SPEC 60375

Armorlite® Type MC XHHW-2 Aluminum Conductor Feeder Cable. Rated 600 or 1000 Volts. Silicone Free

Aluminum XHHW-2 Insulated Singles with 8000 series Triple E™ Aluminum Alloy. Bare AlumaFlex™ Aluminum Alloy Grounding Conductor. UL Listed. 600 or 1000 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B801
  2. Insulation:All phases are insulated with Cross Linked Polyethylene XLPE Type XHHW-2
  3. Ground:Bare aluminum ground
  4. Filler:Fillers as needed
  5. Binder:Mylar tape
  6. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire Armorlite® Type MC Feeder cable is suitable for use as follows:
  • Feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
  • Fished or embedded in plaster.
  • Concealed or exposed installations.
  • Environmental air-handling spaces per NEC 300.22 (C).
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
  • Installation in cable tray and approved raceways.
  • Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(E)
  • Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
  • Binder tape with print legend wrapped around assembly.
  • Type XHHW-2 rated 90ºC Wet and Dry
  • Per NEC (330.10), unjacketed MC cable can be used in dry location

  • Southwire Armorlite® Type MC Feeder Cable - meets or exceeds the following requirements:
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • Federal Specification A-A59544 (formerly J-C-30B)
  • NFPA 70 (National Electrical Code), Article 330
  • Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
  • Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    E96627 {UL} TYPE MC AWG XX XHHW-2 CDRS FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeDiameter Over ArmorOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchlbs/1000ft
    890092630.1697451x60.844244
    600742430.2127451x60.956314
    557199230.2686451x41.082417
    558064130.2988551x41.101490
    6417931/030.33610551x41.154569
    6787271/030.33610551x6 GG CU1.283656
    5648862/030.37612551x4 GG1.405711
    6787312/030.37612551x6 GG CU1.294727
    6417983/030.42215551x41.311786
    6418004/030.47419551x21.5381037
    64180225030.52022651x21.6561203
    64180530030.56935651x21.7471377
    64180735030.61535651x21.8301549
    64339340030.65935651x11.9261738
    64176440040.65935651x1/02.2032332
    64339650030.73535651x12.0662072
    64339875030.90858801x1/02.4542996
    611203640.1697451x60.925295
    608364440.2127451x61.036382
    557249240.2686451x41.184530
    559963140.2988551x41.322646
    6417242/040.37612551x41.382874
    6417303/040.42215551x41.5841112
    6417364/040.47419551x21.7261356
    64174325040.52022651x11.8831600
    64175030040.56935651x11.9911840
    64175735040.61535651x1/02.1102091
    64177050040.73535651x2/02.3912805
    67177950040.73535651x2/0 GG2.4952861
    64177675040.90858801x3/02.8534096
    677592100041.06061801x6003.5635659
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    GG - Green Ground
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusMax Pull TensionDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 60°CAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesLbsΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    635.94720.6740.8120.051405055
    436.77510.4240.5100.048556575
    237.611940.2670.3210.0457590100
    137.715060.2110.2540.04685100115
    1/038.119000.1680.2010.044100120135
    1/039.019000.1680.2010.044100120135
    2/039.823950.1330.1600.043115135150
    2/039.123950.1330.1600.043115135150
    3/039.230200.1050.1260.042130155175
    4/0310.838080.0840.1000.041150180205
    250311.645000.0710.0860.041170205230
    300312.254000.0590.0710.041195230260
    350312.863000.0500.0620.040210250280
    400313.572000.0440.0540.040225270305
    400415.476800.0440.0540.040180216244
    500314.590000.0350.0440.039260310350
    750317.2135000.0240.0310.038320385435
    646.55030.6740.8120.051324044
    447.38010.4240.5100.048445260
    248.312740.2670.3210.045607280
    149.316060.2110.2540.046688092
    2/049.725550.1330.1600.04392108120
    3/0411.132210.1050.1260.042104124140
    4/0412.140620.0840.1000.041120144164
    250413.248000.0710.0860.041136164184
    300413.957600.0590.0710.041156184208
    350414.867200.0500.0620.040168200224
    500416.796000.0350.0440.039208248280
    500417.596000.0350.0440.039208248280
    750420.0144000.0240.0310.038256308348
    1000424.9192000.0180.0250.037300356400
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.004