SPEC 44145

Portable Power

Flexible Copper conductors, TPE insulation and Jacket. Sunlight Resistant.

...

Construction:

  1. Conductor:Bare, soft drawn, annealed, flexible, rope-lay stranded copper per ASTM B3/B172. Separator applied to facilitate stripping
  2. Insulation:Heat and moisture resistant TPE
  3. Fillers:Fillers applied as needed to round the cable core
  4. Binder:Paper binder
  5. Jacket:Black TPE (other colors available upon request)

Applications and Features:

Southwire Portable Power cable is for use in flexible, portable indoor and outdoor temporary power, portable industrial machinery and compressors, food processing and wash down facilities. Suitable for use in temperatures between -40ºC to maximum 105ºC.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • UL 1650 Standard for Portable Power Cable
  • CSA C22.2 No. 96 Portable Power Cables
  • Sample Print Legend:

    SOUTHWIRE(R) SEOPRENE(R) XX-X TYPE PPE E172226 (UL) 2000V 90C DRY 75C WET C(UL) TYPE PPC/TPE 2000V -40C TO 105C 75C WET FT1 SUNLIGHT RESISTANT
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over ConductorInsul. ThicknessJacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.No.inchmilmilinchlb/1000ft
    30275124650.09460750.750280
    302901051040.12560750.950473
    30260841680.145601450.989536
    30261642660.186601551.100729
    30281652590.186601401.210912
    30262444200.235601751.2701051
    30282454200.235601551.4191272
    30264246650.290601451.4801519
    302672/0413300.400801601.9302759
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CInductive ReactanceMin Bending RadiusAllowable Ampacity In Air 60°CAllowable Ampacity In Air 75°CAllowable Ampacity In Air 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    121.7742.1370.0543.0212528
    101.0811.3020.0503.8303439
    80.6790.8180.0524.0384652
    60.4350.5240.0515.5506270
    60.4350.5240.0516.1506270
    40.2740.3300.0486.4678191
    40.2740.3300.0487.1678191
    20.1720.2070.0457.490106122
    2/00.0870.1040.0439.7139166190
    * Inductive impedance is based on non-ferrous conduit.
    * Amapcity based on NEC Tare 400.5 (A)(2)

    Revision: 1.000.012