SPEC 10090
CU 150V HVAC Wire Unshielded Thermostat CL2/CMH
CU 150V HDPE Insulation PVC Jacket CL2/CMH Power Limited Unshielded Thermostat Wire
Construction:
- Conductor:Solid bare copper per ASTM B3
- Insulation:High Density Polyethylene HDPE
- Rip Cord:Rip cord for ease of jacket strip ability
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket in Brown
Applications and Features:
Specifications:
Sample Print Legend:
TYPE CL2 C{ETL}US XX AWG XX/C BAROSTAT II SUN RES -- TYPE CMH FT1 -- {MM/DD/YY} {HH:MM}
Table 1 – Physical and Electrical Data
Stock Number | Cond. Size | Cond. Number | Cond. Strands | Diameter Over Cond. | Color | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | DC Resistance @ 25°C | AC Resistance @ 75°C | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG | No. | strands | inch | mil | mil | inch | lb/1000ft | lb/1000ft | Ω/1000ft | Ω/1000ft | |||||||||
20 AWG | |||||||||||||||||||
552020◊ | 20 | 2 | Solid | 0.032 | RD, WE | 5 | 14 | 0.114 | 6 | 9 | 10.503 | 13.269 | |||||||
552030◊ | 20 | 3 | Solid | 0.032 | RD, WE, GN | 5 | 14 | 0.121 | 9 | 13 | 10.503 | 13.269 | |||||||
552040◊ | 20 | 4 | Solid | 0.032 | RD, WE, GN, BE | 5 | 14 | 0.132 | 12 | 16 | 10.503 | 13.269 | |||||||
552050◊ | 20 | 5 | Solid | 0.032 | RD, WE, GN, BE, YW | 5 | 15 | 0.147 | 15 | 20 | 10.503 | 13.269 | |||||||
552060◊ | 20 | 6 | Solid | 0.032 | RD, WE, GN, BE, YW, BN | 5 | 15 | 0.160 | 18 | 24 | 10.503 | 13.269 | |||||||
552070◊ | 20 | 7 | Solid | 0.032 | RD, WE, GN, BE, YW, BN, OE | 5 | 15 | 0.160 | 21 | 27 | 10.503 | 13.269 | |||||||
552080◊ | 20 | 8 | Solid | 0.032 | RD, WE, GN, BE, YW, BN, OE, BK | 5 | 15 | 0.173 | 24 | 30 | 10.503 | 13.269 | |||||||
552100◊ | 20 | 10 | Solid | 0.032 | RD, WE, GN, BE, YW, BN, OE, BK, PK, GY | 5 | 15 | 0.202 | 30 | 38 | 10.503 | 13.269 | |||||||
552120◊ | 20 | 12 | Solid | 0.032 | RD, WE, GN, BE, YW, BN, OE, BK, PK, GY, TN, PE | 5 | 15 | 0.209 | 36 | 42 | 10.503 | 13.269 | |||||||
18 AWG | |||||||||||||||||||
553020◊ | 18 | 2 | Solid | 0.040 | RD, WE | 5 | 14 | 0.132 | 10 | 14 | 6.669 | 8.425 | |||||||
553030◊ | 18 | 3 | Solid | 0.040 | RD, WE, GN | 5 | 14 | 0.140 | 15 | 19 | 6.669 | 8.425 | |||||||
553040◊ | 18 | 4 | Solid | 0.040 | RD, WE, GN, BE | 5 | 14 | 0.154 | 19 | 25 | 6.669 | 8.425 | |||||||
553050◊ | 18 | 5 | Solid | 0.040 | RD, WE, GN, BE, YW | 5 | 15 | 0.170 | 24 | 30 | 6.669 | 8.425 | |||||||
553060◊ | 18 | 6 | Solid | 0.040 | RD, WE, GN, BE, YW, BN | 5 | 15 | 0.186 | 29 | 36 | 6.669 | 8.425 | |||||||
553070◊ | 18 | 7 | Solid | 0.040 | RD, WE, GN, BE, YW, BN, OE | 5 | 15 | 0.186 | 34 | 41 | 6.669 | 8.425 | |||||||
553080◊ | 18 | 8 | Solid | 0.040 | RD, WE, GN, BE, YW, BN, OE, BK | 5 | 15 | 0.202 | 39 | 47 | 6.669 | 8.425 | |||||||
553100◊ | 18 | 10 | Solid | 0.040 | RD, WE, GN, BE, YW, BN, OE, BK, PK, GY | 5 | 15 | 0.238 | 48 | 58 | 6.669 | 8.425 | |||||||
553120◊ | 18 | 12 | Solid | 0.040 | RD, WE, GN, BE, YW, BN, OE, BK, PK, GY, TN, PE | 5 | 15 | 0.245 | 58 | 69 | 6.669 | 8.425 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Revision: 1.000.009
Updated On: Dec. 28, 2023, 4:28 a.m. UTC