SPEC 45314
AL 600/1000V XLPE Insulation AIA PVC Jacket. XHHW-2 Silicone Free
Type MC Power Cable 600Volt Four Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket with 3 Bare AL Ground. Silicone Free.

Construction:
- Conductor: Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
- Grounding Conductor:Three separate ground wires with a combined circular mil of 50% of the phase condutor. Class 4. B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Filler:Paper filler or Polypropylene filler
- Binder:Polypropylene tape
- Armor:Aluminum Interlocked Armor (AIA)
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of op- erating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. The ground is sized to 50% of the phase conductor with three separate bare grounds one in each interstecie between condutors. Silicone Free.
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE MASTER-DESIGN {UL} 4/C 750 KCMIL COMPACT 8000 AL. --- TRIPLE E ALLOY AA8176 XHHW CDRS 600 VOLTS GW 3 X 2/0 AWG 3E AL TYPE MC EZ-JKT FOR CT USE SUN. RES. DIRECT BURIAL 90{D}C
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Diameter Over Insulation | Ground | Diameter Over Armor | Jacket Thickness | Approx. OD | Aluminum Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | inch | No. x AWG | inch | mil | inch | lb/1000ft | lb/1000ft | ||
TBA | 1/0 | 4 | 19 | 0.336 | 55 | 0.446 | 3 x 6 | 1.301 | 50 | 1.401 | 617 | 890 |
TBA | 2/0 | 4 | 19 | 0.376 | 55 | 0.486 | 3 x 6 | 1.398 | 50 | 1.498 | 735 | 1033 |
TBA | 3/0 | 4 | 19 | 0.422 | 55 | 0.532 | 3 x 4 | 1.609 | 60 | 1.729 | 885 | 1254 |
TBA | 4/0 | 4 | 19 | 0.474 | 55 | 0.584 | 3 x 4 | 1.735 | 60 | 1.855 | 1132 | 1535 |
TBA | 250 | 4 | 37 | 0.520 | 65 | 0.650 | 3 x 2 | 1.895 | 60 | 2.015 | 1306 | 1785 |
TBA | 300 | 4 | 37 | 0.569 | 65 | 0.699 | 3 x 2 | 2.013 | 60 | 2.133 | 1517 | 2031 |
TBA | 350 | 4 | 37 | 0.615 | 65 | 0.745 | 3 x 2 | 2.124 | 60 | 2.244 | 1726 | 2274 |
TBA | 500 | 4 | 37 | 0.735 | 65 | 0.865 | 3 x 1 | 2.415 | 75 | 2.565 | 2370 | 3079 |
TBA | 600 | 4 | 61 | 0.812 | 80 | 0.972 | 3 x 1/0 | 2.674 | 75 | 2.824 | 2797 | 3671 |
587658◊ | 750 | 4 | 58 | 0.908 | 80 | 1.068 | 3 x 2/0 | 2.896 | 80 | 3.062 | 3688 | 4896 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | ||
TBA | 1/0 | 4 | 9.8 | 2028 | 0.168 | 0.201 | 0.044 | 80 | 96 | 108 |
TBA | 2/0 | 4 | 10.4 | 2556 | 0.133 | 0.160 | 0.043 | 92 | 108 | 120 |
TBA | 3/0 | 4 | 12.1 | 3222 | 0.105 | 0.126 | 0.042 | 104 | 124 | 140 |
TBA | 4/0 | 4 | 12.9 | 4063 | 0.084 | 0.100 | 0.041 | 120 | 144 | 164 |
TBA | 250 | 4 | 14.1 | 4800 | 0.071 | 0.086 | 0.041 | 136 | 164 | 184 |
TBA | 300 | 4 | 14.9 | 5760 | 0.059 | 0.071 | 0.041 | 156 | 184 | 208 |
TBA | 350 | 4 | 15.7 | 6720 | 0.050 | 0.062 | 0.040 | 168 | 200 | 224 |
TBA | 500 | 4 | 17.9 | 9600 | 0.035 | 0.044 | 0.039 | 208 | 248 | 280 |
TBA | 600 | 4 | 19.7 | 10000 | 0.029 | 0.037 | 0.039 | 228 | 272 | 308 |
587658◊ | 750 | 4 | 21.4 | 10000 | 0.024 | 0.031 | 0.038 | 256 | 308 | 348 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
Revision: 1.000.001
Updated On: Aug. 18, 2023, 2:40 p.m. UTC