 VW-1 cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, and aerially when supported by a messenger. These cables are ideal for use in establishments where low smoke and low acid emissions are desired for public safety and health and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA C22.2 No.230 Tray Cables - Rated TC
  • CSA C22.2 No. 2556 / UL 2556 Cable Test Methods
  • CSA SUN RES - for Sunlight Resistant rating
  • CSA ST1 Smoke Test - marked FT4-ST1 (1/0 and Larger)
  • Oil Res I & Sun Res - AWG 8 & Larger
  • Sample Print Legend:

    SOUTHWIRE SOLONONplus (TM) LSZH XLPO 156205 {CSA} XXX AWG (XXX mm2) AL RW90 600/1000V VW-1 HAL-FREE TC PRI PRII GRI GRII -40°C SR FT4 ST-1 {SEQUENTIAL METER MARKS} SEQ METERS [date code]
    Table 1 – Weights and Measurements
    Cond. SizeStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.milinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    27600.358851.43980.2670.3210.045100
    119800.4081091.65020.2110.2540.046115
    1/019800.4461341.76330.1680.2010.044135
    2/019800.4861631.97980.1330.1600.043150
    3/019800.5322002.110060.1050.1260.042175
    4/019800.5842462.312690.0840.1000.041205
    25037900.6502972.615000.0710.0860.041230
    35037900.7454012.921000.0500.0620.040280
    40037900.7894533.124000.0440.0540.040305
    50037900.8655563.430000.0350.0440.039350
    75061901.0688355.345000.0240.0310.038435
    100061901.22010906.160000.0180.0250.037500
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Weights and Measurements (Metric)
    Cond. SizeStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.mmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    271.529.0912635.5617710.881.050.1476100
    1192.0310.3616240.6422340.690.830.1509115
    1/0192.0311.3319943.1828170.550.660.1444135
    2/0192.0312.3424348.2635510.440.520.1411150
    3/0192.0313.5129853.3444770.340.410.1378175
    4/0192.0314.8336658.4256470.280.330.1345205
    250372.2916.5144266.0466750.230.280.1345230
    350372.2918.9259773.6693450.160.200.1312280
    400372.2920.0467478.74106800.140.180.1312305
    500372.2921.9782786.36133500.110.140.1280350
    750612.2927.131243134.62200250.080.100.1247435
    1000612.2930.991622154.94267000.060.080.1214500
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM

    Revision: 1.000.006

    Updated On: Nov. 20, 2024, 9:31 p.m. UTC