SPEC 45311
AL 600/1000V XLPE Insulation AIA PVC Jacket XHHW-2. CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free
Type MC Power Cable 600Volt Three Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free.
Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
- Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polypropylene tape
- Armor:Aluminum Interlocked Armor (AIA)
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Silicone Free.
Specifications:
Sample Print Legend:
{SQFTG_DUAL} SOUTHWIRE {UL} E96627 3/C XXX KCMIL COMPACT AL.--- {ALUMAFLEX}® AA8176 XX MILS XLP 600 VOLTS GW 1 X X AWG 3E AL TYPE MC FOR CT USE SUN. RES. DIRECT BURIAL 90°C USA
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Diameter Over Armor | Jacket Thickness | Approx. OD | Aluminum Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | inch | mil | inch | lb/1000ft | lb/1000ft | ||
TBA | 8 | 3 | 7 | 0.134 | 45 | 1 x 8 | 0.696 | 50 | 0.796 | 137 | 264 |
TBA | 6 | 3 | 7 | 0.169 | 45 | 1 x 8 | 0.771 | 50 | 0.871 | 177 | 322 |
TBA | 4 | 3 | 7 | 0.212 | 45 | 1 x 6 | 0.864 | 50 | 0.964 | 245 | 414 |
TBA | 2 | 3 | 7 | 0.268 | 45 | 1 x 6 | 0.985 | 50 | 1.085 | 335 | 538 |
TBA | 1 | 3 | 19 | 0.298 | 55 | 1 x 4 | 1.093 | 50 | 1.193 | 415 | 664 |
TBA | 1/0 | 3 | 19 | 0.336 | 55 | 1 x 4 | 1.175 | 50 | 1.275 | 490 | 766 |
TBA | 2/0 | 3 | 19 | 0.376 | 55 | 1 x 4 | 1.262 | 50 | 1.362 | 581 | 886 |
TBA | 3/0 | 3 | 19 | 0.422 | 55 | 1 x 4 | 1.361 | 50 | 1.461 | 697 | 1036 |
TBA | 4/0 | 3 | 19 | 0.474 | 55 | 1 x 2 | 1.573 | 60 | 1.693 | 861 | 1283 |
TBA | 250 | 3 | 37 | 0.52 | 65 | 1 x 2 | 1.716 | 60 | 1.836 | 1025 | 1527 |
TBA | 300 | 3 | 37 | 0.569 | 65 | 1 x 2 | 1.822 | 60 | 1.942 | 1277 | 1822 |
671658 | 350 | 3 | 35 | 0.615 | 65 | 1 x 2 | 1.929 | 65 | 2.061 | 1356 | 1976 |
561053 | 500 | 3 | 35 | 0.735 | 65 | 1 x 1 | 2.188 | 65 | 2.320 | 1844 | 2603 |
646658 | 500 | 3 | 35 | 0.735 | 65 | 1 x 250 | 2.188 | 65 | 2.320 | 2002 | 2720 |
TBA | 600 | 3 | 61 | 0.812 | 80 | 1 x 1 | 2.412 | 75 | 2.562 | 2291 | 3243 |
641478 | 750 | 3 | 58 | 0.908 | 80 | 1 x 1/0 | 2.624 | 80 | 2.790 | 2650 | 3630 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Amp | Amp | ||
TBA | 8 | 3 | 5.6 | 297 | 1.072 | 1.290 | 0.034 | 0.052 | 40 | 45 |
TBA | 6 | 3 | 6.1 | 472 | 0.674 | 0.812 | 0.029 | 0.051 | 50 | 55 |
TBA | 4 | 3 | 6.7 | 751 | 0.424 | 0.510 | 0.023 | 0.048 | 65 | 75 |
TBA | 2 | 3 | 7.6 | 1194 | 0.267 | 0.321 | 0.019 | 0.045 | 90 | 100 |
TBA | 1 | 3 | 8.4 | 1506 | 0.211 | 0.254 | 0.021 | 0.046 | 100 | 115 |
TBA | 1/0 | 3 | 8.9 | 1900 | 0.168 | 0.201 | 0.019 | 0.044 | 120 | 135 |
TBA | 2/0 | 3 | 9.5 | 2395 | 0.133 | 0.160 | 0.017 | 0.043 | 135 | 150 |
TBA | 3/0 | 3 | 10.2 | 3020 | 0.105 | 0.126 | 0.015 | 0.042 | 155 | 175 |
TBA | 4/0 | 3 | 11.9 | 3808 | 0.084 | 0.100 | 0.014 | 0.041 | 180 | 205 |
TBA | 250 | 3 | 12.9 | 4500 | 0.071 | 0.086 | 0.015 | 0.041 | 205 | 230 |
TBA | 300 | 3 | 13.6 | 5400 | 0.059 | 0.071 | 0.013 | 0.041 | 230 | 260 |
671658 | 350 | 3 | 14.4 | 6300 | 0.050 | 0.062 | 0.012 | 0.040 | 250 | 280 |
561053 | 500 | 3 | 16.2 | 9000 | 0.035 | 0.044 | 0.010 | 0.039 | 310 | 350 |
646658 | 500 | 3 | 16.2 | 9000 | 0.035 | 0.044 | 0.010 | 0.039 | 310 | 350 |
TBA | 600 | 3 | 17.9 | 10800 | 0.029 | 0.037 | 0.012 | 0.039 | 340 | 385 |
641478 | 750 | 3 | 19.5 | 13500 | 0.024 | 0.031 | 0.011 | 0.038 | 385 | 435 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
Revision: 1.000.007
Updated On: May 8, 2024, 1:57 p.m. UTC