SPEC 10103

HI-LO Supreme Parallel Water Well Cable Type THW

600V Extreme, Oil-Resistant, Moisture Resistant Conditions. Rated -50°C to +105°C,

...

Construction:

  1. Conductor:Class K, flexible stranded soft drawn bare copper per ASTM B172
  2. Insulation:Polyvinyl Chloride (PVC) Type THW
  3. Jacket:Thermoplastic elastomer (TPE)

Applications and Features:

For use in residential, farm and industrial water well applications. Used in both Grounded and ungrounded water well cable systems. Conductors are parallel and insulated with PVC colored black, red, and yellow. Insulated and jacketed with a premium thermoplastic elastomer (TPE) material. Oil resistant. Used in both high temperature and low temperature wells

Specifications:

  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • Sample Print Legend:

    SOUTHWIRE® E23919 XX AWG (X.XX{mm2}) {UL} 600V PUMP CABLE 90°C DRY 75°C WET {DD/MM/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over ConductorInsul. ThicknessJacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.No.inchmilmilinchlb/1000ft
    597854142410.07030250.188 x 0.32643
    597858122650.08830250.206 x 0.36263
    5978621021050.11330250.231 x 0.51291
    597765143410.07030250.188 x 0.46465
    597855143410.07030250.188 x 0.46465
    597859123650.08830250.205 x 0.51894
    597856123650.08830250.206 x 0.51894
    5978601031050.11330250.231 x 0.593136
    5978631031050.11330250.231 x 0.593136
    597865831680.14145300.316 x 0.861241
    597766144410.07030250.188 x 0.60287
    597857124650.08830250.206 x 0.674126
    5978611041050.11330250.231 x 0.774181
    597864841680.14145300.316 x 1.01289
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CInductive ReactanceMax Pull TensionAllowable Ampacity In Raceway At 60°CAllowable Ampacity In Raceway At 75°CAllowable Ampacity In Raceway At 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftΩ/1000ftlbAmpAmpAmp
    142.6313.1700.05865152025
    121.6622.0020.054104202530
    101.0401.2530.050166303540
    142.6313.1700.05865152025
    142.6313.1700.05898152025
    121.6622.0020.054156202530
    121.6622.0020.054104202530
    101.0401.2530.050166303540
    101.0401.2530.050249303540
    80.6530.7860.052396405055
    142.6313.1700.05898152025
    121.6622.0020.054156202530
    101.0401.2530.050249303540
    80.6530.7860.052396405055
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.001