SPEC 25075
DURATRAY™ CU 1000V XLPE Insulation. RHH/RHW-2/RW90 UL & CSA
Single Copper Conductors, XLPE Insulation, Sunlight Resistant, 1000V, 90ºC MAX, -40ºC MIN, Gasoline & Oil Resistant

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Cross Linked Polyethylene (XLPE)
Applications and Features:
Suitable for installation in Cable Trays, Underground Duct Banks - As per CE Code limitations. Standard colour is black. Some sizes may be availabe in white, red, blue, yellow, brown, orange or grey. Green Duraground™ also available.
Specifications:
Sample Print Legend:
{SQFTG} E30117 MASTER-DESIGN {UL} XXX AWG CU RHH-RHW-2 1000V FOR CT USE FT4 SR PR I OR PR II 90{D}C WET OR DRY -40{D}C --- {CSA} LL90458 4/0 AWG (107{MM2}) RW90 1000V TC FT4 SR -40{D}C XLPE --- RoHS
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Strand | Insul. Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity In Raceway 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mil | inch | lb/1000ft | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | |
| TBA | 8 | 7 | 60 | 0.262 | 72 | 1 | 132 | 0.653 | 0.81 | 0.052 | 55 |
| TBA | 6 | 7 | 60 | 0.298 | 106 | 1.2 | 209 | 0.411 | 0.51 | 0.051 | 75 |
| TBA | 4 | 7 | 60 | 0.345 | 159 | 1.4 | 333 | 0.258 | 0.32 | 0.048 | 95 |
| TBA | 2 | 7 | 60 | 0.403 | 241 | 1.6 | 530 | 0.162 | 0.201 | 0.045 | 130 |
| 694140 | 1/0 | 19 | 80 | 0.528 | 394 | 2.1 | 844 | 0.102 | 0.127 | 0.044 | 170 |
| 649089◊ | 2/0 | 19 | 80 | 0.572 | 486 | 2.3 | 1064 | 0.082 | 0.102 | 0.043 | 195 |
| 649149 | 3/0 | 19 | 80 | 0.622 | 601 | 2.5 | 1342 | 0.064 | 0.079 | 0.042 | 225 |
| 649098◊ | 4/0 | 19 | 80 | 0.666 | 744 | 2.7 | 1692 | 0.051 | 0.063 | 0.041 | 260 |
| TBA | 250 | 37 | 95 | 0.748 | 882 | 3 | 2000 | 0.043 | 0.053 | 0.041 | 290 |
| 649108◊ | 350 | 37 | 95 | 0.841 | 1216 | 3.4 | 2800 | 0.031 | 0.039 | 0.04 | 350 |
| 649047◊ | 500 | 37 | 95 | 0.966 | 1703 | 3.9 | 4000 | 0.021 | 0.027 | 0.039 | 430 |
| 649049◊ | 750 | 61 | 110 | 1.2 | 2545 | 6 | 6000 | 0.014 | 0.019 | 0.038 | 535 |
| 649131◊ | 1000 | 61 | 110 | 1.349 | 3349 | 6.7 | 8000 | 0.011 | 0.016 | 0.037 | 615 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
†Ampacities derived from the 2015 Canadian Electrical Code - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C. - Table 2 - for Cable in Conduit. Not more than 3 aluminum conductors in a conduit and based on an ambient temperature of 30°C.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Weights and Measurements (Metric)
| Stock Number | Cond. Size | Strand | Insul. Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity In Raceway 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | kg/km | mm | newton | Ω/km | Ω/km | Ω/km | Amp | |
| TBA | 8 | 7 | 1.52 | 6.65 | 107 | 25.40 | 587 | 2.14 | 2.66 | 0.1706 | 55 |
| TBA | 6 | 7 | 1.52 | 7.57 | 158 | 30.48 | 930 | 1.35 | 1.67 | 0.1673 | 75 |
| TBA | 4 | 7 | 1.52 | 8.76 | 237 | 35.56 | 1482 | 0.85 | 1.05 | 0.1575 | 95 |
| TBA | 2 | 7 | 1.52 | 10.24 | 359 | 40.64 | 2359 | 0.53 | 0.66 | 0.1476 | 130 |
| 694140 | 1/0 | 19 | 2.03 | 13.41 | 586 | 53.34 | 3756 | 0.33 | 0.42 | 0.1444 | 170 |
| 649089◊ | 2/0 | 19 | 2.03 | 14.53 | 723 | 58.42 | 4735 | 0.27 | 0.33 | 0.1411 | 195 |
| 649149 | 3/0 | 19 | 2.03 | 15.80 | 894 | 63.50 | 5972 | 0.21 | 0.26 | 0.1378 | 225 |
| 649098◊ | 4/0 | 19 | 2.03 | 16.92 | 1107 | 68.58 | 7529 | 0.17 | 0.21 | 0.1345 | 260 |
| TBA | 250 | 37 | 2.41 | 19.00 | 1313 | 76.20 | 8900 | 0.14 | 0.17 | 0.1345 | 290 |
| 649108◊ | 350 | 37 | 2.41 | 21.36 | 1810 | 86.36 | 12460 | 0.10 | 0.13 | 0.1312 | 350 |
| 649047◊ | 500 | 37 | 2.41 | 24.54 | 2534 | 99.06 | 17800 | 0.07 | 0.09 | 0.1280 | 430 |
| 649049◊ | 750 | 61 | 2.79 | 30.48 | 3787 | 152.40 | 26700 | 0.05 | 0.06 | 0.1247 | 535 |
| 649131◊ | 1000 | 61 | 2.79 | 34.26 | 4984 | 170.18 | 35600 | 0.04 | 0.05 | 0.1214 | 615 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
†Ampacities derived from the 2015 Canadian Electrical Code - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C. - Table 2 - for Cable in Conduit. Not more than 3 aluminum conductors in a conduit and based on an ambient temperature of 30°C.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 3- Stock Code by Color
| Size (AWG / kcmil) | Black | White | Red | Blue | Yellow | Brown | Orange | Grey |
|---|---|---|---|---|---|---|---|---|
| 1/0 | 694140 | 649133 | 649135 | 649138 | TBA | TBA | TBA | TBA |
| 2/0 | 649089 | 649082 | 649084 | 649086 | TBA | TBA | TBA | TBA |
| 3/0 | 649149 | 649142 | 649144 | 649147 | TBA | TBA | TBA | TBA |
| 4/0 | 649098 | 649091 | 649093 | 649096 | TBA | TBA | TBA | TBA |
| 250Kcmil | TBA | TBA | TBA | TBA | TBA | TBA | TBA | TBA |
| 350Kcmil | 649108 | 649101 | 649104 | 649106 | TBA | TBA | TBA | TBA |
| 500Kcmil | 649047 | 649112 | 649114 | 649116 | TBA | TBA | TBA | TBA |
| 750Kcmil | 649049 | 649118 | 649120 | 649122 | TBA | TBA | TBA | TBA |
| 1000Kcmil | 649131 | 649124 | 649126 | 649128 | TBA | TBA | TBA | TBA |