SPEC 25067

DURAGROUND™ CU 1000V XLPE RHH/RHW-2/RW90 UL & CSA FT4 Tray Rated Ground Cable

Single Copper Conductors, XLPE Insulation, Sunlight Resistant, 1000V, 90°C MAX, -40°C MIN, Gasoline & Oil Resistant

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type RW90

Applications and Features:

Suitable for installation in Cable Trays and Underground Duct Banks- As per CE Code limitations (see Rule 12-2202) for grounding and bonding applications.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA SUN RES - for Sunlight Resistant rating
  • CT USE Sizes 1/0 AWG and Larger
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • Sample Print Legend:

    E30117 {UL} XXXX KCMIL CU RHH-RHW-2 1000V FOR CT USE FT4 SR PR I OR PR II 90°C WET OR DRY -40°C --- {CSA} LL90458 XXXX KCMIL (XXX{mm2}) RW90 1000V TC FT4 SR -40°C XLPE --- RoHS {MMM/DD/YYYY}
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.milinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    TBA8760GN0.2627211320.6530.810.05255
    TBA6760GN0.2981061.22090.4110.510.05175
    TBA4760GN0.3451591.43330.2580.320.04895
    6490402760GN0.4092461.65300.1620.2010.045130
    TBA1/01980GN0.5223892.18440.1020.1270.044170
    6490422/01980GN0.5724862.310640.0820.1020.043195
    TBA3/01980GN0.6165942.513420.0640.0790.042225
    6490444/01980GN0.6667442.716920.0510.0630.041260
    TBA2503795GN0.748882320000.0430.0530.041290
    6490553503795GN0.84112163.428000.0310.0390.04350
    6490575003795GN0.96617033.940000.0210.0270.039430
    64905975061110GN1.22545660000.0140.0190.038535
    649062100061110GN1.34933496.780000.0110.0160.037615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    †Ampacities derived from the 2015 Canadian Electrical Code - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C. - Table 2 - for Cable in Conduit. Not more than 3 aluminum conductors in a conduit and based on an ambient temperature of 30°C.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.mmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    TBA871.52GN6.6510725.405872.142.660.170655
    TBA671.52GN7.5715830.489301.351.670.167375
    TBA471.52GN8.7623735.5614820.851.050.157595
    649040271.52GN10.3936640.6423590.530.660.1476130
    TBA1/0192.03GN13.2657953.3437560.330.420.1444170
    6490422/0192.03GN14.5372358.4247350.270.330.1411195
    TBA3/0192.03GN15.6588463.5059720.210.260.1378225
    6490444/0192.03GN16.92110768.5875290.170.210.1345260
    TBA250372.41GN19.00131376.2089000.140.170.1345290
    649055350372.41GN21.36181086.36124600.100.130.1312350
    649057500372.41GN24.54253499.06178000.070.090.1280430
    649059750612.79GN30.483787152.40267000.050.060.1247535
    6490621000612.79GN34.264984170.18356000.040.050.1214615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    †Ampacities derived from the 2015 Canadian Electrical Code - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C. - Table 2 - for Cable in Conduit. Not more than 3 aluminum conductors in a conduit and based on an ambient temperature of 30°C.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.016

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC