SPEC 45252
CU 600/1000V XLPE Insulation PVC Jacket. XHHW-2
Type TC-ER Power Cable 600 or 1000 Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Copper Ground (Bare or Insulated). Silicone Free.

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
- Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8. (When present, cable conductor sizes 8 & 6 AWG have an insulated green ground)
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free.
Specifications:
Sample Print Legend:
Bare Ground: {SQFTG} SOUTHWIRE{R} {UL} XX AWG (X.XX{mm2}) 3/C TYPE TC-ER XHHW-2 CDRS 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE XHHW-2 CT FT4 SR 600V 90C
Green Ground: {SQFTG} SOUTHWIRE{R} {UL} XX AWG (X.XX{mm2}) CU 3/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG CU GREEN INSULATED 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE XHHW-2 CT FT4 SR 600V 90C
Green Ground: {SQFTG} SOUTHWIRE{R} {UL} XX AWG (X.XX{mm2}) CU 3/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG CU GREEN INSULATED 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE XHHW-2 CT FT4 SR 600V 90C
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | mil | inch | lb/1000ft | lb/1000ft | ||
555196◊ | 8 | 3 | 7 | 0.141 | 45 | 60 | 0.627 | 154 | 283 |
480590◊ | 8 | 3 | 7 | 0.141 | 45 | 60 | 0.682 | 186 | 322 |
555195 | 6 | 3 | 7 | 0.177 | 45 | 60 | 0.704 | 245 | 386 |
480608◊ | 6 | 3 | 7 | 0.177 | 45 | 60 | 0.782 | 297 | 466 |
480616◊ | 4 | 3 | 7 | 0.225 | 45 | 60 | 0.806 | 441 | 612 |
480624◊ | 2 | 3 | 7 | 0.282 | 45 | 80 | 0.974 | 702 | 920 |
480632◊ | 1 | 3 | 19 | 0.322 | 55 | 80 | 1.106 | 864 | 1142 |
480640◊ | 1/0 | 3 | 19 | 0.361 | 55 | 80 | 1.192 | 1069 | 1408 |
480657◊ | 2/0 | 3 | 19 | 0.405 | 55 | 80 | 1.287 | 1326 | 1713 |
480665◊ | 3/0 | 3 | 19 | 0.456 | 55 | 80 | 1.391 | 1699 | 2054 |
480673◊ | 4/0 | 3 | 19 | 0.512 | 55 | 80 | 1.494 | 2109 | 2502 |
480681◊ | 250 | 3 | 37 | 0.558 | 65 | 80 | 1.611 | 2469 | 2928 |
672206 | 350 | 3 | 37 | 0.661 | 65 | 110 | 1.885 | 3535 | 4300 |
480707◊ | 350 | 3 | 37 | 0.661 | 65 | 110 | 1.898 | 3438 | 4105 |
588013 | 350 | 3 | 37 | 0.661 | 65 | 110 | 2.081 | 3797 | 4578 |
480715 | 400 | 3 | 37 | 0.705 | 65 | 110 | 2.025 | 3906 | 4726 |
480723◊ | 500 | 3 | 37 | 0.789 | 65 | 110 | 2.155 | 4884 | 5676 |
890148 | 500 | 3 | 37 | 0.789 | 65 | 110 | 2.155 | 5007 | 5904 |
583697 | 500 | 3 | 37 | 0.789 | 65 | 110 | 2.262 | 5092 | 6073 |
593173 | 600 | 3 | 61 | 0.865 | 80 | 110 | 2.436 | 6136 | 7248 |
TBA | 600 | 3 | 61 | 0.865 | 80 | 110 | 2.446 | 5815 | 6970 |
890388◊ | 600 | 3 | 61 | 0.865 | 80 | 110 | 2.453 | 5820 | 6795 |
672210 | 600 | 3 | 61 | 0.865 | 80 | 110 | 2.566 | 6392 | 7564 |
589359 | 750 | 3 | 61 | 0.968 | 80 | 110 | 2.656 | 7676 | 8955 |
554410 | 750 | 3 | 61 | 0.968 | 80 | 110 | 2.656 | 7277 | 8557 |
TBA | 1000 | 3 | 61 | 1.117 | 80 | 140 | 3.038 | 9684 | 11368 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | ||
555196◊ | 8 | 3 | 2.5 | 396 | 0.653 | 0.786 | 0.052 | 40 | 50 | 55 |
480590◊ | 8 | 3 | 2.7 | 396 | 0.653 | 0.786 | 0.052 | 40 | 50 | 55 |
555195 | 6 | 3 | 2.8 | 629 | 0.411 | 0.495 | 0.051 | 55 | 65 | 75 |
480608◊ | 6 | 3 | 3.1 | 629 | 0.411 | 0.495 | 0.051 | 55 | 65 | 75 |
480616◊ | 4 | 3 | 3.2 | 1001 | 0.258 | 0.310 | 0.048 | 70 | 85 | 95 |
480624◊ | 2 | 3 | 3.8 | 1592 | 0.162 | 0.195 | 0.045 | 95 | 115 | 130 |
480632◊ | 1 | 3 | 5.5 | 2008 | 0.128 | 0.154 | 0.046 | 110 | 130 | 145 |
480640◊ | 1/0 | 3 | 5.9 | 2534 | 0.102 | 0.122 | 0.044 | 125 | 150 | 170 |
480657◊ | 2/0 | 3 | 6.4 | 3194 | 0.081 | 0.097 | 0.043 | 145 | 175 | 195 |
480665◊ | 3/0 | 3 | 6.9 | 4027 | 0.064 | 0.078 | 0.042 | 165 | 200 | 225 |
480673◊ | 4/0 | 3 | 7.4 | 5078 | 0.051 | 0.062 | 0.041 | 195 | 230 | 260 |
480681◊ | 250 | 3 | 8.0 | 6000 | 0.043 | 0.053 | 0.041 | 215 | 255 | 290 |
672206 | 350 | 3 | 9.4 | 8400 | 0.031 | 0.039 | 0.040 | 260 | 310 | 350 |
480707◊ | 350 | 3 | 9.4 | 8400 | 0.031 | 0.039 | 0.040 | 260 | 310 | 350 |
588013 | 350 | 3 | 12.4 | 8400 | 0.031 | 0.039 | 0.040 | 260 | 310 | 350 |
480715 | 400 | 3 | 12.1 | 9600 | 0.027 | 0.035 | 0.040 | 280 | 335 | 380 |
480723◊ | 500 | 3 | 12.9 | 10000 | 0.022 | 0.029 | 0.039 | 320 | 380 | 430 |
890148 | 500 | 3 | 12.9 | 10000 | 0.022 | 0.029 | 0.039 | 320 | 380 | 430 |
583697 | 500 | 3 | 13.5 | 10000 | 0.022 | 0.029 | 0.039 | 320 | 380 | 430 |
593173 | 600 | 3 | 14.6 | 10000 | 0.018 | 0.025 | 0.039 | 350 | 420 | 475 |
TBA | 600 | 3 | 14.6 | 10000 | 0.018 | 0.025 | 0.039 | 350 | 420 | 475 |
890388◊ | 600 | 3 | 14.7 | 10000 | 0.018 | 0.025 | 0.039 | 350 | 420 | 475 |
672210 | 600 | 3 | 15.3 | 10000 | 0.018 | 0.025 | 0.039 | 350 | 420 | 475 |
589359 | 750 | 3 | 15.9 | 10000 | 0.014 | 0.022 | 0.038 | 400 | 475 | 535 |
554410 | 750 | 3 | 15.9 | 10000 | 0.014 | 0.022 | 0.038 | 400 | 475 | 535 |
TBA | 1000 | 3 | 18.2 | 10000 | 0.011 | 0.018 | 0.037 | 455 | 545 | 615 |
*Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
Revision: 1.000.002
Updated On: Aug. 18, 2023, 2:40 p.m. UTC