SPEC 10097

CU 600V PVC Insulation PVC Jacket Mini Split Type THWN

CU 600V PVC Insulation PVC Jacket Mini Split Type THWN Rated at 75ºC Wet 90ºC Dry

...

Construction:

  1. Conductor:Solid or stranded bare copper per ASTM B3 or B8
  2. Insulation:Polyvinyl Chloride PVC with Nylon sheath
  3. Filler:Polypropylene filler
  4. Binder:Polyester flat thread binder tape
  5. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free - VW-1 Rated.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wire and Cables (sizes 14 AWG to 1000 kcmil)
  • UL 1277 Electrical Power and Control Tray Cables
  • RoHS-3 Complies with European Directive 2015/863
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE{R} E75755 {UL} XX AWG (X.XX{mm2}) CU 7 CDRS TYPE TC-ER-JP THHN OR THWN CDRS 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {NOM}-ANCE
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.ColorInsul. ThicknessGroundJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°C
    AWGNo.strandsinchmilNo. x AWGmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    16 AWG
    585835163260.056BK, RD, WE, GN201 x 16450.34332724.1815.2822.7-18
    14 AWG
    59540714310.064BK, RD, WE, GN201 x 14450.34850892.6313.3232.72025
    58225714470.070BK, RD, WE, GN20x450.36351942.6313.3232.91620
    40863314770.070BK, RD, BE, OE, YW, BN, RD/BK20x450.413901462.6313.3233.31417
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item

    Revision: 1.000.024

    Updated On: Feb. 9, 2024, 1:41 p.m. UTC