SPEC 47302

CSA 3/C CU 2KV Type SHD-GC RHINOSHIELDTM CPE Mining Cable 90°C. MSHA Approved

Flexible Copper conductors, EPR 100% Insulation Level, Cu/Nylon Braid Shield, Extra Heavy Duty Two Layer Chlorinated Polyethylene (CPE) Jacket with Optional Reflective Stripes

...

Construction:

  1. Conductor:Tin coated, soft drawn, annealed, flexible, rope-lay stranded copper per ASTM B33/B172
  2. Separator Tape:Semi-conducting tape applied between the conductor and insulation to facilitate stripping
  3. Insulation:Ethylene Propylene Rubber (EPR) 100% Insulation Level
  4. Braid Shield:Tin coated, soft drawn, annealed, copper braid shield (60% minimum coverage), combined with color coded nylon (black, white, red) with a 40% maximum coverage
  5. Ground Conductors:Two uninsulated, tin coated, soft drawn, annealed, rope stranded, flexible lay copper per ASTM B33/B172
  6. Ground Check Conductor:Tin coated, soft drawn, annealed, rope stranded, flexible lay copper per ASTM B33/B172 with yellow, high strength, polypropylene insulation
  7. Filler:Rubber fillers as needed
  8. Tape:SBR tape applied over the cabled core for improved mechanical integrity and ease of stripping. Reinforcing twine applied between SBR tape and outer jacket
  9. Outer Jacket:Black, mold cured, extra heavy-duty, flame resistant, thermosetting Chlorinated Polyethylene (CPE). Other colors available
  10. Reflective Stripe:Highly visible reflective stripe embedded into the outer jacket to increase safety and help prevent cable runover (optional, contact your sales representative for part number)

Applications and Features:

RHINOSHIELDTM Type SHD-GC is a heavy-duty trailing cable where flexibility and maximum protection is required. For use with mobile, reeling, or stationary mining equipment, continuous mining machines, longwall mining systems, and blast hole drillers. It is also an ex- cellent choice for shovels, draglines, dredges, cranes and marine shore-to-ship power supplies, and anytime extra-durable, flexible cable is required. Suitable for continuous submersion in water. Ground check conductor provides fail-safe ground monitoring. Embossed print legend for easy cable identification. Cold Bend and Impact Tested to -50°C.

Specifications:

  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • CSA C22.2 No. 96 Portable Power Cables
  • ICEA S-75-381 Portable and Power Feeder Cables for Use in Mines
  • MSHA Approved
  • Sample Print Legend:

    SOUTHWIRE (R) RHINOTM BRAND CABLE # AWG CU 3/C EPR TYPE SHD-GC 2000V -50°C 90°C P-07-KA140005 MSHA
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over ConductorInsul. ThicknessDiameter Over InsulationGround Check SizeGround Check StrandsGround Check Insulation ThicknessJacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.No.inchmilinchAWGNo.milmilinchlb/1000ft
    678035143410.077600.21441301250.865369
    569653123650.094700.2351265301570.95493
    5696541031040.118600.2401265301551.00555
    569655831680.155700.30110104401401.06741
    679865631330.21700.35610104401651.247874
    649339432590.256700.48168551801.3781256
    TBA332590.285700.4618168451701.511690
    587868233080.32700.4668168551831.541744
    586860^133850.355800.5128168552401.732250
    5878631/032730.385840.5578168552941.852535
    5849072/033240.42840.5868168552701.9562768
    6413413/034180.506800.6728168552702.133652
    5863874/035320.577840.7518168552642.283880
    65361725036080.611000.8166133602052.484889
    64721735038550.721000.9266133552352.86205
    640977500312210.91001.1066133553473.199022
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ Blue jacket
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive ReactanceInductive ReactanceWorking TensionMin Bending RadiusAllowable Ampacity In Air 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftMΩ/1000ftlbinchAmp
    142.6312.6830.0680.046-6-
    121.661.700.530.040-7-
    101.041.300.0410.051113.000749
    80.6760.8450.0410.039113.000769
    60.4210.5260.0330.036179.0007.793
    40.2670.3340.0280.034285.0008.4122
    30.2120.2650.0260.033360.0009.1140
    20.1680.2100.0240.032454.0009.5159
    10.1330.1660.0240.032572.00010.6184
    1/00.1110.1390.0220.031722.00011.2211
    2/00.0850.1060.0210.031910.00012243
    3/00.0670.0840.0180.0291147.00012.8279
    4/00.0530.0660.0160.028144613.9321
    2500.0450.0560.0170.0291709.00015.1355
    3500.0320.0400.0150.0282393.00016.9435
    5000.0230.0290.0120.0273418.00019.1536
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.