SPEC 44122
4/C CU 2000V EPDM/CPE Type G Industrial Grade Cable 90°C. MSHA Approved
Flexible Copper conductors, Ethylene Propylene Diene Monomer (EPDM) insulation, Single Layer Chlorinated Polyethylene (CPE) Jacket

Construction:
- Conductor:Bare, soft drawn, annealed, flexible, rope-lay stranded copper per ASTM B3/B172
- Separator Tape:Non-conducting tape applied between the conductor and insulation to facilitate stripping
- Insulation:Ethylene Propylene Diene Monomer (EPDM). Color coded black, white, blue, red for sizes #4/0 and smaller and black, white, red, orange for sizes over 250 kcmil
- Ground Conductors:Four insulated, bare, soft drawn, annealed, rope stranded, flexible lay copper per ASTM B3/B172
- Fillers:Jute fillers applied as needed to round the cable core
- Reinforcement Binder:Reinforcing binder with twine applied over the core
- Jacket:Black, flame resistant, thermosetting Chlorinated Polyethylene (CPE)
Applications and Features:
Southwire Type G cable is a heavy-duty industrial cable for use in flexible, portable, and extra-hard usage applications where equipment grounding is required per NEC Article 400. Suitable for continuous submersion in water – ideal for submersible pumps, marine application. Also suitable for use in light to medium-duty mining applications. Sunlight and oil resistant. Highly flexible and easy to work with in cold conditions. Not for use as permanent building wiring. Meets FT-5 Flame Test. cUL Listed.
Specifications:
Sample Print Legend:
2 AWG 4/C TYPE G PORTABLE POWER CABLE 90°C WET OR DRY 2000V OIL AND SUN RES (UL) P-136-35-MSHA AIWTM c(UL) FT1/FT5 (-40°C)
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Cond. Strands | Diameter Over Conductor | Insul. Thickness | Ground | Jacket Thickness | Approx. OD | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | No. | inch | mil | No. x AWG | mil | inch | lb/1000ft | ||
| 562078 | 8 | 4 | 71 | 0.145 | 60 | 4 x 12 | 155 | 0.997 | 704 | BK |
| 571473 | 6 | 4 | 65 | 0.186 | 60 | 4 x 12 | 155 | 1.086 | 867 | BK |
| 571365 | 4 | 4 | 112 | 0.235 | 60 | 4 x 10 | 165 | 1.229 | 1221 | BK |
| 562081 | 2 | 4 | 168 | 0.291 | 60 | 4 x 9 | 182 | 1.454 | 1763 | BK |
| 562083 | 1 | 4 | 224 | 0.3 | 80 | 4 x 8 | 155 | 1.617 | 2130 | BK |
| 562084 | 1/0 | 4 | 259 | 0.379 | 80 | 4 x 7 | 177 | 1.716 | 2541 | BK |
| 562085 | 2/0 | 4 | 324 | 0.4 | 80 | 4 x 6 | 213 | 1.873 | 3150 | BK |
| 560066 | 3/0 | 4 | 418 | 0.48 | 80 | 4 x 5 | 209 | 1.984 | 3769 | BK |
| 562086 | 4/0 | 4 | 532 | 0.53 | 80 | 4 x 4 | 225 | 2.174 | 4597 | BK |
| 571407 | 250 | 4 | 627 | 0.605 | 95 | 4 x 3 | 297 | 2.564 | 5836 | BK |
| 570260 | 350 | 4 | 893 | 0.67 | 95 | 4 x 2 | 375 | 2.877 | 7899 | BK |
| 570261 | 500 | 4 | 1221 | 0.858 | 95 | 4 x 1/0 | 350 | 3.281 | 10482 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance | Max Pull Tension | Min Bending Radius | Allowable Ampacity In Air 60°C | Allowable Ampacity In Air 75°C | Allowable Ampacity In Air 90°C |
|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | Ω/1000ft | Ω/1000ft | Ω/1000ft | lb | inch | Amp | Amp | Amp |
| 8 | 0.654 | 0.812 | 0.052 | 528 | 4 | 38 | 46 | 52 |
| 6 | 0.419 | 0.52 | 0.051 | 839 | 5.4 | 50 | 62 | 70 |
| 4 | 0.263 | 0.326 | 0.048 | 1335 | 6.1 | 67 | 81 | 91 |
| 2 | 0.166 | 0.206 | 0.045 | 2123 | 7.3 | 90 | 106 | 122 |
| 1 | 0.132 | 0.164 | 0.046 | 2678 | 8.1 | 105 | 125 | 142 |
| 1/0 | 0.105 | 0.13 | 0.044 | 3379 | 8.6 | 121 | 145 | 164 |
| 2/0 | 0.084 | 0.104 | 0.043 | 4259 | 9.4 | 139 | 166 | 190 |
| 3/0 | 0.066 | 0.082 | 0.042 | 5369 | 9.9 | 161 | 193 | 219 |
| 4/0 | 0.053 | 0.066 | 0.041 | 6771 | 13 | 186 | 222 | 253 |
| 250 | 0.045 | 0.056 | 0.041 | 8000 | 15.4 | 207 | 248 | 282 |
| 350 | 0.032 | 0.041 | 0.04 | 11200 | 17.3 | 254 | 305 | 346 |
| 500 | 0.022 | 0.029 | 0.039 | 16000 | 19.7 | 314 | 376 | 429 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
Revision: 1.000.002
Updated On: Dec. 31, 2024, 11:07 p.m. UTC