SPEC 60515

Titan®2 Type UL Liquidtight Flexible Metal Conduit

Liquidtight Flexible Metal Conduit Metal Conduit. UL Listed. CSA Listed. Oil-Resistant. Sunlight-Resistant. Temperature Rated -55ºC to 80ºC

...

Construction:

  1. Armor:Titan®2 Type HC is manufactured with a spiral wound strip of heavy gauge, corrosion-resistant, hot-dipped galvanized steel. For 3/8" through 1-1/4" trade sizes, the core is constructed with a square locked steel strip with an integral copper-bonding strip enclosed within the steel convolutions.
  2. Jacket:A rugged, flame retardant, flexible PVC jacket is extruded over the steel core. The jacket provides protection from liquids, oil, certain chemicals, temperature, extreme weather and sunlight.

Applications and Features:

Titan®2 Type UL is suitable for the following installations:
  • For extreme temperature environments
  • For the installation and protection of electrical conductors in circuits of 600 Volts nominal, or less.
  • Where the conditions of installation, operation, or maintenance require flexibility or protection from liquids, vapors, solids, or weather
  • Used in industrial and commercial applications for conveyors, blowers, cranes, air conditioners, machine tooling and lubrication equipment
  • Exposed or concealed installations
  • Applications requiring movement, crossover connections, or tight bends
  • Permitted for equipment grounding in sizes 3/8" through 1-1/4" in lengths not exceeding 6 feet per NEC 250.118(6)
  • For flexible connections to swimming pool, spa, and hot tub motors per NEC® 680.21(A)(3) & 680.42(A)(1)
  • Electric signs and outline lighting supply and secondary-circuit conductors per NEC® 600.7, 600.31 (1000 volts or less) & 600.32 (over 1000 volts)
  • Floating building feeders and services per NEC® 553.7
  • Boatyards & Marinas in accordance with NEC® 555.13
  • Cranes & Hoists in accordance with NEC® 610.11(C)
  • For Elevator, Dumbwaiters, Escalators, Moving Walks, Wheel Chair Lifts & Stairway Chair Lifts in accordance with NEC® 620.21 (where expressly permitted)
  • Under raised floors in information technology equipment conductors and cables in accordance with NEC® 645.5 (D) & 645.5(D)(2)
  • Service entrance in lengths up to six feet per NEC® 230.43(15)
  • Electric signs and outline lighting supply and secondary-circuit per NEC 600.31 (1000 Volts or less) & NEC 600.32 (over 1000 Volts)
  • Approved for use in lengths longer than 6 feet per NEC® 356.10(5)

  • Hazardous location:
  • Class I, Div. 2 - NEC® 501.10(B)(2) and 501.30(B)
  • Class II, Div. 1 and 2 - NEC® 502.10(A)(2) and 502.30(B) and NEC 502.10(B)(2)
  • Class III, Div. 1 and 2 - NEC® 503.10(A)(2) and 503.30(B) and NEC 503.10(A)(2)

  • Titan®2 Type HC Features
  • A protective combination of thermoplastic materials formed into a conduit/raceway which seals out water, liquids, abrasives, alcohol, coolants, corrosive fumes and gases, dirt, grease, mineral acids, non-concentrated fixed alkalines, petroleum oils, salt air and spray, and weather
  • Smooth interior for easy wire pulling
  • UV sunlight resistant jacket
  • Rated for temperature range of -30°C to 80°C , 60°C Oil (-22 to +176, 140°F Oil)
  • Accepts standard liquid-tight fittings for use with LFNC-B
  • Rated for direct burial applications including concrete encasement
  • Specifications:

  • UL 360 Liquidtight Flexible Steel Conduit
  • CSA 22.2 No. 56 Flexible metal conduit and liquid-tight flexible metal conduit
  • NFPA 70 (National Electrical Code), Article 350 - Liquidtight Flexible Metal Conduit
  • Titan®2 Type UL
    Trade SizeInner Diam (Min/Max)Outer Diam (Min/Max)WeightMinimum Bend Radius
    InchInchInchLb/100ftInch
    3/80.484/0.5040.690/0.710244.0
    1/20.622/0.6420.820/0.840306.5
    3/40.820/0.8401.030/1.050388.5
    11.041/1.0661.290/1.3156013.0
    1-1/41.380/1.4101.630/1.6608016.0
    1-1/21.575/1.6001.865/1.90011318.0
    22.020/2.0452.340/2.37514922.3
    2-1/22.480/2.5052.840/2.87519729.3
    33.070/3.1003.460/3.50026535.0
    3-1/23.500/3.5403.960/4.00030040.0
    44.000/4.0404.460/4.50031048.0

    Put Ups (Gray)

    TRADE SIZE (Inch)25 ft50 ft100 ft150 ft250 ft400 ft500 ft600 ft1000 ft
    3/8550929035509290155092905
    1/2550826035508260555082602
    3/4550827035508270555082702
    15509300355093004
    1-1/45509330555093303
    1-1/25509320555093201
    25509310555093101
    2-1/25510640155106403
    35510650455106503
    3-1/25510660455106603
    45510670455106702

    Put Ups (Black)

    TRADE SIZE (Inch)25 ft50 ft100 ft150 ft250 ft400 ft500 ft600 ft1000 ft
    3/85529080455290805
    1/2552894045528942155289401
    3/4552896045528960255289601
    15528980155289804
    1-1/45529040255290421
    1-1/25531620355316201
    25529060255290601
    355373704
    455290501

    Revision: 1.000.005

    Updated On: Dec. 11, 2023, 9:29 p.m. UTC