SPEC 10105

Round Water Well Cable Type THW

600V Extreme, Oil-Resistant, Moisture Resistant Conditions. Rated 75°C

...

Construction:

  1. Conductor:Stranded class B compressed bare copper ASTM B8
  2. Insulation:Polyvinyl Chloride (PVC) Type THW
  3. Jacket:Thermoplastic elastomer (TPE)

Applications and Features:

For use in residential, farm and industrial water well applications. Used in both Grounded and ungrounded water well cable systems. Conductors are parallel and insulated with PVC colored black, red, and yellow. Insulated and jacketed with a premium thermoplastic elastomer (TPE) material. Oil resistant. Used in both high temperature and low temperature wells

Specifications:

  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE® SUBMERSIBLE PUMP CABLE TYPE THW XX AWG (X.XX{mm2}) W/GRD 600 VOLTS {UL}
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over ConductorJacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.No.inchmilinchlb/1000ft
    584705123190.088300.448105
    584707103190.113300.498148
    58470963190.177300.709369
    58471043190.225300.811537
    566483124190.088300.494150
    566484104190.113300.550208
    58470884190.141300.632260
    56648584190.141300.670306
    56648664190.177300.764446
    56648744190.225300.856614
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CInductive ReactanceMax Pull TensionMin Bending RadiusAllowable Ampacity In Raceway At 60°CAllowable Ampacity In Raceway At 75°CAllowable Ampacity In Raceway At 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftΩ/1000ftlbinchAmpAmpAmp
    121.6622.0020.0541561.7202530
    101.0401.2530.0502491.9303540
    60.4110.4950.0516292.8556575
    40.2580.3100.04810013.2708595
    121.6622.0020.0541561.9202530
    101.0401.2530.0502492.2303540
    80.6530.7860.0523962.5405055
    80.6530.7860.0523962.6405055
    60.4110.4950.0516293.0556575
    40.2580.3100.04810013.4708595
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.001