SPEC 60413
Red Alert® Type MC-FPLP Fire Alarm Composite
Copper THHN/THWN or Type TFN Insulated Copper Singles. UL Listed as Type MC and Type FPLP. 600 Volt Type MC and 300 Volt Type FPLP. Rated VW-1. Red Lightweight Aluminum Interlocked Armor.
Construction:
- Conductor:Solid copper per ASTM B3
- Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath, Colors: See Table 1.
- Drain Wire:Tinned drain wire the same size as the pair condutors
- Shield:Aluminum foil with blue laminate
- Binder:Mylar
- Armor:Red Aluminum Interlocked Armor
Applications and Features:
Southwire Red Alert® Type MC-FPLP Cable is suitable for use as follows:
Wiring in Plenums, Ducts or Other Spaces Used for Environmental Air-Handling Purposes per NEC 300.22(C) & 760.135(C). Power-Limited and Non-Power Limited fire alarm circuits, including smoke detectors, bells, horns, fire alarm control panel equipment, and initiation and signaling devices. Class 1, Class 2, and Class 3 remote control, signaling, and power-limited circuits. Power, lighting, control, and signal circuits. Fished or embedded in plaster. Concealed or exposed installations. Places of Assembly per NEC 518.4 and theaters per NEC 520.5. Installation in cable tray and approved raceways. Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(E) Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations. Binder tape with print legend wrapped around assembly. Approved for the State of Rhode Island Fire Systems. Rated at 600V, 90ºC dry as Type MC or 300V, 105ºC dray as Type FPLP. Anti-short bushings are not required for use with MC cable per NEC and UL.
Southwire Red Alert® Type MC-FPLP Cable - meets or exceeds the following requirements:
UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com ) Federal Specification A-A59544 (formerly J-C-30B) NFPA 70 (National Electrical Code), Article 330 Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
Southwire Red Alert® Type MC-FPLP Cable - meets or exceeds the following requirements:
Specifications:
Sample Print Legend:
SOUTHWIRE E96627 XX AWG MC 600V {UL} TYPE (THHN OR TFN) INSULATED CONDUCTORS OR TYPE FPLP {UL} 105°C DRY-FOR USE IN CABLE TRAYS
Table 1 – Weights and Measurements
Stock Number | Composite Number and Size | Cond. Size | Conductor Number | Insulation Thickness | Shielded | Color | Cond. Size | Conductor Number | Insulation Thickness | Shielded | Color | Diameter over Armor | Overall Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mils | AWG/Kcmil | mils | inch | lbs/1000ft | ||||||||
554542 | 2/C #14 and 2/C #16 | 14 | 2 | 20 | NO | Blk/Wht | 16 | 2 | 20 | YES | Blk/Wht | 0.665 | 155 |
554545 | 2/C #14 and 2/C #16 | 14 | 2 | 20 | NO | Blk/Wht | 16 | 2 | 20 | NO | Red/Blu | 0.632 | 138 |
671536 | 2/C #14 and 2/C #16 | 14 | 2 | 20 | NO | Blk/Red | 16 | 2 | 20 | NO | Blk/Red | 0.665 | 146 |
671730 | 2/C #14 and 2/C #16 | 14 | 2 | 20 | NO | Blk/Red | 16 | 2 | 20 | NO | Blk/Red | 0.688 | 152 |
554547 | 2/C #14 and 2/C #16 | 14 | 2 | 20 | NO | Brn/Org | 16 | 2 | 20 | YES | Red/Blu | 0.654 | 153 |
554548 | 2/C #14 and 2/C #18 | 14 | 2 | 20 | YES | Blk/Wht | 18 | 2 | 20 | YES | Red/Blu | 0.636 | 139 |
679360 | 2/C #14 and 2/C #18 | 14 | 2 | 20 | YES | Blk/Wht/Grn | 18 | 2 | 20 | YES | Red/Blu | 0.636 | 139 |
555576 | 2/C #12 and 2/C #16 | 12 | 2 | 20 | NO | Blk/Red | 16 | 2 | 20 | YES | Blk/Wht | 0.703 | 183 |
Table 2 – Electrical and Engineering Data
Stock Number | Composite Number and Size | Conductor Size | DC Resistance @ 25º | AC Resistance @ 75ºC | Capacitance | Cond. Size | DC Resistance @ 25º | AC Resistance @ 75ºC | Capacitance | Min Bend Radius | Allowable Ampacity Raceway 60ºC | Allowable Ampacity Raceway 75ºC | Allowable Ampacity Raceway 90ºC |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
14 | Ohms/1000ft | Ohms/1000ft | pf/ft | AWG/Kcmil | ohms/1000ft | Ohms/1000ft | pf/ft | inch | amps | amps | amps | ||
554542 | 2/C #14 and 2/C #16 | 14 | 2.63 | 3.17 | 57 | 16 | 4.18 | 5.03 | 49 | 4.6 | 15 | 20 | 25 |
554545 | 2/C #14 and 2/C #16 | 14 | 2.63 | 3.17 | 57 | 16 | 4.18 | 5.03 | 49 | 4.4 | 15 | 20 | 25 |
671536 | 2/C #14 and 2/C #16 | 14 | 2.63 | 3.17 | 57 | 16 | 4.18 | 5.03 | 49 | 4.6 | 15 | 20 | 25 |
671730 | 2/C #14 and 2/C #16 | 14 | 2.63 | 3.17 | 57 | 16 | 4.18 | 5.03 | 49 | 4.8 | 15 | 20 | 25 |
554547 | 2/C #14 and 2/C #16 | 14 | 2.63 | 3.17 | 57 | 16 | 4.18 | 5.03 | 49 | 4.5 | 15 | 20 | 25 |
554548 | 2/C #14 and 2/C #18 | 14 | 2.63 | 3.17 | 57 | 18 | 6.66 | 8.03 | 45 | 4.4 | 15 | 20 | 25 |
679360 | 2/C #14 and 2/C #18 | 14 | 2.63 | 3.17 | 57 | 18 | 6.66 | 8.03 | 45 | 4.4 | 15 | 20 | 25 |
555576 | 2/C #12 and 2/C #16 | 12 | 1.66 | 2.00 | 71 | 16 | 4.18 | 5.03 | 49 | 4.9 | 20 | 25 | 30 |